rio (9 <br />LIGHTING RENOVATION PLAN <br />1/811 � 1 1-011 <br />GENERAL LIGHTING NOTES <br />1 . PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT <br />TO EMERGENCY EGRESS LIGHTS. RUN 3 #12 - 1 #12 GND - 3/4"C TO <br />INCLUDE UNSWITCHED CONDUCTOR. <br />2. PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL LIGHTING CIRCUIT <br />TO EXIT SIGNS. RUN 2 # 12 - I # 12 GND - 3/4"C. <br />3. LIGHT FIXTURES BEING REUSED SHALL BE REPAIRED, CLEANED AND <br />RELAMPED. <br />4. SWITCHES SHALL BE GANGED WHEN THEY APPEAR ADJACENT <br />TO ONE ANOTHER ON PLANS WHEREVER PRACTICABLE. PROVIDE <br />MULTI -GANG JUNCTION BOX AND COVER PLATE AS REQUIRED. <br />5. DASHED ARCS INDICATE CONTINUATION OF BRANCH CIRCUIT BUT NOT <br />SWITCH CONTROL. <br />6. UNLESS OTHERWISE NOTED, ALL FIXTURES AND DEVICES SHOWN ON <br />THIS PLAN ARE NEW. ALL NEW FIXTURES AND SWITCHES SHALL <br />MATCH WELL 65 IN WINTERPARK. <br />7. VERIFY THAT DIMMER MATCHES LAMP TYPE PRIOR TO ORDER. <br />& ELECTRICAL CONTRACTOR SHALL PROVIDE A LUMINAIRE DISCONNECT <br />CONNECTOR FOR ALL FLUORESCENT FIXTURES, AS REQUIRED BY N.E.C, <br />410.130(g)3 2011. UL LISTED CONNECTORS ARE MANUFACTURER BY <br />IDEAL, THOMAS AND BETTS AND WAGO, ANY UL LISTED CONNECTOR <br />WILL BE ACCEPTABLE. INSTALL PER MANUFACTURERS SPECIFICATIONS. <br />9. EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN FROM FIELD <br />INVESTIGATION AND/OR ORIGINAL DOCUMENTS AND SHOWN FOR <br />THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND SHALL NOT <br />BE CONSIDERED "AS -BUILT" CONDITION. BEFORE CONSTRUCTION <br />BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL BRANCH <br />CIRCUITS. <br />10. CONTRACTOR SHALL INCLUDE COMMISSIONING OF LIGHTING <br />CONTROL SYSTEM BY MANUFACTURER IN BASE BID, <br />11. VERIFY CEILING TYPES BEFORE ORDERING LIGHT FIXTURES. <br />LIGHTING PLAN NOTES <br />FEED FIXTURES FROM EXISTING, LOCAL LIGHTING CIRCUIT. FIELD <br />VERIFY EXACT CIRCUIT NUMBER. TYPICAL ALL EXIT SIGNS. RUN <br />AB 2#12 1 #12 GND - 3/4" C. <br />PROVIDE A NEW EXTERIOR GRADE BUILDING WALL MOUNTED <br />LED LIGHT FIXTURE (ANPLIGHTING TYPE <br />ORB220-FR-MOl 6LDD-W-35K-RTCW) COORDINATE MOUNTING <br />SOURCE, CORD STYLE AND FINISHES WITH ARCHiTECT/OWNER <br />PRIOR TO ORDERING. CONNECT ALL BUILDING MOUNTED <br />LIGHTS TO PANEL VIA TIME CLOCK WITH PHOTOCELL. REFER TO <br />EXTERIOR LIGHTING/SIGNAGE WIRING DIAGRAM. <br />"N <br />ROVIDER WORK <br />ROOM <br />F-132--1 <br />- ---� Do <br />� _J <br />—OF <br />ONE -- <br />row <br />q <br />< <br />V <br />1-21541, <br />V <br />1-19 <br />1 7 <br />BI- 5 <br />WELLNESS SUITE <br />5 <br />WELLN�SS SUITE <br />WELLNESS SUITE I <br />Ili's <br />WELLNESS SUIT <br />8 1 <br />6 <br />F <br />7 <br />I <br />L -------- <br />I?% <br />f <br />I OL <br />9 <br />.02F <br />HUDDLE <br />Al-31 <br />E;= <br />I <br />W limmmoppo-P <br />51111 L, i <br />pffa <br />924 1, <br />1. d i <br />wd <br />.......... ............................ .. <br />a El I AUTOCLAVE <br />Al-18 <br />Ik Wo Ali-16 <br />.0111-111�.Al <br />&A <br />=A <br />INC� <br />--_� 2 POWER RENOVATION PLAN <br />E3.1) 1/8" = V-0" <br />GENERAL POWER NOTES <br />1 . INDICATED CIRCUIT NUMBERS ARE SUGGESTED FROM EXISTING <br />SPARE BREAKERS AND SPACES IN EXISTING PANELS. <br />CONTRACTOR MAY USE DIFFERENT CIRCUIT NUMBERS TO MATCH <br />FIELD CONDITIONS. <br />2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH INTERIOR <br />DESIGN PACKAGE FOR ALL MILLWORK AND WALL DESIGNS PRIOR <br />TO COMMENCING WORK. <br />3. EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN FROM FIELD <br />INVESTIGATION AND /OR ORIGINAL DOCUMENTS AND SHOWN <br />FOR THE CONVENIENCE OF THE ELECTRICAL CONTRACTOR AND <br />SHALL NOT BE CONSIDERED "AS -BUILT" CONDITION. BEFORE <br />CONSTRUCTION BEGINS, ELECTRICAL CONTRACTOR SHALL FIELD <br />VERIFY ALL BRANCH CIRCUITS. <br />4. PROVIDE TYPED, UPDATED PANEL SCHEDULES UPON COMPLETION <br />OF WORK. <br />5. PROVDE SHOW WINDOW RECEPTACLES ABOVE ALL WINDOWS <br />PER CODE LISTED IN THIS NOTE: <br />• Definition per Article 100 of NEC for Show Window - Any <br />window, including windows above doors, used or designed <br />to be used for the display of goods or advertising material, <br />whether it is fully or partly enclosed or entirely open at the <br />rear and whether or not it has a platform raised higher <br />than the street floor level. <br />• Article 210.62 of NEC Show Windows - provide at least (1) <br />receptacle within 18in of top of show window for each 12 <br />feet or major faction thereof (6' or more) of show window <br />measured horizontally. <br />• Article 210.14(G) and 220.43(A) regarding load calculations <br />- 210.14(G) allows calculations for unit load per receptacle <br />(180VA). We will use this method. 220.43(A) is for show <br />window linear lighting which does not apply. <br />6. REFER TO FIRE ALARM NOTES, RISER AND SPKIFICATIONS FOR MORE <br />INFORMATION. <br />nr: <br />�q" Of OUTLET BOX <br />CONFIGURATION 13' <br />LCD WDAX LOCATION <br />POWER PLAN NOTES <br />0 <br />CONNECT ELECTRIC WATER HEATER. PROVIDE 30A, 3P, 240V, <br />CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE <br />N-1, NON -FUSED DISCONNECT SWITCH. COORDINATE WITH <br />MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL <br />PLUMBING CONTRACTOR. RUN 3#10, 1 #10 GND - 3/4" C. <br />CONTRACTOR. FAN HAS MOTION SENSOR CONTROL. <br />PROVIDE FLUSH MOUNTED FLOOR BOX WITH 120V QUAD <br />CONNECT SPLIT SYSTEM. PROVIDE 30A, 2P, 240V, N-3R FUSED <br />RECEPTACLE AND TELE/DATA OUTLETS, WALKER OMNIBOX <br />DISCONNECT SWITCH ON ROOF, FUSE PER MANUFACTURER'S <br />SERIES (#88OS2-TWO GANG) OR APPROVED EQUAL. SAWCUT <br />NAMEPLATE. COORDINATE WITH MECHANICAL CONTRACTOR. <br />FLOOR AS REQUIRED. RUN 2#12, 1 #12 FOR 120V POWER. <br />ELECTRICAL POWER IS THROUGH CONDENSING UNIT THEN TO <br />RUN 1-1/4" CONDUIT WITH PULLSTRING FOR LOW VOLTAGE <br />INDOOR UNIT. <br />CABLING. PROVIDE ALL ACCESSORIES REQUIRED FOR A <br />RUN 2 #10 - 1 #10 GND - 3/4"C TO CONDENSING UNIT AND 2 <br />COMPLETE SYSTEM. COORDINATE EXACT LOCATION, FINISHES, <br />#10 - 1 #10 GND - 3/4"C TO INDOOR UNIT. <br />COVERPLATES AND TYPE OF LOW VOLTAGE OUTLETS WITH <br />PROVIDE 30A, 2P, 240V, N-1, FUSED DISCONNECT SWITCH AT <br />OWNER. <br />INDOOR UNIT, FUSE AS MANUFACTURER'S NAMEPLATE. <br />(D <br />NEW CARD READER AND ELECTRIC STRIKE. PROVIDE 3/4" <br />(D <br />EXTEND CONDUIT (2)4"C. TO NEW COMM ROOM. <br />RACEWAY TO ACCESSIBLE CEILING FOR LOW VOLTAGE POWER. <br />COORDINATE WITH CARD READER VENDOR. TENANT SECURITY <br />PROVIDE RECESSED, FLANGELESS BOX WITH DUPLEX <br />SYSTEM SHALL BE CONNECTED TO BUILDING FIRE ALARM <br />RECEPTACLE AT HEIGHT SHOWN DRAWING 2/E3.1. ARLINGTON <br />SYSTEM TO RELEASE ALL LOCKS UPON ACTIVATION. PROVIDE <br />MODEL #TVBS81 0. <br />ALL CONNECTIONS AND ACCESSORIES REQUIRED FOR A FULLY <br />OPERATIONAL SYSTEM. ANY CARD READERS INSTALLED IN <br />CONNECT 120V POWER TO NEW EXHAUST FAN. PROVIDE <br />SUCH A WAY THAT THEY PREVENT FREE EGRESS SHALL BE IN <br />MOTOR -RATED SWITCH. COORDINATE WITH MECHANICAL <br />COMPLIANCE WITH SECTION 7.2.1.6.2 FOR ACCESS <br />CONTRACTOR. FAN SHALL RUN CONTINUOUSLY. <br />CONTROLLED EGRESS DOOR ASSEMBLIES (NFPA 101) <br />PROVIDE 36" PROPER CLEARANCE PER NEC IN FRONT OF NEW <br />PROVIDE RECESSED 2-GANG BOX AT 42" A.F.F FOR AV <br />PANELS. <br />CABLING. TYPICAL FOR ALL ALL WELLNESS SUITES. ARLINGTON <br />MODEL #TVBS81 0, <br />PROVIDE NEW FLOW AND TAMPER SWITCHES ON EXISTING <br />BACKFLOW PREVENTER. CONNECT PER MANUFATURERS <br />PROVIDE JUNCTION BOXES AND 120V CIRCUIT FOR DOOR <br />SPECIFICATIONS. <br />OPENER. COORDINATE EXACT REQUIREMENTS WITH VENDOR. <br />REFER TO ARCHITECT'S DRAWING 2/AO.5 FOR RECESSED <br />PROVIDE 8'H X 4W X 3/4"D PLYWOOD BACK BOARD ON WALL <br />DRYWALL NICHE. LOCATE DUPLEX RECEPTACLE IN SIDE WALL OF <br />(D <br />FOR TELECOMMUNICATION EQUIPMENT. PAINT WITH GRAY FIRE <br />NICHE AS SHOWN. <br />RETARDENT PAINT. INSTALL DOUBLE DUPLEX RECEPTACLE <br />MOUNTED @ 42" AFF. RUN 2" E.C. TO EXISTING MAIN <br />TELEPHONE TERMINAL BOARD. PROVIDE #6 GROUND WITH <br />BUS BAR CONNECTED TO BUILDING GROUND LUG. <br />PA'nENT CARE AREA SYMBOL LEGEND <br /><0> GENERAL CARE - CATEGORY 2 <br />NOTES: <br />1. THERE ARE NO CRITICAL OR WET PATIENT AREAS IN THE SCOPE OF WORK. <br />2, GENERAL PATIENT CARE AREAS REQUIRE A WIRING METHOD WITH A REDUNDANT <br />GROUND AS PER ARTICLE 517.13 OF THE NEC. <br />GROUNDING 0 FALL RECEPTACLES, LIGHTING AND FIXED EQUIPMENT IN PATIENT <br />CARE AREAS SHALL COMPLY WITH NEC ARTICLE 517.13 (A) AND (B) <br />Al <br />www.CVDstudio.com <br />CAMPBELL + VAN DUSEN Design Studio, LLC. <br />255 South Orange Avenue Suite # 1240 <br />Orlando, Florida 32801 <br />Phone: 407.930.6016 <br />FL. Lic. No. AA26003339 <br />ARCHITECT OF RECORD <br />FRANK W. CAMPBELL AIA <br />FLLIC NO. AR0016053 <br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED, <br />SEALED AND DATED BY THE ARCHITECT OF RECORD <br />G. S PA 4,, <br />r E N <br />4Z- % <br />No. 6460' <br />3 <br />-a STATE OF <br />ell <br />Bryan G. Spangler, PE, <br />FL Reg. No. 64601 <br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED, <br />SEALED AND DATED BY THE ENGINEER OF RECORD <br />I <br />LJ_ <br />V� <br />ry <br />0 <br />F— <br />q <br />LU <br />F— <br />U <br />I <br />< <br />Q <br />00 <br />U_1 <br />LU <br />> <br />I <br />0 <br />= <br />F_ <br />F— <br />+ <br />LO <br />U <br />= <br />Cie <br />< <br />LU <br />LLJ <br />0 <br />-0 ,1- <br />�10 U-) <br />CL_ <br />U-1 <br />n-I <br />< <br />3: <br />or-01 <br />CL <br />ru-_41 <br />CI*Yl)l <br />CONSTRUCTION DOCUMENTS <br />03.24.2023 <br />PRINCIPAL IN CHARGE <br />F, CAMPBELL <br />.................................................................... <br />PROJECT MANAGER <br />M. TORRES <br />................................................... ...... ......... <br />ADVENT HEALTH <br />WELL 65+ <br />ZEPHYRHILLS <br />22-0328-01 <br />ELECTRICAL <br />RENOVATION PLANS <br />NOTE: <br />CONFIGURATION'A REFERS TO KEYED NOTE <br />CONFIGURATION 'B' REFERS TO KEYED NOTE (D <br />11�flll III �i. � I _Tli I lif - I <br />E3. I <br />