<br />LIGHTING RENOVATION PLAN
<br />1/811 � 1 1-011
<br />GENERAL LIGHTING NOTES
<br />1 . PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT
<br />TO EMERGENCY EGRESS LIGHTS. RUN 3 #12 - 1 #12 GND - 3/4"C TO
<br />INCLUDE UNSWITCHED CONDUCTOR.
<br />2. PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT
<br />TO EXIT SIGNS. RUN 2 # 12 - I # 12 GND - 3/4"C.
<br />3. LIGHT FIXTURES BEING REUSED SHALL BE REPAIRED, CLEANED AND
<br />RELAMPED.
<br />4. SWITCHES SHALL BE GANGED WHEN THEY APPEAR ADJACENT
<br />TO ONE ANOTHER ON PLANS WHEREVER PRACTICABLE. PROVIDE
<br />MULTI -GANG JUNCTION BOX AND COVER PLATE AS REQUIRED.
<br />5. DASHED ARCS INDICATE CONTINUATION OF BRANCH CIRCUIT BUT NOT
<br />SWITCH CONTROL.
<br />6. UNLESS OTHERWISE NOTED, ALL FIXTURES AND DEVICES SHOWN ON
<br />THIS PLAN ARE NEW. ALL NEW FIXTURES AND SWITCHES SHALL
<br />MATCH WELL 65 IN WINTERPARK.
<br />7. VERIFY THAT DIMMER MATCHES LAMP TYPE PRIOR TO ORDER.
<br />& ELECTRICAL CONTRACTOR SHALL PROVIDE A LUMINAIRE DISCONNECT
<br />CONNECTOR FOR ALL FLUORESCENT FIXTURES, AS REQUIRED BY N.E.C,
<br />410.130(g)3 2011. UL LISTED CONNECTORS ARE MANUFACTURER BY
<br />IDEAL, THOMAS AND BETTS AND WAGO, ANY UL LISTED CONNECTOR
<br />WILL BE ACCEPTABLE. INSTALL PER MANUFACTURERS SPECIFICATIONS.
<br />9. EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN FROM FIELD
<br />INVESTIGATION AND/OR ORIGINAL DOCUMENTS AND SHOWN FOR
<br />THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND SHALL NOT
<br />BE CONSIDERED "AS -BUILT" CONDITION. BEFORE CONSTRUCTION
<br />BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL BRANCH
<br />CIRCUITS.
<br />10. CONTRACTOR SHALL INCLUDE COMMISSIONING OF LIGHTING
<br />CONTROL SYSTEM BY MANUFACTURER IN BASE BID,
<br />11. VERIFY CEILING TYPES BEFORE ORDERING LIGHT FIXTURES.
<br />LIGHTING PLAN NOTES
<br />FEED FIXTURES FROM EXISTING, LOCAL LIGHTING CIRCUIT. FIELD
<br />VERIFY EXACT CIRCUIT NUMBER. TYPICAL ALL EXIT SIGNS. RUN
<br />AB 2#12 1 #12 GND - 3/4" C.
<br />PROVIDE A NEW EXTERIOR GRADE BUILDING WALL MOUNTED
<br />LED LIGHT FIXTURE (ANPLIGHTING TYPE
<br />ORB220-FR-MOl 6LDD-W-35K-RTCW) COORDINATE MOUNTING
<br />SOURCE, CORD STYLE AND FINISHES WITH ARCHiTECT/OWNER
<br />PRIOR TO ORDERING. CONNECT ALL BUILDING MOUNTED
<br />LIGHTS TO PANEL VIA TIME CLOCK WITH PHOTOCELL. REFER TO
<br />EXTERIOR LIGHTING/SIGNAGE WIRING DIAGRAM.
<br />"N
<br />ROVIDER WORK
<br />ROOM
<br />F-132--1
<br />- ---� Do
<br />� _J
<br />—OF
<br />ONE --
<br />row
<br />q
<br /><
<br />V
<br />1-21541,
<br />V
<br />1-19
<br />1 7
<br />BI- 5
<br />WELLNESS SUITE
<br />5
<br />WELLN�SS SUITE
<br />WELLNESS SUITE I
<br />Ili's
<br />WELLNESS SUIT
<br />8 1
<br />6
<br />F
<br />7
<br />I
<br />L --------
<br />I?%
<br />f
<br />I OL
<br />9
<br />.02F
<br />HUDDLE
<br />Al-31
<br />E;=
<br />I
<br />W limmmoppo-P
<br />51111 L, i
<br />pffa
<br />924 1,
<br />1. d i
<br />wd
<br />.......... ............................ ..
<br />a El I AUTOCLAVE
<br />Al-18
<br />Ik Wo Ali-16
<br />.0111-111�.Al
<br />&A
<br />=A
<br />INC�
<br />--_� 2 POWER RENOVATION PLAN
<br />E3.1) 1/8" = V-0"
<br />GENERAL POWER NOTES
<br />1 . INDICATED CIRCUIT NUMBERS ARE SUGGESTED FROM EXISTING
<br />SPARE BREAKERS AND SPACES IN EXISTING PANELS.
<br />CONTRACTOR MAY USE DIFFERENT CIRCUIT NUMBERS TO MATCH
<br />FIELD CONDITIONS.
<br />2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH INTERIOR
<br />DESIGN PACKAGE FOR ALL MILLWORK AND WALL DESIGNS PRIOR
<br />TO COMMENCING WORK.
<br />3. EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN FROM FIELD
<br />INVESTIGATION AND /OR ORIGINAL DOCUMENTS AND SHOWN
<br />FOR THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND
<br />SHALL NOT BE CONSIDERED "AS -BUILT" CONDITION. BEFORE
<br />CONSTRUCTION BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD
<br />VERIFY ALL BRANCH CIRCUITS.
<br />4. PROVIDE TYPED, UPDATED PANEL SCHEDULES UPON COMPLETION
<br />OF WORK.
<br />5. PROVDE SHOW WINDOW RECEPTACLES ABOVE ALL WINDOWS
<br />PER CODE LISTED IN THIS NOTE:
<br />• Definition per Article 100 of NEC for Show Window - Any
<br />window, including windows above doors, used or designed
<br />to be used for the display of goods or advertising material,
<br />whether it is fully or partly enclosed or entirely open at the
<br />rear and whether or not it has a platform raised higher
<br />than the street floor level.
<br />• Article 210.62 of NEC Show Windows - provide at least (1)
<br />receptacle within 18in of top of show window for each 12
<br />feet or major faction thereof (6' or more) of show window
<br />measured horizontally.
<br />• Article 210.14(G) and 220.43(A) regarding load calculations
<br />- 210.14(G) allows calculations for unit load per receptacle
<br />(180VA). We will use this method. 220.43(A) is for show
<br />window linear lighting which does not apply.
<br />6. REFER TO FIRE ALARM NOTES, RISER AND SPKIFICATIONS FOR MORE
<br />INFORMATION.
<br />nr:
<br />�q" Of OUTLET BOX
<br />CONFIGURATION 13'
<br />LCD WDAX LOCATION
<br />POWER PLAN NOTES
<br />0
<br />CONNECT ELECTRIC WATER HEATER. PROVIDE 30A, 3P, 240V,
<br />CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE
<br />N-1, NON -FUSED DISCONNECT SWITCH. COORDINATE WITH
<br />MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL
<br />PLUMBING CONTRACTOR. RUN 3#10, 1 #10 GND - 3/4" C.
<br />CONTRACTOR. FAN HAS MOTION SENSOR CONTROL.
<br />PROVIDE FLUSH MOUNTED FLOOR BOX WITH 120V QUAD
<br />CONNECT SPLIT SYSTEM. PROVIDE 30A, 2P, 240V, N-3R FUSED
<br />RECEPTACLE AND TELE/DATA OUTLETS, WALKER OMNIBOX
<br />DISCONNECT SWITCH ON ROOF, FUSE PER MANUFACTURER'S
<br />SERIES (#88OS2-TWO GANG) OR APPROVED EQUAL. SAWCUT
<br />NAMEPLATE. COORDINATE WITH MECHANICAL CONTRACTOR.
<br />FLOOR AS REQUIRED. RUN 2#12, 1 #12 FOR 120V POWER.
<br />ELECTRICAL POWER IS THROUGH CONDENSING UNIT THEN TO
<br />RUN 1-1/4" CONDUIT WITH PULLSTRING FOR LOW VOLTAGE
<br />INDOOR UNIT.
<br />CABLING. PROVIDE ALL ACCESSORIES REQUIRED FOR A
<br />RUN 2 #10 - 1 #10 GND - 3/4"C TO CONDENSING UNIT AND 2
<br />COMPLETE SYSTEM. COORDINATE EXACT LOCATION, FINISHES,
<br />#10 - 1 #10 GND - 3/4"C TO INDOOR UNIT.
<br />COVERPLATES AND TYPE OF LOW VOLTAGE OUTLETS WITH
<br />PROVIDE 30A, 2P, 240V, N-1, FUSED DISCONNECT SWITCH AT
<br />OWNER.
<br />INDOOR UNIT, FUSE AS MANUFACTURER'S NAMEPLATE.
<br />(D
<br />NEW CARD READER AND ELECTRIC STRIKE. PROVIDE 3/4"
<br />(D
<br />EXTEND CONDUIT (2)4"C. TO NEW COMM ROOM.
<br />RACEWAY TO ACCESSIBLE CEILING FOR LOW VOLTAGE POWER.
<br />COORDINATE WITH CARD READER VENDOR. TENANT SECURITY
<br />PROVIDE RECESSED, FLANGELESS BOX WITH DUPLEX
<br />SYSTEM SHALL BE CONNECTED TO BUILDING FIRE ALARM
<br />RECEPTACLE AT HEIGHT SHOWN DRAWING 2/E3.1. ARLINGTON
<br />SYSTEM TO RELEASE ALL LOCKS UPON ACTIVATION. PROVIDE
<br />MODEL #TVBS81 0.
<br />ALL CONNECTIONS AND ACCESSORIES REQUIRED FOR A FULLY
<br />OPERATIONAL SYSTEM. ANY CARD READERS INSTALLED IN
<br />CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE
<br />SUCH A WAY THAT THEY PREVENT FREE EGRESS SHALL BE IN
<br />MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL
<br />COMPLIANCE WITH SECTION 7.2.1.6.2 FOR ACCESS
<br />CONTRACTOR. FAN SHALL RUN CONTINUOUSLY.
<br />CONTROLLED EGRESS DOOR ASSEMBLIES (NFPA 101)
<br />PROVIDE 36" PROPER CLEARANCE PER NEC IN FRONT OF NEW
<br />PROVIDE RECESSED 2-GANG BOX AT 42" A.F.F FOR AV
<br />PANELS.
<br />CABLING. TYPICAL FOR ALL ALL WELLNESS SUITES. ARLINGTON
<br />MODEL #TVBS81 0,
<br />PROVIDE NEW FLOW AND TAMPER SWITCHES ON EXISTING
<br />BACKFLOW PREVENTER. CONNECT PER MANUFATURERS
<br />PROVIDE JUNCTION BOXES AND 120V CIRCUIT FOR DOOR
<br />SPECIFICATIONS.
<br />OPENER. COORDINATE EXACT REQUIREMENTS WITH VENDOR.
<br />REFER TO ARCHITECT'S DRAWING 2/AO.5 FOR RECESSED
<br />PROVIDE 8'H X 4W X 3/4"D PLYWOOD BACK BOARD ON WALL
<br />DRYWALL NICHE. LOCATE DUPLEX RECEPTACLE IN SIDE WALL OF
<br />(D
<br />FOR TELECOMMUNICATION EQUIPMENT. PAINT WITH GRAY FIRE
<br />NICHE AS SHOWN.
<br />RETARDENT PAINT. INSTALL DOUBLE DUPLEX RECEPTACLE
<br />MOUNTED @ 42" AFF. RUN 2" E.C. TO EXISTING MAIN
<br />TELEPHONE TERMINAL BOARD. PROVIDE #6 GROUND WITH
<br />BUS BAR CONNECTED TO BUILDING GROUND LUG.
<br />PA'nENT CARE AREA SYMBOL LEGEND
<br /><0> GENERAL CARE - CATEGORY 2
<br />NOTES:
<br />1. THERE ARE NO CRITICAL OR WET PATIENT AREAS IN THE SCOPE OF WORK.
<br />2, GENERAL PATIENT CARE AREAS REQUIRE A WIRING METHOD WITH A REDUNDANT
<br />GROUND AS PER ARTICLE 517.13 OF THE NEC.
<br />GROUNDING 0 FALL RECEPTACLES, LIGHTING AND FIXED EQUIPMENT IN PATIENT
<br />CARE AREAS SHALL COMPLY WITH NEC ARTICLE 517.13 (A) AND (B)
<br />Al
<br />www.CVDstudio.com
<br />CAMPBELL + VAN DUSEN Design Studio, LLC.
<br />255 South Orange Avenue Suite # 1240
<br />Orlando, Florida 32801
<br />Phone: 407.930.6016
<br />FL. Lic. No. AA26003339
<br />ARCHITECT OF RECORD
<br />FRANK W. CAMPBELL AIA
<br />FLLIC NO. AR0016053
<br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
<br />SEALED AND DATED BY THE ARCHITECT OF RECORD
<br />G. S PA 4,,
<br />r E N
<br />4Z- %
<br />No. 6460'
<br />3
<br />-a STATE OF
<br />ell
<br />Bryan G. Spangler, PE,
<br />FL Reg. No. 64601
<br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
<br />SEALED AND DATED BY THE ENGINEER OF RECORD
<br />I
<br />LJ_
<br />V�
<br />ry
<br />0
<br />F—
<br />q
<br />LU
<br />F—
<br />U
<br />I
<br /><
<br />Q
<br />00
<br />U_1
<br />LU
<br />>
<br />I
<br />0
<br />=
<br />F_
<br />F—
<br />+
<br />LO
<br />U
<br />=
<br />Cie
<br /><
<br />LU
<br />LLJ
<br />0
<br />-0 ,1-
<br />�10 U-)
<br />CL_
<br />U-1
<br />n-I
<br /><
<br />3:
<br />or-01
<br />CL
<br />ru-_41
<br />CI*Yl)l
<br />CONSTRUCTION DOCUMENTS
<br />03.24.2023
<br />PRINCIPAL IN CHARGE
<br />F, CAMPBELL
<br />....................................................................
<br />PROJECT MANAGER
<br />M. TORRES
<br />................................................... ...... .........
<br />ADVENT HEALTH
<br />WELL 65+
<br />ZEPHYRHILLS
<br />22-0328-01
<br />ELECTRICAL
<br />RENOVATION PLANS
<br />NOTE:
<br />CONFIGURATION'A REFERS TO KEYED NOTE
<br />CONFIGURATION 'B' REFERS TO KEYED NOTE (D
<br />11�flll III �i. � I _Tli I lif - I
<br />E3. I
<br />
|