DESIGN LOADS: <br />CAST IN PLACE CONCRETE NOTES: <br />BUILDING CODE: 201 0 EDITION OF FLORIDA BLDG. CODE. <br />SPECIAL INSPECTION REQUIREMENTS: NO <br />DESIGN WIND LOADING CRITERIA. <br />CODE: ASCE7-10 <br />DESIGN BASE WIND SPEED: V(ult) = 148 MPH (3 SEC. GUST) <br />V(asd) = 11 5 MPH (3 SEC. GUST) <br />EXPOSURE CATEGORY "B" <br />INTERNAL PRESS COEFF. = +f-0,18 <br />BUILDING ENCLOSURE CATEGORY = ENCLOSED <br />BUILDING RISK CATEGORY = CATEGORY IV (FIRE STATION) <br />COMPONENT AND CLADDING DESIGN PRESSURES: <br />EVIDENCE SHALL BE SUBMITTED WHICH DOCUMENTS THAT THE GLAZING AND OTHER <br />STRUCTURES WHICH ENCLOSE OPENINGS IN THE BUILDING ENVELOPE (DOORS, WINDOWS, <br />LOUVERS, STOREFRONTS, CURTAINWALLS, SKYLIGHTS, ETC.) HAVE BEEN TESTED <br />SUCCESSFULLY (HAVE SURVIVED FULL SCALE TESTING BY AN ACCREDITED TESTING <br />LABORATORY) TO CONFIRM THAT THE GLAZING AND CONNECTIONS (FASTENING OF THE <br />GLAZING TO THE BUILDING FRAME) MEET THE CRITERIA OF THE 201 0 FLORIDA BUILDING <br />CODE AND THE FOLLOWING <br />GRAVITY DESIGN LOADS: <br />DEAD I OADS* <br />ROOF STRUCTURE = 15 PSIF <br />LIVE LOADS: <br />ROOF - 20 PSF <br />EXTENT OF STRUCTURAL ANALYSIS: <br />THE STRUCTURAL ANALYSIS AND DESIGN PERFORMED ON THIS PROJECT BY WEBER AND <br />TINNEN, P.A , STRUCTURAL ENGINEERS WAS LIMITED TO THAT AREA AND SPECIFICALLY <br />INCLUDED ONLY THOSE ELEMENTS WHICH WERE DIRECTLY EFFECTED BY THE MODIFICATIONS <br />REQUIRED TO ADAPT THE EXISTING BUILDING TO SUIT THE OWNER'S REQUIREMENTS AND <br />CHANGES. NO OTHER STRUCTURAL ANALYSIS OF THE EXISTING BUILDING STRUCTURE(S) WAS <br />PERFORMED AND NONE IS EXPRESSED OR IMPLIED. <br />EXISTING CONDITIONS REPRESENTED BY THESE DOCUMENTS: <br />SHOULD THE GENERAL CONTRACTOR, OR ANY OF HIS SUB -CONTRACTORS OBSERVE OR <br />BECOME AWARE OF ANY EXISTING CONDITION(S) WHICH VARY OR APPEAR TO BE CONTRARY <br />TO THOSE REPRESENTED BY THESE DOCUMENTS, HE SHALL IMMEDIATELY BRING SUCH TO THE <br />ATTENTION OF THE ARCHITECT. DUE CARE WAS EXERCISED IN THE RESEARCH AND <br />PREPARATION OF THESE DOCUMENTS. BUT AS IS OFTEN THE CASE IN RENOVATION AND <br />RETROFIT PROJECTS, SOME EXISTING CONDITIONS REPRESENTED BY THE AVAILABLE <br />ORIGINAL DESIGN AND CONSTRUCTION DOCUMENTS MAY VARY FROM WHATWAS ACTUALLY <br />CONSTRUCTED. IMMEDIATE NOTIFICATION OF TI iE DESIGN TEAM OF SUCH CONDITIONS WILL <br />LESSEN THE IMPACT OF ANY NECESSARY CHANGES OR MODIFICATIONS. ADDITIONALLY, <br />SHOULD THE GENERAL CONTRACTOR, OR ANY OF HIS SUB -CONTRACTORS OBSERVE OR <br />BECOME AWARE OF ANY EXISTING CONDITION(S) WHICH WOULD SUGGEST THE POTENTIAL FOR <br />EXISTING STRUCTURAL DISTRESS OR OVERSTRESS, HE SHALL IMMEDIATELY BRING SUCH TO <br />THE ATTENTION OF THE ARCHITECT. <br />NOTE: IT IS ANTICIPATED THAT THEREWILL BE ADDITIONAL CONDITIONS THAT HAVE NOT BEEN <br />SPECIFICALLY ADDRESSED BYTHE STRUCTURAL DOCUMENTS. GENERALLYA SIMILAR <br />CONDITION WILL HAVE BEEN ADDRESSED STRUCTURALLY AND AN EXISTING <br />CORRECTION DETAIL CAN BE APPLIED TO THE CONDITION IN QUESTION. IF THE <br />REPAIR CANNOT BE CONSIDERED SIMILAR TO AN EXISTING CORRECTION DETAIL, THE <br />CONSTRUCTION MANAGER SHALL CONTACT THE ARCH ITECT/ENGI NEER AND REQUEST <br />THAT THE CONDITION BE OBSERBED AND THAT A NEW CORRECTION DETAIL BE <br />PREPARED TO SPECIFICALLY ADDRESS THE CONDITION. <br />TYPICAL STRUCTURAL CONDITIONS THAT MUST BE REPAIRED/CORRECTED: <br />1. THE CONTINUITY OF THE EXISTING POURED IN PLACE CONCRETETIE BEAM MUST BE <br />RE-ESTABLISHED AT ANY LOCATION WHERE SUCH CONTINUITY HAS BEEN INTERRUPTED. <br />THIS MAY INCLUDE LOCATIONS WHERE THE BEAM WAS CUT OR CHIPPED AWAY TO <br />FACILITATE THE PASSAGE OF DUCTWORK, CRACKING IN THE BEAM DUE TO THE <br />EX PAN SION/CONTRACTI ON AT A SECTION OF REDUCED DEPTH, ETC. <br />NOTE: WHERE A PENETRATION WAS SPECIFICALLY FORMED INTO THE ORIGINAL CONCRETE <br />BEAM POUR AND WHERE (IN ADDITION) THERE IS NO EVIDENCE OF CRACKING OR <br />OTHER DISTRESS IN THE VACINITY OF THE OPENING IN THE BEAM, SUCH REPAIR <br />SHOULD NOT BE REQUIRED. <br />2. CRACKING OR SPALLING OF CONCRETE AT STRUCTURAL SUPPORTS FOR STEEL BEAMS OF <br />BAR JOISTS. <br />3, WHEREVER NEW DUCT OPENINGS ARE TO RE CUT INTO THE MASONRY WAL I BELOW THE <br />EXISTING REINFORCED CONCRETE TIE BEAM: <br />A� SUCH OPENINGS SHALL NOT OCCUR BELOW THE SUPPORT POINT FOR EXISTING <br />CONCRETE BEAMS, STEEL BEAMS OR CHANNELS OR STRUCTURAL STEEL BAR JOISTS <br />WITHOUT THE ERECTION OF SUPPLEMENTARY STRUCTURAL STEEL CHANNELS TO <br />REINFORCE THE EXISTING TIE BEAM, SINCE THE LAP LOCATIONS AND THE LAP <br />LENGTHS OF THE REINFORCING IN THE TIE BEAMS IS UNKNOWN. <br />B. WHERE DUCT PENETRATIONS ARE ADJACENT TO ONEANOTHER, EITHER NEW OR E <br />EXISTING, f HE COLUMN/PIER SECTION BETWEEN ADJACENT DUCI OPENINGS SHALL <br />NOT BE LESS TI IAT 7 5/8" WIDE X 16 INCHES LONG WITH ONE NO. 6 BAR VERTICAL IN <br />EACH CELL SOLID GROUTED IN PLACE. DOWELS SHALL BE DRILLED 8 INCHES INTO THE <br />FOUNDATION AND THE TIE BEAM AND SHALL BE EPDXIED IN PLACE. <br />4. EXISTING MASONRY OPENINGS ORIGINALLY PROVIDED FOR DUCTWORK, WHICH ARE NO <br />LONGER REQUIRED TO REMAIN OPEN, MUST BE SOLIDLY INFILLED WITH CONCRETE <br />MASONRY PURSUANT TO INFILL DETAILS PROVIDED. <br />GENERAL CONSTRUCTION NOTES: <br />1. THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONTRACT DOCUMENTS. <br />THEY SHALL BE RESPONSIBLE FOR THE FIELD COORDINATION OF ARCHITECTURAL, <br />STRUCTURAL, CIVIL, MECHANICAL AND ELECTRICAL TRADES, INCLUDING THE <br />DETAILS AND THE DIMENSIONS. ANY DISCREPANCIES BETWEEN DRAWINGS, DETAILS, <br />DIMENSIONS, ETC., SHALL BE BROUGHT 70 THE ATTENTION OF THE ARCHITECT <br />IMMEDIATELY UPON DISCOVERY AND PRIOR TO COMMENCING CONSTRUCTION OF THE <br />AFFEC I ED AREA. DO NO I SCALE DRAWINGS FOR DIMEN61ONS NOT PROVIDED. REFER I 0 <br />THE ARCHITECTURAL DRAWINGS FOR ANY DIMENSIONS NOT PROVIDED ON THE <br />STRUCTURAL DRAWINGS. <br />2. THE INFORMATION CONTAINED IN THE STRUCTURAL DRAWINGS IS, IN ITSELF, INCOMPLETE <br />AND SHALL BE USED IN CONJUNCTION WITH ALL CONTRACT DOCUMENTS, INCLUDING THE <br />WRITTEN SPECIFICATION, ISSUED IN CONJUNCTION WITH THE DRAWINGS AND ALL <br />REFERENCED CONSTRUCTION MATERIALS INSTITUTE OR ASSOCIATION SPECIFICATIONS, <br />STANDARD PRACTICES, CODES, ETC. <br />3. SPECIFICATIONS INDICATED IN THE STRUCTURAL CONTRACT DOCUMENTS ARE TO BE <br />CONSIDERED MINIMUM ACCEPTABLE CRITERIA AND MAY BE SUPERSEDED BY MORE <br />STRINGENT CRITERIA REQUIRED AS A PART OF THE ARCHITECTURAL CONTRACT <br />4. SECTIONS AND DETAILS ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL <br />APPLY AT ALL SIMILAR LOCATIONS, UNLESS OTHER SECTIONS AND DETAI LS ARE <br />SPECIFICALLY REFERENCED. <br />5. WHERE, IN THE OPINION OF THE CONTRACTOR: <br />A INFORMATION IS UNCLEAR <br />B. INFORMATION IS NOT PROVIDED <br />C. THERE IS A CONFLICT BETWEEN THE DRAWINGS AND THE SPECIFICATION <br />D THERE IS A CONFLICT WITHIN THE DRAWINGS <br />E. THERE 13 A CONFLICT WITHIN THE SPECIFICATIONS <br />THE HIGHER QUALITYAND/OR GREATER QUANTITY OF THE CONFLICTING OPTIONS SHALL <br />GOVERN. IMMEDIATELY AFTER THE DISCOVERY OF SUCH SITUATIONS, THE <br />CONTRACTOR SHALL CONTACT THE ARCHITECTIENGI NEER FOR GUIDANCE. THE <br />ARCHITECT/ENGI NEER IS AND SHALL REMAIN THE FINAL AUTHORITY FOR I NTERPR ETATION <br />OF THE DOCUMENTS IN SITUATIONS OF CONFLICT. <br />6. REFER TO THE ARCHITECTURAL DRAWINGS FOR FINISHED FLOOR ELEVATIONS, SLOPES <br />AND LOCA I ION OF DEPRESSED AREAS.(_;OM PARE VVI I H STRUCTURAL PLANS AND DETAILS <br />AND REPORT ANY DISCREPANCIES TO TI IE ARCHITECT PRIOR TO FABRICATION OR <br />INSTALLATION OF STRUCTURAL WORK. <br />7. ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE 2010 EDITION OF <br />THE FLORIDA BUILDING CODE AND THE WRITTEN SPECIFICATION BOOKLET ISSUED WITH <br />THE DRAWINGS. <br />S. THE SAFETY OF THE WORKERS AND THE CONSTRUCTION SITE IS THE SOLE <br />RESPONSIBILITY OF THE CONTRACTOR. NEITHER THE ARCHITECT NOR THE STRUCTURAL <br />ENGINEER SHALL BE HELD LIABLE FOR ACCIDENTS DURING CONSTRUCTION OF THE <br />PROJECT. THESE DOCUMENTS DO NOT INCLUDE PROVISIONS TO SATISFY SAFETY <br />REQUIREMENTS. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ENSURING <br />CONFORMANCE WITH ALL OSHA STANDARDS. JOB SITE VISITS BY THE ENGINEER SHALL <br />NOT CONSTITUTE APPROVAL, AWARENESS OR LIABILITY FOR ANY HAZARDOUS <br />CONDITIONS. <br />9. IT IS THE SOLE RESPONSIBILITY OF THE CONTRACT OR TO DETERMI NE ERECTION <br />PROCEDURE, MEANS, METHODS AND SEQUENCE OF CONSTRUCTION. IT IS THE SOLE <br />RESPONSIBILITY OF TFIF CONTRACTOR TO ENSURE THE STRUCTURAL STABILITY OF THE <br />BUILDING AND 17S COMPONENT PARTS DURING ALL PHASES OF CONSTRUCTION THIS <br />INCLUDES, BUT IS NOT LIMITED TO THE ADDITION OF ANY NECESSARY TEMPORARY <br />BRACING, GUYING, SHORING, TIE DOWNS, ETC., THAT MAY BE REQUIRED TO RESIST <br />FORCES APPLIED DURING CONSTRUCTION, INCLUDING WIND. <br />10. THE CONTRACTOR SHALL EXERCISE SUCH MEASURES AS ARE REQUIRED TO PROTECT <br />ADJOINING PROPERTY, STRUCTURES, FACILITIES AND UTILITIES FROM DAMAGE <br />DURING CONSTRUCTION. <br />11. THE GENERAL CONTRACTOR SHALL FIELD VERIFYALL DIMENSIONS PRIOR TO BEGINNING <br />CONSTRUCTION THE CONTRACTOR SHALL COORDINATE ALL DIMENSIONS AND <br />ELEVATIONS WITH THE ARCHITECTURAL DRAWINGS. <br />12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER DESIGN AND CONSTRUCTION <br />OF ALL NECESSARY FORMWORK, SHORING, RESHORING AND UNDERPINNING, WHICH IS <br />REQUIRED TO SAFELY CONSTRUCT THE STRUCTURE. THE CONTRACTOR IS RESPONSIBLE <br />FOR ANY DAMAGE CAUSED BY THE INSTALLATION OF ANY TEMPORARY SHORING AND/CR <br />UNDERPINNING. THE DESIGN OF ANY REQUIRED FORMWORK, SHORING, RESHORING, <br />UNDERPINNING, ETC., SHALL BE PROVIDED BY A PROFESSIONAL ENGINEER CURRENTLY <br />REGISTEREDIN I HE SIAIE OF FLORIDA (WHOSE TRAINING AND PRACTICE EXPERIENCE IS <br />STRUCTURAL ENGINEERING). DESIGN CALCULATIONS AND ERECTION DRAWING (WHICH <br />SHALL BEAR HIS SEAL, SIGNATURE AND THE DATE. SHALL BE SUBMITTED TO THE <br />ARCHITECT AND RESPONSIBLE BUILDING AUTHORITY. <br />13. THE CONTRACTOR HAS THE FULL RESPONSIBILITY FOR PROVIDING ANY AND ALL BRACING <br />NECESSARY TO MAINTAIN STABILITY AND STRUCTURAL INTEGRITY OF WALLS DURING <br />CONSTRUCTION. RETAINING WALLS (IF ANY) SHALL BE BRACED PRIOR TO AND DURING ALL <br />COM PACTI NG AN D BACKFI LLI NG OPERATI ONS. <br />14. NO MODIFICATION OF ANY STRUCTURAL MEMBER SHALL BE PERMITTED WITHOUT FIRST <br />OBTAINING NOTIFICATION IN WRITING FROM THE STRUCTURAL ENGINEER THAT SUCH <br />N40DIFICATION IS PERMISSIBLE. THIS INCLUDES ANY MODIFICATION WHICH MAY <br />ADVERSELY AFFECT THE STRENGTH OF THE MEMBER. <br />SHOP DRAWING SUBMITTALS: <br />SHOP DRAWINGS ARE AN AID FOR FIELD PLACEMENT AND ARE SUPERSEDED BY THE <br />STRUCTURAL DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE <br />CERTAIN THAT ALL CONSTRUCTION IS IN FULL AGREEMENTWITH THE LATEST STRUCTURAL <br />DRAWINGS. REVIEW OF SHOP FABRICATION AND ERECTION DRAWINGS BY THE ARCHITECT AND <br />STRUCTURAL ENGINEER IS FOR COORDINATION OF REVISIONS, INTERPRETATION REQUESTS <br />AND FOR VERIFICATION OF THE FABRICATOR'S UNDERSTANDING OF MAJOR DESIGN <br />REQUIREMENTS. IT IS 1 HE RL6PONSIBILI FY OF THE CONTRACTOR TO APPROVE FOR SAME AS <br />ABOVE AND, IN ADDITION, TO REVIEW FOR DETAIL DESIGN REQUIREMENTS AND DIMENSIONS. <br />A/E REVIEW WILL NOT COVER DIMENSIONS OR DETAIL DESIGN REQUIREMENTS, SUCH AS <br />LENGTHS, QUANTITIES, ETC. THIS REVIEW NEITHER GUARANTEES THAT THE SHOP DRAWINGS <br />ARE CORRECT NOR INFERS THAT THE SHOP DRAWINGS SUPERSEDE THE STRUCTURAL <br />DRAWINGS. AlE REVIEW WILL NOT COMMENCE UNTIL ALL OF THE FCLLOWI NG REQUIREMENTS <br />ARESATISFIEDI <br />1. ALL SUBMITTALS SHALL INCLUDE ONE SET OF REPRODUCIBLES & TWO SETS OF PRINTS FOR <br />REVIEW AND FILE IN AfE OFFICE. THE REPRODUCIBLES WILL BE MARKED TO INDICATE ANY <br />NOTED DISCREPANCIES AND/OR ERRORS. THE REPRODUCIBLES WILL BE RETURNED TO THE <br />CONTRACTOR FOR PRINTING OF DISTRIBUTION SETS. <br />NOTE: SUBMITTALS MADE IN ANY FORM OTHER THAN THAT REQUESTED WILL BE REJECTED <br />AND RETURNED TO THE CONTRACTOR WITHOUT ANY REVIEW. A PROPER SUBMITTAL <br />WILL BE REQUESTED AND NO ACTION WILL BETAKEN UNTIL A rRorER SUBMITTAL IS <br />RECEIVED. <br />NOTE FAXED OR E-MAILED SUBMITTALS ARE UNACCEPTABLE AND WILL NOT BE REVIEWED. <br />NOTE ANY DELAYS CAUSED RY IMPROPER SUBMITTALS WILL BE THE SOLE RESPONSIBILITY <br />OF THE CONTRACTOR. <br />2. SHOP DRAWINGS SHALL NOT BE PREPARED UTILIZING REPRODUCTIONS OF THE CONTRACT <br />DOCUMENTS. SUCH SUBMITTALS WILL BE RETURNED WITHOUT ANY REVIEW AND WILL <br />REQUIRE RESUBMITTAL. <br />3. SUBMITTED DRAWINGS MUST BE COMPLETE, NOT PROGRESS PRIN-1 SI SUBMIT -FED <br />DRAWINGS MUST HAVE BEEN CHECKED, APPROVED, DATED, AND INITIALED BY BOTH THE <br />DETAILER AND THE PERSON IN RESPONSIBLE CHARGE OF FINAL REVIEW AND APPROVAL OF <br />THE SHOP DRAWINGS IN THE FABRICATORS OFFICE. <br />4. THE CONTRACTOR SHALL HAVE REVIEWED AND APPROVED THE SHOP DRAWINGS PRIOR TO <br />SURMITTING FOR A/E REVIEW THF PROJECT MANAGER SHALL INDICATE (EITHER RY COVER <br />LETTER OR BY WRITTEN STATEMENT ON EACH SHEET OF DRAWINGS SUBMITTED) <br />FOLLOWING NOTE: <br />"THESE SHOP DRAWINGS AND ALL WORK TO BE PERFORMED MEET OR EXCEED THE <br />REQUIREMENTS OF THE CONTRACT DOCUMENTS IN ALL RESPECTS". STATEMENT <br />SHALL BE SIGNED AND DATED BYTHE PROJECT MANAGER. <br />5. SUBMITTALS SHALL PROVIDE FOR AT LEAST FOURTEEN (14) WORKING DAYS IN THE <br />ENGINEERS OFFICE FOR REVIEW. FOURTEEN DAYCLOCKWILL NOT START UNTIL RECEIPT <br />OF PROPER SUBMI I IAL. PHASED SUBMITTALS AND SMALLER PACKAGES ARE MORE EASILY <br />AND QUICKLY RETURNED. <br />6. NOTE THAT THE CONTRACTOR'S (OR SUB -CONTRACTOR'S) FAILURE TO SUBMIT SHOP <br />DRAWINGS IN A TIMELY MANNER (PROVIDING FOR THE REQUIRED REVIEW TIME IN THE <br />ENGINEER'S OFFICE) WILL NOT CONSTITUTE AN EMERGENCY AND AN IMMEDIATE <br />REVI EW BY THE ENGINEER! <br />THE CONTRAC70R AND SUB -CONTRACTORS SHALL ASSUME FULL RESPONSIBILITY, <br />UNRELIEVED BY REVIEW OF SHOP DRAWINGS AND DOCUMENTS, FOR: DIMENSIONS: <br />HER TRADES' FABRICATION PROCESSES- CONSTRUCTION TECHNIQUES, <br />SAFETY CONDITIONS; AND FULFILLING DETAIL REQUIREMENTS'OFTHEIR CONTRACT. <br />GENERAL SPREAD FOOTING FOUNDATION NOTES: <br />1. THE DESIGN SCIIJIFOUNDATION CONTACT PRESSURE = 1500 PSF. IF DURING THE <br />EXCAVATION, THE CONTRACTOR OBSERVES ANYTHING THATWOULD INDICATE POOR SOIL <br />BEARING CONDITIONS, IT MAY BE NECESSARYTO HAVE THE ASSUMMED BEARING <br />PRESSURE SHALL BE VERIFIED BY AT LEAST ONE 25 FEET DEEP STANDARD PENETRATION <br />TEST BORINGS AND A GEOTECHNICAL REPORT PERFORM ED/PREPARED BY A <br />GEOTECHNICAL ENGINEER HOLDING CURRENT REGISTRATION IN THE STATE OF FLORIDA <br />AS A PROFESSIONAL ENGINEER. THE REPORT SHALL BE SIGNED AND SEALED BY THE <br />GEOTECHNICAL P.E. TI IE REPORT SHALL CONTAIN SPECIFIC DETAILED SITEWORK <br />INSTRUCTIONS AND PROCEDURES WHICH ARE REQUIRED AS A PART OF THE FOUNDATION <br />CONSTRUCTION AND SHALL BE FOLLOWED BY THE GENERAL CONTRACTOR. <br />2. ALL FILL MATERIAL SHALL BE PLACED AND COMPACTED IN STRICT CONFORMANCE WITH <br />THE GEOTECHNICAL REPORT PREPARED FOR THE PROJECT. IN NO INSTANCE SHALL FILL <br />MATERIAL BE PLACED AND COMPACTED IN INDIVIDUAL LIFT DEPTHS EXCEEDING 12 INCHES <br />UNLESS SPECIFICALLY DIRECTED TO DO SO IN WRITING BY THE PROJECT GEOTECHNICAL <br />ENGINEER. IN NO INSTANCE SHALL FILL MATERIAL AND NATURAL SUBGRADE MATERIAL <br />(UPON WHICH FOUNDATIONS AND/OR SLABS ON GRADE ARE 70 BE SUPPORTED) BE <br />COMPACTED TO A CRITERIA LESS THAT 98% OF MODIFIED PROCTOR MAXIMUM DRY <br />DENSITY UNLESS SPECIFICALLY DIRECTED TO DO SO IN WRITING BY THE PROJECT <br />GEOTECHNICAL ENGINEER. <br />3. ALL POURED IN PLACIECONCRETE SHALL HAVETHE FOLLOWING MINIMUM 28 DAY ULTIMATE <br />COMPRESSIVE STRENGTH: <br />A. FOUNDATIONS - fc = 3000 PSI. <br />B. COLUMNS AND (OR) PEDESTALS - f'c = 4000 PSI. <br />C. BEAMS - f'c = 4000 PSI. <br />4. THE CONTRACTOR SHALL RETAIN AN INDEPENDENT TESTING LABORATORY TO PERFORM <br />THE FOLLOWING TESTS: <br />A. ONE DENSITYTEST FOR EACH 1500 SQUARE FEET OF COMPACTED SUBGRADE OR <br />COMPACTED FILL. <br />B. ONE DENSITY TEST AT EACH COLUMN FOOTING. <br />C. ONE DENSITYTEST FOR EACH 25 FEET OFWALL FOOTING. <br />D. SEECAST IN PLACE CONCRETE NOTES FOR CONCRETETESTING REQUIREMENTS. <br />ONE COPYOFALL TEST REPORT RESULTS SHALL BE SENT DIRECTLY TO THE ARCHITECT, <br />STRUCTURAL ENGINEER, OF-CFECHNICAL ENGINEER AND GENERAL CONTRACTOR. <br />5, ALL REINFORCING BAR SHALL RIF G)RADFfy = 60 KSI AND SHALL MFFTASTM SPECIFICATION <br />A-615 (Sl). <br />6. ALL FOUNDATION REBAR LAPS SHALL BE AS SCHEDULED ON THE DRAWINGS FOR THE <br />SPECIFIC STRUCTURAL ELEMENT AND STRENGTH OF CONCRETE TO BE POURED <br />7. PROVIDE CORNER BARS TO MATCH SIZE AND COUNT OF FOUNDATION LONGITUDINAL BARS. <br />8. BUILDING DESIGN PURSUANT TO THE 2010 EDITION OF THE FLORIDA BUILDING CODE. <br />9. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO BEGINNING <br />FOUNDATION CONSTRUCTION. <br />10. UNLESS SPECIFICALLY DETAILED OTHERWISE, FOUNDATIONS SHALL BE LOCATED AT THE <br />CENTER OF WALLS AND/OR COLUMNS WHICH THEY SUPPORT. TOLERANCIEFORTHE <br />ACCEPTABILITY OF PLACEMENT OF FOUNDATIONS, ANCHOR BOLTS, COLUMN DOWELS, <br />WALLDOWELS, ETC., SHALL BE GOVERNED BY THE APPROPRIATE AISC, ACI AN D/OR <br />BUILDING CODES PROVISIONS. <br />1 . CAST IN PLACE CONCRETE WORK INCLUDES REINFORCING STEEL AND RELATED WORK <br />SHOWN INCLUDING FORMWORK, SE71NG ANCHOR BOLTS, PLATES, FRAMES, DOWELS FOR <br />MASONRY OR OTHER ITEMS EMBEDDED IN CONCRETE. <br />2. ALL CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF THE FOLLOWING <br />CODES AND STANDARDS (LATEST EDITIONS): <br />A. ACI 11 7 "STANDARD TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS" <br />B. ACI232.11R "USE OF ROW OR PROCESSED NATURAL POZZOLANS IN CONCRETE' <br />OR <br />ACI 232.2R "USE OF FLY ASH IN CONCRETE" <br />OR <br />ACI 233R"GROUND GRANULATED BLAST FURNACE SLAG"CEMENT IN CONCRETE AND <br />MORTAR <br />C ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS" <br />D. ACI 302 �GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION" <br />E. ACI 304 "RECOMMENDED PRACTICE FOR MEASURING: MIXING, TRANSPORTING AND <br />PLACING CONCRETE" <br />F. ACI 304,2R PLACING CONCRETE BY PUMPING METHODS <br />G. ACI 305R "RECOMMENDED PRACTICE FOR HOTWEATHER CONCRETING" <br />H. ACI 306R "RECOMMENDED PRACTICE FOR COLD WEATHER CONCRETING" <br />1. ACI 308 'STANDARD PRACTICE FOR CURING CONCRETE; <br />J. ACI 309R "GUIDE FOR CONSOLI DATION OF CONCRETE" <br />K� ACI 311 "RFCOMMFNDED PRACTICE FOR CONCRETE INSPECTION" <br />L. ACI 316 DETAILS AND DETAILING OF CONCRETE REINFORCEMENT" <br />M. ACI 318 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" <br />N. ACI 347 "RECOMMENDED PRACTICE FOR CONCRETE FORMWORK" <br />0. ACI MANUAL OF CONCRETE PRACTICE - PARTS 1 THRU 5 (AS APPROPRIATE TO TYPE OF <br />CONSTRUCTION). <br />3. CONCRETE SHALL BE NORMAL WEIGHT (U.N.0) AND SHALL BE BATCHED, MIXED AND <br />TRANSPORTED IN ACCORDANCEWITH ASTM C94,"THE SPECIFICATIONS FOR READY MIX <br />CONCRETE". <br />NOTE: THE CONCRETE SHALL BE PLACED W17HIN 90 MINUTES OF BATCH TIME. <br />CONCRETE MIX DESIGN SHALL BE PROPORTIONED IN ACCORDANCE WITH ACI <br />301 TO PROVIDE CONCRETE CAPABLE OF BEING PLACED WITHOUT EXCESSIVE <br />SEGREGATION AND WITH ACCEPTABLE FINISHING PROPOIFIRTIES, DURABILITY, <br />SURFACE HARDENERS, APPEARANCE, AND STRENGTH REQUIREMENTS <br />REQUIRED BY THESE SPECIFICATIONS. <br />MATERIALS USED IN THE CONCRETE MIX: <br />A. PORTLAND CEMENT: ASTM C 150, TYPE 1 OR TYPE 11 <br />B. AGGREGATES: NORMAL WEIGHT CONCRETE, COARSE AND FINE, ASTM C33 (MAXIMUM <br />AGGREGATE SIZE: FOUNDATIONS - #57, ALL OTHER CONCRETE STRUCTURAL ELEMENTS <br />- *67. <br />C. Al R ENTRAI NI NG AGENT SHALL MEET ASTM. C-260 <br />D. WATER REDUCING: AS-1 M 0494, TYPE A <br />E. WATER: FRESH, CLEAN AND POTABLE. <br />F. NO ACCELERATORS, RETARDERS OR ADMIXTURES CONTAINING CHLORIDES WI LL BE <br />PERMITTED. <br />G. CALCIUM CHLORIDE SHALL NOT BE USED IN THE MIX <br />NOTE: ADDING OF WATER TO MIX IN FIELD: <br />THE READYMIX DRIVER SHALL HAVE IN HIS POSSESSION AT TIME OF DELIVERY, <br />WRITTEN INSTRUCTIONS FROM THE READYMIX SUPPLIER DETAILING THE <br />MAXIMUM AMOUNT OF WATER WHICH CAN BE ADDED TO THE MIX BY THE <br />DRIVER IN THE FIELD (GALLONS PER YARD). OTHERWISE WATER SHALL NOT 13E <br />ADDEDTO THE MIX AFTER LEAVING THE BATCH PLANT. <br />H. FLY -ASH: ASTM C618, CLASS F, 20% MAXIMUM BY WEIGHT. DO NOT USE FOR EXPOSED <br />SLABS FOR ARCHITECTURAL CONCRETE. <br />I SUPER PLASTICIZER* ASTM C494, TYPE F OR G, WHERE ALJTHOR17ED BY THE ENGINEER <br />J. SLAG CEMENT IN CONCRETE: ASTM C989,30% BY WEIGHT <br />4. CONCRETE SHALL HAVE THE MINIMUM ULTIMATE COMPRESSIVE STRENGTH AT 28 DAYS, <br />(U.N.O.), FOR THE STRUCTURAL ELEMENT INDICATED BELOW: <br />FOUNDATION: 3000 PSI <br />SLAB ON GRADE: 3000 rsi <br />COLUMNS: 4000 PSI <br />TIE BEAMS: 4000 PSI <br />BEAMS. 4000PSI <br />CONCRETE MIX DESIGN SUBMITTAL DATA REQUIRED: <br />A. INTENDED USAGE AND LOCATION FOR EACH MIX TYPE <br />B. MIX DESIGN FOR EACH TYPE <br />C. CEMENT CONTENT IN POUNDS -PER -CUBIC YARD <br />D. COURSE AND FINE AGGREGATE IN PCUNDS/CUBIC YARD <br />E. WATER CEMENT RATIO BY WEIGHT (NOT TO EXCEED D.60 EVERYWHERE EXCEPT SLAB <br />ON GRADE W/C = 0.5) <br />F. CEMENT TYPE OF MANUFACTURER <br />G. SLUMP RANGE <br />H AIR CONTFNT <br />1. ADMIXTURE TYPE AND MANUFACTURER <br />J. PERCENT ADMIXTURE BY WEIGHT <br />K. HISTORICAL PERFORMANCE STRENGTH TEST DATA REQUIREDTO ESTABLISH MIX <br />DESIGN. <br />5. THE CONTRACTOR SHALL RETAIN THE SERVICES OF A QUALIFIED ACCREDITED TESTING <br />LABORATORYTO PERFORM THE FOLLOWING TESTING SERVICES: <br />A. SAMPLING PER ASTM. C-172 <br />NOTE: SAMPLING SHALL BETAKEN FROM THE POINT OF DELIVERY OF THE CONCRETE. <br />IN OTHER WORDS IF A CONCRETE PUMP IS USED, 5AMPLIFS SHALL BE LAKEN FROM THE <br />DISCHARGE END OF THE HOSE. <br />R SLUMP PER ASTM C-143 <br />C. COMPRES,q; VE STRENGTH PER ASTM. C-31 & C-39. FOR EACH CLASS OF CONCRETE <br />POURED, PROVIDE FOUR CYLINDERS FOR EACH 50 CUBIC YARDS OF <br />CONCRETE OR FRACTION THEREOF. BREAK ONE CYLINDER AT (7) DAYS, TWO AT (28) <br />DAYS AND HOLD THE REMAINING IN RESERVE IN CASE A 56 DAY TESTIS REQUIRED. A <br />TEST RESULT IS CONSIDERED TO BE THE AVERAGE OF THE TWO CYLINDER BREAKS. <br />ONE COPY OF ALL TEST RESULTS SHALL BE SENT DIRECTLY TO THE OWNER, <br />ARCHITECT, STRUC I URAL ENGINEER AND GENERAL CON I RACIOR IMMEDIATELY UPON <br />DETERMINATION OF RESULTS. FREQUENCY OF TESTING SHALL NOT BE LESS THAN <br />ONCE A DAY WHEN CONCRETE IS POURED NOR LESS THAN ONCE FOR EACH 5000 <br />SQUARE FEET OF SURFACE AREA FOR SLABS OR WALLS <br />6. REINFORCEMENT USED IN CONCRETE STRUCTURAL ELEMENTS: <br />A. DEFORMED BARS: ALL MILD REINFORCING BAR USED IN CONCRETE SHALL BE GRADE 60 <br />KSI DEFORMED BAR CONFORMING TO ASTM SPECIFICATION A-61 6 (Sl). <br />B. SMOOTH DOWF1 S- ASTM A615, PLAIN BARS, MINIMUM YIELD STRENGTH OF 60 KSI <br />C. WELDED WIRE FABRIC: CONFORM TOASTM. A-185 AND SUPPLIED IN FLAT SHEETS <br />(RATHER THAN IN ROLLS). FABRIC SHALL BE PLACED ON CONTINUOUS NO. 4 REBAR <br />CHAIRS SPACED AT 3 FT O.C. TO MAINTAIN THE PROPER LOCATION WITHIN THE <br />D. ACCESSORIES TO CONFORM TO ACI 315. <br />E. WHERE CONCRETE SURFACES ARE EXPOSED, MAKE THOSE PORTIONS OF ALL <br />ACCESSORIES IN CONTACT WITH THE CONCRETE SURFACE OR WHININ 112 INCHES <br />THEREOF, OF PLASTIC. <br />F. ALL REINFORCING DETAILS SHALL CONFORM TO ACI 315, LATEST EDITION, "MANUAL OF <br />STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES" (U.N.C.) <br />G. SUBMIT COMPLETE DETAIL AND PLACING SHOP DRAWINGS FOR ALL REINFORCING <br />7. CONCRETE COVER OVER REINFORCING IN CONCRETE STRUCTURAL ELEMENTS SHALL BE <br />AS FOLLOWS: <br />A. FOUNDATIONS: 3" <br />B. COLUMNS: 1 112" (2" FOR NO. 6 AND LARGER BARS) <br />C. BEAMS: 1 112" (2" FOR NO. 6 AND LARGER BARS) <br />D. WALLS. 1 112" (2" FOR NO. 6 AND LARGER BARS) <br />E. SLABS: V (INTERIOR), 1 112" (EXTERIOR) <br />8. LAP SPLICE LENGTHS SHALL BE AS SCHEDULED FOR THE STRENGTH OF CONCRETE AND <br />SPECIFIC STRUCTURAL ELEMENT IN QUESTION. <br />9� PROVIDE PROPERLY TIED SPACERS, CHAIRS. BOLSTERS, ETC., AS ARE REQUIRED AND <br />NECESSARY TO ASSEMBLE, PLACE AND SUPPORT ALL REIN FORCING IN THE PROPER <br />REQUIRED LOCATION WITHIN THE FORMWORK (AND MAINTAIN REINFORCING IN THE <br />PROPER POSITICIN DURING CONCRETE PLACEMENT OPERATIONS AND UNDER THE <br />APPLICATION OF CONSTRUCTION LOADS AND OPERATIONS). WHEREWIRE TYPE SUPPORTS <br />AREUSED, COMPLYING WITH CRSI RECOMMENDATIONS, PLASTIC TIP LEGS SHALL BE <br />USED WHEN CONCRETE IS TO BE EXPOSED TO EXTERIOR CONDITIONS <br />10. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER DESIGN AND <br />CONSTRUCTION OF ALL NECESSARY FORMWORK, SHORING AND RESHORING IN <br />ACCORDANCE WITH ACI 347. THE DESIGN SHALL BE PREPARED BY A DELEGATED <br />SPECIALTY STRUCTURAL ENGINEER CURRENTLY REGISTERED IN THE STATE OF INTENDED <br />CONSTRUCTION OF THE PROJECT WHERE LIFE SAFETY ISSUESARE CRITICAL AND <br />ERECTION DRAWING SHALL BEAR HIS SEAL AND SIGNATURE AND THE DATE ERECTION <br />DRAWINGS SHALL BE SUBMITTED TO THE RESPONSIBLE BUILDING AUTHORITY. <br />NOTE: EARTH MAYBE USED AS VERTICAL SURFACE FORMS FOR FOOTINGS PROVIDED <br />THAT THE FOOTING OVERALL WIDTH IS INCREASED IN SIZE BY FOUR INCHES. <br />11. POUR BREAKS IN BEAMS AND SLABS SHALL OCCUR AT MID SPAN BETWEEN SUPPORTS <br />(POINTS OF MINIMUM SHEAR) BY USE OF VERTICAL BULKHEADS. COLD JOINTS LOCATIONS <br />MUST BE LOCATED TO PROVIDE THE LEAST IMPACT ON THE STRENGTH OF THE <br />STRUCTURAL MEMBER. <br />NOTE: HORIZONTAL CONSTRUCTION JOINTS WILL NOT BE PERMITTED IN ANY <br />HORIZONTAL SPAN CONCRETE MEMBER! <br />12. PROVIDE MINIMUM 14 GAGE GALVANIZED CORRUGATED DOVETAIL ANCHORSAT 161, O.C. TO <br />CONNECT ADJACENT MASCNRYTO CONCRETE STRUCTURAL ELEMENTS. PROVIDE <br />DOVETAIL ANCHOR HARDWARE WITH HOT DIP GALVANIZED FINISH, (ASTM A 153, <br />CLASS B2, (1.5 OZ. PER SQ. FT.)). <br />13. PROVIDE NEOPRENE WATER STOPS AT ALL CONSTRUCTION JOINTS IN CAST IN PLACE <br />CONCRETE WHERE ONE SIDE IS DIRECTLY EXPOSED TO EITHER THE WEATHER ORIN <br />DIRECT CONTACT WITH SOIL AND THE OTHER SIDE OCCURS WITHIN ENCLOSED SPACE. <br />14. PROVIDE COMMERCIAL FORM COATING COMPOUNDS (RELEASE AGENTS) THAT WILL NOT <br />BOND, STAIN OR ADVERSELY AFFECTTHE FINISHED CONCRETE SURFACE- <br />15. PLACE CORNER BARS AT CORNERS AND ENDS OF ALL FOOTINGS, WALLS AND BEAMS. BAR <br />SIZE AND COUNT SHALL MATCH THE LONGITUDINAL REINFORCING IN THE MORE HEAVILY <br />REINFORCED INTERSECTING ELEMENT (U N.C.). <br />16, DOWEL INTERSECTING WALLS, BEAMS, ETC. WITH DOWELS OF THE SAME SIZE, COUNT AND <br />SPACING AS THE LONGITUDINAL REINFORCING IN THE MORE HEAVILY REINFORCED <br />MEMBER FRAMING INTO THE JOINT. <br />1 7 � PLACE A MINIMUM OF TWO (2) NO. 5 BARS (U.N.O.) AROUND ALL FOUR SIDES OF OPENINGS <br />IN CONCRETE STRUCTURAL ELEMENTS. BARS SHALL EXTEND AT LEAST 36 IN. BEYOND <br />THE FACE OF THE OPENING. <br />18 TYPICAL SPACING OF TIES AND STIRRUPS AS INDICATED ON THE PLANS SHALL BE <br />REDUCED BY 50% FOR THE SPACE BETWEEN THE FACE OF THE SUPPORT AND THE FIRST <br />STIRRUP OR TIE (U.N.O.). <br />19. VERTICAL AND HORIZONTAL REINFORCING INDICATED ON THE DRAWINGS SHALL BE <br />DOWELED OJT OF THE FOUNDATION (OR THE ELEMENTWHERE THE REINFORCING <br />ORIGINATES, (SLAB, BEAM, TIE BEAM, WALL, ETC.) UTILIZING AN ACI STANDARD <br />HOOK EMBEDDED TO DEVELOP THE FULL ULTIMATE TENSILE STRENGTH OF THE BAR <br />(U.N.O.). <br />20. VERTICALWALL REINFORCING INDICATED ON THE DRAWINGS SHALL EXTEND FROM THE <br />FOUNDATION, (OR PER NOTE NO. 19 ABOVE), TO THE TIE BEAM AT THETOP OF THE WALL <br />PROVIDE A STANDARD ACI 90 DEGREE HOOK (EMBEDDED TO DEVELOP THE FULL ULTIMATE <br />STRENGTH OF THE BAR) OUT OF THE ELEMENT WHERE THE REINFORCING ORIGINATES AND <br />INTOTHE TOP OF THE TIE BEAM. HOOK SIZE AND COUNT SHALL MATCH THE VERTICAL <br />REINFORCING LAP SPLICE LENGTHS SHALL BE AS SCHEDULED ON THE PLANS. <br />NOTE: WHEN LAYING OUT FOUNDATION DOWELS FOR "UNIFORMLY" SPACED VERTICAL <br />WALL REINFORCING, FIRST LOCATE THE DOWELS SPECIFIED AT WINDOW, DOOR& <br />OTHER MASONRY OPENINGS, ENDS OF WALLS, COLUMNS, TIE COLUMNS, <br />PILASTERS, ETC., THEN LOCATE DOWELS IN BETWEEN AT THE SPECIFIED MAXIMUM <br />UNIFORM SPACING. <br />21. THE MINIMUM BEARING OF CONCRETE BEAMS ON SUPPORT SHALL BE 8" (UNLESS NOTED <br />OR DETAILED OTHERWISE). WHERE BEAM BEARS ON A MASONRY SUPPORT, EXTEND BEAM <br />A DISTANCE OVER THE SUPPORT AT LEAST EQUAL TO THE LENGTH OF ALL REINFORCED <br />AND GROUTED CELLS ADJACENT TO THE MASONRY OPENING. WHERE THE BEAM BEARS ON <br />A REINFORCED CONCRETE SUPPORT, EXTEND THE BEAM ACROSS THE FULL LENGTH OF <br />THE SUPPORT (FULL BEARING OF BEAM ON SUPPORT). NOTE: ALL CONTINUOUS <br />LONGITUDINAL BEAM REINFORCING SHALL EXTEND FULL LENGTH ACROSS SUPPORT. <br />LENGTH OF BEARING OF BEAM ON SUPPORT SHALL NOT BE LESS THAN DEPTH OF BEAM. <br />22. SEE ARCHITECTURAL MECHANICAL, AND ELECTRICAL DRAWINGS FOR LOCATIONS OF <br />EMBEDDED ITEMS, CONDUITS, PIPES, SLEEVES, SLAB DEPRESSIONS, ANCHORS, INSERTS, <br />ETC, IN AND THRU CONCRETE ELEMENTS, REQUIRED BY OTHER TRADES. NO CONDUITS, <br />PIPES, SLEEVES, PENETRATIONS OR INSERTS OF ANY TYPE WILL BE PERMITTED IN BEAMS, <br />JOISTS, SLABS, COLUMNS OR WALLS UNLESS APPROVED BY THE ENGINEER, SHOWN ON <br />THE SHOP DRAWINGS, AND CONSTRUCTED TO COMPLY WITH THE REQUIREMENTS OF <br />SECTION 63 OF ACI 318. AFTER APPROVAL BY THE ENGINEER, THE CONTRACTOR SHALL <br />FURNISH AND COORDINATE THE INSTALLATION OF EMBEDDED ITEMS PRIOR TO PLACING <br />THE CONCRETE. <br />23. GENERALLY, REINFORCING SHALL NOT BE CUT TO ACCOMMODATE THE INSTALLATION OF <br />EMBEDS, ANCHORS, SLEEVES AND/OR OTHER ITEMS. WHERE SUCH IS ABSOLUTELY <br />NECESSARY, NOTIFY THE STRUCTURAL ENGINEER OF THE INTENTION TO DO SO AND FOR <br />EACH BAR CUT, PROVIDE ONE ADDITIONAL BAR EACH SIDE OF THE BAR WHICH WAS CUT. <br />SIZE OF ADD BARS SHALL MATCH SIZE OF ORIGINAL BAR AND LENGTH SHALL BE <br />ADEQUATE TO AT LEAST PROVIDE A CLASS "B" FENSION LAP (OR EMBEDMENT) EACH SIDE <br />OF THE BAR WHICH WAS CUT <br />24. REMOVE TRASH AND DEBRIS FROM FORMWORK AND THOROUGHLY WET FORMS <br />IMMEDIATELY PRIOR TO PLACING CONCRETE. <br />25, THE CONCRETE SHALL BE PLACED IN ONE CONTINUOUS OPERATION BETWEEN <br />CTION JOINTS. <br />26. THE CONCRETE SHALL BE POURED BY PUMP OR BUCKET AND SHALL BE CONSOLIDATED IN <br />PLACE USING INTERNAL VIBRATORS. <br />27. THE CONTRACTOR SHALL BEGIN CONCRETE CURING IMMEDIATELY AFTER FINISHING <br />OPERATIONS ARE COMPLETED. CURING AGENT SHALL BEA 30% SOLIDS LIQUID MEMBRANE <br />FORMING CHEMICAL COMPOUND AND SHALL MEET ASTM. C-309. THEIGENERAL <br />CONTRACTOR IS TO VERIFY THAT ANY CURING COMPOUNDS THAT ARE USED ARE <br />COMPATIBLE WITH FINISH MATERIALS TO BE INSTALLED ON THE SURFACE OF THE <br />CONCRETE <br />NOTE� VVET CURING ]SAN ACCEPTABLE AND PREFERRED METHOD OF CURING FOR SLABS. <br />THIS REQUIRES THAT THE SURFACE OF THE SLAB REMAIN SATURATED FOR AT <br />LEAST 4 DAYS WITH WET BURLAP OR POLYETHYLENE SHEETS. THIS <br />METHOD WILL GREATLY REDUCE VOLUME CHANGE AND SHRINKAGE CRACKS. <br />PLAIN & REINFORCED MASONRY NOTES: <br />1 AL L MASONRY WORK SHALL CONFORM TO ACI 530-OWASCIF 9-081TIVIS 402-08, "BUI LDI NG <br />12. CONCRETE MASONRY WALLS SHALL BE BONDED AT ALL EXTERIOR AND INTERIOR <br />INTERSECTING WALLS AND CORNERS BY OVERLAPPING COURSES (RUNNING BOND). THIS <br />PROVISION APPLIES TO BOTH BEARI NG AND NON-BEARI NG WALLS. WALLS SU PPORTED BY <br />SLAB HAUNCHES SHALL BE BONDED TO WALLS SUPPORTED BY FOOT] NGS WITH <br />GALVANIZED "Z" STRAP (12 GAGE MIN.) ANCHORS AT 24 INCHES O.C. IN MORTAR JOINTS. <br />13. ALL MASONRY HEAD AND END JOINTS SHALL BE FILLED SOLIDLYWITH MORTAR FOR A <br />DISTANCE FROM THE FACE OF THE WALL OF NOT LESS THAN THE THICKNESS OF THE <br />LONGITUDINAL FACE SHELLS. <br />14. TO REDUCE LEAKAGE OF GROUT INTO ADJACENT VERTICAL CELLS, CROSSWEBS MUST BE <br />FULLY BEDDED IN MORTAR AT ALL CELLS CONTAINING VERTICAL REINFORCING. <br />NOTE: WHERE GROUTING TECHNIQUE WILL NOT REQUIRE (BY CODE) THE PLACEMENT <br />OF CLEANOUT HOLES, MASONS SHALL EXERCISE SUCH MEASURES AS ARE <br />NECESSARY TO KEEP CELLS CLEAN & FREE OF SOIL, SAND, MORTAR FINS <br />(DROPPINGS), ETC., SO AS TO NOT INTERFERE WITH GROUTIFOUNDATION BOND <br />AT GROUTED CELLS, SO AS TO NOT RESTRICT THE FLOW OF GROUT, AND SO AS <br />TO PROVIDE A FULLY HOMOGENEOUSLY GROUTED CELL. <br />15. PROVIDE A 3" HIGH X 4" WIDE CLEANOUT HOLE AT THE BASE COURSE OF ALL REINFORCED <br />CELLS TO VERIFY PROPER GROUT PLACEMENT WHEREVER GROUT POUR HEIGHT EXCEEDS <br />6-0" IN HEIGHT. REMOVE DEBRIS FROM CLEANOUT HOLE PRIOR TO CAPPING. GROUT <br />POURS EXCEEDING 5'-O" IN HEIGHT SHALL BE PLACED IN INDIVIDUAL LIFTSWHICH SHALL <br />NOT EXCEED 6-0" IN HEIGHT. GROUT POUR HEIGHTS SHALL NOT EXCEED 8!-O", DUE TO THE <br />DIFFICULTY IN VIBRATING AND LENGTH OF AVAILABLE 3/4" 01A. HEAD LOW VELOCITY <br />VIBRATORS. EACH LIFT MUST BE CONSOLIDATED AND RECONSOLIDATED AS INDICATED <br />BELOW PRIOR TO PLACING THE NEXT LIFT. TERMINATE TOP OF GROUT POUR 1/2" BELOW <br />TOP OF MASONRY UNITS TO PROVIDE SHEAR KEY FOR CONTINUED GROUTING. <br />16. ALL GROUT PLACEMENT SHALL BE CONSOLIDATED IN PLACE TO INSURE SOLIDLY GROUTED <br />ELEMENTS HAVING NO POCKETS, VOIDS, HONEYCOMB, ETC., BY USE OF A LCIW VELOCITY <br />MECHANICAL VIBRATOR HAVING A 3/4" HEAD. GROUT SHALL BE RECONSOLIDATED WITHIN <br />15 TO 30 MINUTES OF INITIAL POUR AND CONSOLIDATION TO ADJUST FOR WATER <br />ABSORPTION INTO CM U'S. <br />11. WH ERE GROUT PLAC EMEN I IS IN] ERRUPIED `-OR ONE HOUR OR MORE, THE LAST POUR <br />MUST BE TERMINATED 1 1/2 INCHES BELOW THE TOP OF THE BLOCK TO PROVIDE A SHEAR <br />KEY FOR CONTINUED GROUTING <br />18. THE CONTRACTOR HAS THE FULL RESPONSIBILITY OF PROVIDING ANY AND ALL NECESSARY <br />BRACING OF WALLS DURING CONSTRUCTION TO MAINTAIN STABILITY AND STRUCTURAL <br />INTEGRITY. RETAINING WALLS, IF ANY, SHALL BE BRACED PRIOR TO AND DURING ALL <br />BACKFILLING AND COMPACTING OPERATIONS. <br />19. PROVIDE HORIZON IAL AND VERITCAL REINFORCING PER CON I RAO 1 DOCUMENTSAND <br />SOLID GROUT FILLED CELLS AT ALL VERTICAL REINFORCING. <br />NOTE: HORIZONTAL AND VERTICAL REINFORCING (REBAR) TO BE EMBEDDED IN <br />GROUT SHALL BE PLACED AND HELD IN PROPER POSITION DURING GROUTING <br />(BY MECHANICAL MEANS IF NECESSARY) SO AS TO ALLOW FOR A MINIMUM <br />THICKNESS OF GROUT (CLEAR DISTANCE BETWEEN THE REINFORCING AND <br />THE INSIDE FACE OF THE MASONRY UNIT) OF NOT LESS THAN 1/4 INCH FOR <br />FINE GROUT AND NOT LESS THAN 112 INCH FOR COURSE GROUT. <br />NOTE: VERTICAL CELLS SHALL BE GROUTED TO WITHIN% INCH OF THE BOTTOM OF <br />BEAMS PRIOR TO THE PLACEMENT OF LONGITUDINAL BEAM REINFORCING. <br />CELLS SHALL NOT BE GROUTED AS BEAM IS BEING POURED OR GROUTED! <br />20. PROVIDE REINFORCING BAR LAP SPLICE LENGTHS AS SHOWN ON DRAWING SDII, IN <br />ACCORDANCE WITH THE 2010 EDITION OF THE FLORIDA BUILDING CODE <br />NOTE: IN BEAMS, TIE BEAMS, ETC, PLACE LAPPING BARS IN VERTICAL ALIGNMENT, <br />ONE ABOVE THE OTHER, IN ORDER TO AVOID REINFORCING CONGESTION, <br />PROVIDE ADEQUATE SPACE FOR PASSAGE OF VERTICAL REINFORCING, <br />PROVIDE FOR PROPER GROUT FLOW & CONSOLIDATION, TO PROVIDE FOR <br />PROPER GROUT COVER AROUND RFINFORC ,ING AND PROVIDE FOR PROPFR <br />DEVELOPMENT OF REINFORCING. <br />21. VERTICAL REINFORCING INDICATED ON THE DRAWINGS SHALL BE DOWELED OUT OF THE <br />FOUNDATION (OR ELEMENT WHERE REINFORCING ORIGINATES (BEAM, SLAB, TIE BEAM, <br />WALL, ETC.) UTILIZING A STANDARD ACI 90 DEG. HOOK (EMBEDDED TO DEVELOP THE FULL <br />ULTIMATE TENSILE STRENGTH OF THE BAR.) U.N.C. <br />22. VERTICAL WALL REINFORCING INDICATED ON THE DRAWINGS, WHEREVER POSSIBLE, SHALL <br />FXTFND FROM FOUNDATION (OR PFR NOTE NO. 23 ABOVE) 70 TIE BEAM AT THE TOP OF THE <br />WALL. PROVIDE A STANDARD ACI 90 DEG. HOOK OUT OF THE FOUNDATION AND INTO THE <br />TIEBEAM. LAP SPLICE LENGTHS SHALL BE AS INDICATED BY NOTE NO. 22, ABOVE. WHENA <br />VERTICAL DOWEL DOES NOT ALIGN WITH A CELL IN THE WALL ABOVE, IT SHALL NOT BE <br />BENT MORE THAN I 0 DEGREES FROM THE VERTICAL (REMOVE CELL DIVIDER WEB WHEN <br />REQ'D.). FURTHER, THE DOWEL SHALL NOT BE BENT MORE THAN ONCE AND SHALL NOT BE <br />BENT INTO A CURVED SHAPE. DOWELS MUST BE GROUTED INTO CELLS IN VERTICAL <br />ALIGNMENT. <br />NOTE: WHEN LAYING OUT FOUNDATION DOWELS FOR "UNIFORMLY'SPACED WALL <br />REINFORCING, FIRST LOCATE DOWELS SPECIFIED AT WINDOW, DOOR &OTHER <br />MASONRY OPENINGS, ENDS OF WALLS, COLUMNS, PILASTERS, TIE COLUMNS, <br />ETC., THEN LOCATE THE DOWELS IN BETWEEN AT THE SPECIFIED MAXIMUM <br />SPACING. <br />23. UNLESS SPECIFICALLY DETAILED TO BE MORE HEAVILY REINFORCED, PROVIDE THE <br />FOLLOWING MINIMUM VERTICAL REINFORCING IN ALL MASONRY WALLS: <br />8 <br />< <br />a: <br />z D <br />w <br />Z, F11 <br />z 6 2:g <br />�_ Ill . <br />00 6 � 12 <br />r. 6 < (!r <br />co <br />9 I <br />� I I I I <br />V 6 2 <br />m 19 <br />Lu �. 1 <br />C4 II.; Il-- <br />�: rj) 2 . I i; <br />TO THE BEST OF MY KNOWLEDGE, THE <br />PLANS AND SPECIFICATIONS COMPLY WITH <br />THE CURRENT MINIMUM BUILDING CODES. <br />v 9 EE IR I F. "'llopeRm"I,.K. <br />Rempoppla- <br />9�r �- - - E. , - - - - - - - - j; - <br />W i kd <br />k i lWit,t . r-. <br />i JOV C 2013 <br />P.E. #20683 <br />CODE REQUIREMENTS FOR MASONRY STRUCTURES" AND ACI 530.1-08/ASCE 6_081TMS 602 <br />A. ADJACENT TO ALL MASONRY WALL OPENINGS: 1 NO. 6 VERT. <br />-08, "SPECIFICATIONS FOR MASONRY STRUCTURES". <br />B. EXTERIOR 8 INCH WALLS: I NO� 5 VERT. AT 2'-O" O.0 <br />C. INTERIOR 8 INCH WALLS: 1 NO. 5 VER 1. A 1 4'-O" O.C. <br />WEBER AND TINNEN, P.A. <br />2. <br />ALL HOLLOW LOAD BEARING CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM. C-90, <br />NORMAL WEIGHT, TYPE 11, (PROVIDE TYPE I (MOISTURE CONTROLLED UNITS) WHENEVER <br />24. <br />VERTICAL REBAR SHALL BE HELD IN PROPER POSITION AT TOP AND BOTTOM AND AT NOT <br />THEY ARE AVAILABLE): <br />MORE THAN 8'-O" O.C. IN BETWEEN VIA PREFABRICATED GALVANIZED WIRE REBAR <br />POSITIONERS. THE MINIMUM CLEARANCE FROM FACE OF MASONRY SHALL BE 112 ". THE <br />STANCARD STRENGTH CMU'S, <br />MINIMUM SPACING BETWEEN ADJACENT BARS SHALL BE ONE BAR DIAMETER OR 1". <br />HAVING A MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF 1900 PSI (ON THE NET AREA <br />WHICHEVER IS GREATER, <br />OF THE CMU) IN ACCORDANCE WITH ASTM C-1 40 AND fm = 1500 PSI BYTHE UNIT <br />STRENGTH METHOD <br />25. <br />WHEREVERTICAL MASONRYWALL REINFORCING IS CONTINUOUS THROUGH ACONCRETE <br />. <br />SLAB, PROVIDE A 3 INCH DIAMETER FORMED HOLE IN THE SLAB TO ALLOW FOR PASSAGE <br />PRIOR TO DELIVERY OF ANY MASONRY UNITS TO THE JOB SITE, THE CMU SUPPLIER SHALL <br />OF GROUT. <br />PROVIDE VERIFICATION OF MASONRY UNIT STRENGI H, ON BOTH THE NET AND THE GROSS <br />CROSS SECTIONAL AREA OF THE CMU'S PER ASTM C-1 40 (FOR EACH SIZE AND TYPE OF <br />26. <br />PROVIDE CORNER BARS AT ENDS AND CORNERS OF ALL WALLS, FOOTINGS, BEAMS, ETC. <br />UNIT TO BE USED ON THE PROJECT). SUCH VERIFICATION SHALL INCLUDE TEST REPORTS <br />BAR SIZE AND COUNT SHALL MATCH THE LONGITUDINAL REINFORCING IN THE MORE <br />FROM AN ACCREDITED TESTING LABORATORY STATING THE RESULTS OF THE TESTING <br />HEAVILY REINFORCED CONNECTING MEMBER. (U.N.O.). <br />PROGRAM AND AFFIDAVITS FROM THE SUPPLIER CERTIFYING THAT ALL UNITS CONFORM <br />TO THE RESPECTIVE ASTM REQUIREMENTS. <br />NOTE: AT CORNERS OF BEAMS, TIE BEAMS, ETC., PLACE AND TIE CORNER BARS IN <br />VERTICAL ALIGNMENT, EITHER ABOVE OR BELOW CONTINUOUS LONGITUDINAL <br />3. <br />MORTAR SHALL BE TYPE S (1800 PSI PROPERTY SPECIFICATION) AND SHALL CONFORM TO <br />REINFORCING, TO AVOID REINFORCING CONGESTION, ALLOW FOR ADEQUATE <br />ASTM. SPEC. C-270. CEMENTIOUS MATERIAL SHALL BE PORTLAND CEMENT COMBINED WITH <br />SPACE FOR PASSAGE AND CONSOLIDATION OF GROUT, TO ALLOW SPACE FOR <br />CITY OF ZEPHYRHILLS <br />HYDRATED LIME AGGREGATE SHALL BE NATURAL OR MANUFACTURED SAND PER ASTM <br />PASSAGE OF VERTICAL REINFORCING, PROVIDE FOR PROPER GROUT COVER <br />RENOVATION <br />C- 1 44. <br />AROUND THE REINFORCING, AND TO PROVIDE FOR ADEQUATE DEVELOPMENT <br />OF THE REINFORCING, <br />OF <br />4. <br />PROVIDE READYMIX GROUT FOR USE IN FILLING OF CELLS AND MASONRY BEAMS HAVING A <br />MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF 3000 PSI (PROPERTY SPECIFICATION) AND <br />27. <br />DOWEL INTERSECTING WALLS, BEAMS, ETC. WITH DOWELS OF THE SAME SIZE, COUNT AND <br />FIRE RESCUE <br />MEETING THE REQUIREMENTS OF ASTM C-476. MAXIMUM AGGREGATE SIZE SHALL BE 3/8" <br />SPACING ASTHE HORIZONTAL REINFORCING IN THE MORE HEAVILY REINFORCED <br />FOR COARSE GROUT. SLUMP SHALL BE 8" MIN. AND 1 1" MAX. <br />CONNECTING MEMBER (U.N.0). <br />STATION NO. 2 <br />NOTE. ADDING OFWATER TO MIX IN THE FIELD: <br />THE READYMIX DRIVER SHALL HAVE IN HIS POSSESSION AT THE TIME OF <br />28. <br />PROVIDE KNOCK OUT BLOCK SILL BEAM BELOW WINDOWS (WITH 2 NO. 5 BARS <br />DELIVERY, WRITTEN INSTRUCTIONS FROM THE READYMIX SUPPLIER DETAILING <br />CONTINUOUS SOLIDLY GROUTED IN PLACE) WHERE SILL BEAM IS NOT OTHERWISE <br />THE MAXIMUM AMOUNT OF WATER WHICH CAN BE ADDED TO THE MIX BY <br />SPECIFICALLY DETAILED ON THE DRAWINGS. <br />THE DRIVER IN THE FIELD (GALLONS PER YARD). OTHERWISE, NOWATER <br />SHALL BE ADDED TOTHE MIX AFTER LEAVING THE BATCH PLANT. <br />29. <br />THE MINIMUM BEARING OF THE LINTELS ON ADJACENT MASONRY SHALL BE 8". <br />DOCUMENTS <br />5. <br />ALL REBAR SHALL BE GRADE 60 KSI - DEFORMED BAR CONFORMING TOASTM SPEC. A-616 <br />30� <br />WHERE VERTICAL REINFORCING OCCURSAT LINTEL BEARING POINT, PROVIDE <br />(Si), <br />CAST IN BLOCKOUT IN BOTTOM OF LINTEL TO ALLOW FOR PASSAGE OF CONTINUOUS <br />REINFORCING AND GROUT. <br />6. <br />PROVIDE HORIZONTAL TRUSS TYPE MASONRYWALL JOINT REINF. (DUROWALL OR EQUAL) <br />@ 16' OiC IN ALL MASONRY WALLS INTERIOR AND EXTERIOR. LONGITUDINAL AND CROSS <br />NOTE: HORIZONTAL REINFORCING IN SILLSAND LINTELS SHALL (UNLESS <br />WIRES OF JOINT REINFORCING SHALL BE 9 GAGE WIRE MIN., (ASTM A 82). PROVIDEHOTDIP <br />SPECIFICALLY DETAILED TO EXTEND FURTHER) RUN CONTINUOUS TO AT LEAST <br />GALVANIZED FINISH ON ALL JOINT REINFORCING, (ASTM A 153 CLASS B2 (1.5 OZ. PER SQL <br />8 INCHES (BEYOND FACE OF JAMB OF MO.) INTO GROUTED AND VERTICALLY <br />m m <br />FT)), PROVIDE PREFABRICATED CORNERSANC/OR TEES AT ALL INTERSECTING MASONRY <br />REINFORCED CELLS BEYOND. <br />12-07-2012 <br />WALLS. JOINT REINF. SHALL BE CONTINUOUS. SPLICE LAP LENGTHS SHALL BE A MINIMUM <br />0 0 <br />OF 6" AND SHALL CONTAIN AT LEAST ONE CROSS WIRE FROM EACH PIECE OF LAPPED <br />31. <br />MINIMUM BEARING OF MASONRY AND CONCRFTF REAMS ON SUPPORT SHALL BE 8' (U N 0) <br />CB+A #1 202 <br />REINFORCING. <br />HOWEVER, WHERE MASONRY BEAMS BEAR ON MASONRY OR CONCRETE COLUMNS, <br />0 0 <br />EXTEND THE BEAM (AND CONTINUOUS LONGITUDINAL BEAM REINFORCING) OVER THE FULL <br />7. <br />SECURE MASONRY TO ADJACENT CONCRETE WITH 14 GAGE (MINIMUM) GALVANIZED <br />LENGTH OF THE CONCRETE OR MASONRY SUPPORTING SECTION. WHERE MASONRY OR <br />DOVETAIL -YPE CORRUGATED MASONRYWALL ANCHORS PLACED AT 16" O.C. MAXIMUM <br />CONCRETE BEAMS BEAR ON MASONRY WALLS, EXTEND THE BEAM BEYOND THE FACE OF <br />SPACING (U.N.O.). PROVIDE HOT DIP GALVANIZED FINISH ON ALL DOVETAIL ANCHORS, <br />THE SUPPORT OVERALL SOLID GROUTED AND REINFORCED CELLS. LENGTH OF BEARING <br />(ASTM A 153 CLASS B2 (1.5 OZ. PER SQ. FT.)). <br />OF BEAM SHALL NOT BE LESS THAN THE DEPTH OF THE BEAM. <br />:�w <br />:. <br />S. <br />SECURE MASONRY TO ADJACENT STRUCTURAL STEEL WITH WELD ON ADJUSTABLE <br />32. <br />UNLESS OTHERWISE NOTED, DETAILED OR SCHEDULED, ALL MASONRY COLUMNS, TIE <br />: <br />.1 <br />­ ... - .... I <br />......... . ... <br />­1 ... I I ­­. <br />�.. <br />ip <br />ANCHOR RODS W1 116 DIAMETER TRIANGULAR TIES AT 16 INCHES O.C. MAXIMUM SPACING <br />COLUMNS, AND PILASTERS SHALL HAVE NO, 2 CLOSED LATERAL TI ES PLACED IN MORTAR <br />.. ��i � <br />I <br />(U.N.O.). PROVIDE HOT DIP GALVANIZED FINISH ON ALL ANCHOR HARDWARE (ASTM A -153 <br />JOINTS AT 8" O.C. WHERE INTERIOR LONGITUDINAL BARS ARE SPACED MORE THAN 6 <br />CLASS B2 (1 �5 CZ PER SO. FT.)) <br />INCHES FROM A CORNER LONGITUDINAL BAR HAVING LATERAL SUPPORT PROVIDED BY THE <br />CORNER OF A LATERAL TIE, PROVIDE DOUBLE HOOK CROSS TIE IN ADDITION TO LATERAL <br />9. <br />PROVIDEVVIRES, TIES, SHEET METAL TIES, STRAPS AND ANCHORS HAVING HOT DIP <br />TIE. <br />GALVANIZE C FINISH (AST M A 153 CLASS 62 (1.5 OZ. PER SQ. FT.)), FOR ALL ANCHORAGE <br />DEVICES NOT COMPLETELY EMBEDDED IN MORTAR OR GROUT. WHERE COMPLETELY <br />33. <br />WHERE ANCHOR BOLTS ARE SET IN MASONRY WALLS, FILL BLOCK CELLS WITH GROUT AT <br />EMBEDDED IN MORTAR OR GROUT, GALVANIZED FINISH SHALL BE ASTIM A 641, CLASS 3 <br />COURSES WHERE BOLTS ARE TO BE PLACED AND AT LEAST TWO COURSES BELOW <br />BELFSKY <br />(.8 OZ- PER SQ FT)- <br />LOWESTBOLT(S). ADDITIONALLY, WHERE EXPANSION ANCHORS ARE TO BE USED, <br />PROVIDE SOLID GROUT AT LEAST 6" AROUND BOLT IN ALL DIRECTIONS AND LIMIT SPACING <br />+ <br />10. <br />THE CONTRACTOR SHALL RETAIN AN INDEPENDENT QUALIFIED ACCREDITED TESTING <br />BETWEEN BOLTS TO 6" O.C. <br />ARROYO <br />LABORATORY TO PERFORM THE FOLLOWING TESTING SERVICES: <br />ARCHITECTS <br />A. GROUT STRENGTH TEST PER ASTM. C-1019 (TEST 5 CUBES PER DAY) <br />R MORTAR STRENGTH TEST PER ASTM. C-780 (TEST 3 CUBES PER DAY) <br />PLAIN & REINFORCED MASONRY NOTES CONTINUE NEXT SHEET. <br />800 SECOND AVENUE SOUTH <br />C, CONCRETE MASONRY UNITS (FOR EACH TYPE& STRENGTH) (TEST 20 UNITS PER 50,00 <br />ST. PETERSBURG, FL 33701 <br />UNITS PLACED) <br />(727) 823-0675 <br />COPIES OF TEST RESULTS SHALL BE IMMEDIATELY FORWARDED TOTHE ARCHITECT, <br />STRUCTURAL ENGINEER AND GENERAL CONTRACTOR. <br />0 0 <br />11. <br />SEE SECTION 2104 IN 2010 EDITION OF THE FLORIDA BUILDING CODE FOR CONSTRUCTION <br />REQUIREMEN-S <br />NOTES & SPECIFICATIONS <br />SN-1 <br />(\r-') THESE DRAWIN030 & THEIR CONTENTS ARE THE SOLE PROPERTY <br />1�/ <br />OF <br />WEBER & TINNEN, P.A. STRUCTURAL ENOINEER0. SCALE: AS NOTED <br />S R ANY PORTIONS IS BY CONTRACT ONLY. <br />UNAUTHORIZED USE WILL BE PROSECUTED. <br />0 0 <br />