NOTE: <br />SECURE UNITS TO ROOF <br />STRUCTURE. PROVIDE NECESSARY <br />TIE -DOWNS AS PER ALL APPLICABLE <br />WIND CODES. <br />RTU <br />OA HOOD WITH <br />MOTORIZED DAMPER. <br />MANUFACTURER'S <br />UNIT CURB, <br />INSTALL AS PER <br />ALL MANUFACTURER <br />RECOMMENDATIONS. <br />SECURE UNIT TO <br />STRUCTURE PER <br />ALL APPLICABLE <br />WIND CODES. <br />CONDENSATE DRAIN WITH P-TRAP. <br />SLOPED TO NEAREST ROOF DRAIN. <br />1 /4" STAINLESS <br />STEEL CABLE <br />(TYP. OF 4) <br />1 /4" U BOLT <br />W/NUTS AND <br />WASHERS (TYP) <br />1/2" EYE BOLT <br />TIE TO STRUCTURE <br />AS REQUIRED <br />ROOF <br />TYPICAL ROOFTOP UNIT DETAIL <br />SCALE: N.T.S. <br />1" MIN. ANGLE OVERLAPS <br />ON WALL AND SIDES J <br />BREAKAWAY DUCT <br />CONNECTION TO <br />SLEEVE. PLAIN "S" <br />SUP ON EACH SIDE SLEEVE <br />OF SLEEVE --- <br />DUCT <br />165" FUSIBLE LINK <br />DAMPER FRAME <br />ANGLE IRON SHALL <br />NOT BE ANCHORED <br />TO WALL <br />ANGLE IRON J <br />ON ALL SIDES <br />CLEARANCE <br />1/4" BOLTS OR 1/2" LONG <br />WELDS -MIN. OF TWO <br />FASTENING PER EDGE <br />ACCESS DOOR <br />DL <br />FIRE RESISTANT <br />SEALANT (TYP.) <br />WALL THICKNESS VARIES <br />SEE ARCH. PLANS <br />FIRE DAMPER DETAIL <br />SCALE: N.T.S. <br />JOIST (TYP.) <br />\AAA/"ZV <br />REFER TO DUCT <br />SIZE ON DRAWING CEILING <br />18 GA. HANGER AIR DEVICE (TYP) <br />SPIRAL STRAP (TYPE.) <br />DUCT (TYP) <br />EXPOSED DUCT HANGING DETAIL <br />N.T.S. ELEVATION VIEW <br />WALL SLEEVE <br />DUCT DIMENSION (IN DIA. <br />OR EITHER RECT.. DIM.) <br />MINIMUM GAUGE <br />0-12" <br />26 <br />13"-30" <br />24 <br />31 "-54" <br />22 <br />55"-84" <br />20 <br />85"-UP <br />18 <br />ANGLE IRON & FASTENER DIMENSIONS <br />LENGTH <br />MIN. ANGLE SIZE <br />FASTENER LOCATION <br />0"-48" <br />1-1/2" x 1-1 /2" <br />8" ON CENTER <br />49"-56" <br />2" x 2" <br />6" ON CENTER <br />56"-UP <br />2-1/2" x 2-1/2" <br />6" ON CENTER <br />NOTES: <br />1. WHERE MANUFACTURER'S INSTALLATION INSTRUCTIONS EXCEED <br />THE REQUIREMENTS OF THIS DETAIL. THEY SHALL BE FOLLOWED. <br />2. FIRE DAMPER SHOWN - SMOKE DAMPER INSTALLATION IDENTICAL <br />EXCEPT FOR DAMPER OPERATOR MECHANISM. <br />3. VERTICAL DAMPER SHOWN - HORIZONTAL INSTALLATION SIMILAR <br />EXCEPT WITH SPRING LOADED DAMPER. <br />4. ASSEMBLY SHALL CARRY UL 555 LABEL <br />5. FIRE DAMPERS SHALL BE FACTORY FABRICATED AIR TIGHT, NOT <br />SEALED BY THE CONTRACTOR OR ON SIGHT. <br />INTERNAL INSULATION <br />WHERE REQUIRED. - <br />ROOF CURB <br />ATTACHED TO zi--� <br />STRUCTURE WITH <br />#12 SCREWS AT <br />MIN. 4" O.C. -� <br />ROOF OPENING <br />GOOSENECK PAINT TO <br />MATCH ROOF <br />,---BIRD SCREEN W/ <br />REMOVABLE FLANGE <br />(ENTIRE ASSEMBLY TO BE <br />PAINTED TO MATCH ROOF) <br />ter -FASTEN GOOSENECK TO <br />CURB WITH MINIMUM THREE <br />#12 SCREWS PER SIDE <br />ROOF CONSTRUCTION, <br />SEE ARCHITECTURAL <br />DRAWINGS. <br />-DUCT, SEE DRAWINGS <br />FOR SIZES. <br />DUCT THRU ROOF DETAIL <br />SCALE: N.T.S. <br />NOTE: <br />MODULE WITH NEGATIVE <br />STATIC PRESSURE. <br />(H) MI <br />1 INCI <br />STATIC <br />X=1/2 (H) <br />(MINIMUM) <br />DRAIN <br />PLUG --,U <br />TRAP D ETAI L <br />SCALE: N.T.S. <br />HANGER <br />SUPPORTS <br />SIZES <br />SHOWN <br />ARE <br />FREE <br />AREA <br />GENERAL MECHANICAL NOTES <br />1. THESE DRAWINGS ARE INTENDED TO BE SCHEMATIC AND DIAGRAMMATIC IN NATURE AND ARE NOT TO BE SCALED. REFER TO ACTUAL SITE LOCATIONS FOR PLACEMENT OF <br />EQUIPMENT. THE CONTRACTOR SHALL NOTIFY THE OWNER OR OWNER'S REPRESENTATIVE IF THERE ARE SUBSTANTIAL DISCREPANCIES BETWEEN THESE CONTRACT DRAWINGS <br />AND ACTUAL SITE CONDITIONS PRIOR TO CONTINUING WORK. CONTRACTOR SHALL MAINTAIN A RED MARKED SET AT ALL TIMES. <br />2. THE CONTRACTOR SHALL VISIT THE JOB SITE AND BE FAMILIAR WITH EXISTING CONDITIONS PRIOR TO ORDERING OR FABRICATING ANY EQUIPMENT, DUCTWORK, ETC.. NO <br />ALLOWANCES WILL BE MADE FOR THE CONTRACTOR'S UNFAMILIARITY WITH THE EXISTING JOB SITE AND CONDITIONS. <br />3. THE CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO OWNER AND LANDLORD'S PROPERTY DURING THE COURSE OF HIS CONSTRUCTION. THIS INCLUDES <br />REPLACING DAMAGED CEILING TILES. <br />4. THE CONTRACTOR IS RESPONSIBLE FOR INSURING THE INTEGRITY OF THE ROOF STRUCTURE. <br />5. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. <br />6. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. <br />7. PROVIDE TURNING VANES IN ALL RECTANGULAR AND SQUARE DUCT ELBOWS. INSTALL DUCT WORK IN ACCORDANCE WITH SMACNA GUIDELINES. PROVIDE HANGER AND DUCT <br />WORK ACCESSORIES AS PER SMACNA RECOMMENDATIONS. PROVIDE BALANCING DAMPERS ON ALL BRANCH DUCT TAKE OFFS. <br />8. ALL NEW DUCT WORK SHALL BE SHEET METAL AND HAVE A MINIMUM INSTALLED INSULATED "R" VALUE EQUAL TO 6.0 <br />9. WHERE DUCT IS VISIBLE THROUGH DIFFUSERS AND/OR GRILLES, IT SHALL BE PAINTED FLAT BLACK. <br />10. ALL VOLUME DAMPERS SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION OR AN ACCESS DOOR SHALL BE PROVIDED. <br />11. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITIONS OF ASHRAE, SMACNA, FLORIDA BUILDING CODE -MECHANICAL, NFPA, EPA, AND GOVERNMENT <br />REGULATIONS. <br />12. CONTRACTOR SHALL COORDINATE WITH ARCHITECT LOCATION OF MAINTENANCE ACCESS PANELS WHERE REQUIRED. <br />13. ALL NEW SUSPENDED CEILING DIFFUSERS SHALL BE TITUS MODEL TMS-A SUSPENDED CEILING DIFFUSER, 24"x24", MAX NC=30, WITH OPPOSED BLADE DAMPER, NECK SIZE <br />& CFM AS LISTED ON DRAWINGS. COLOR SELECTION BY ARCHITECT/OWNER. <br />14. ALL NEW SUSPENDED CEILING RETURN & EXHAUST GRILLES SHALL BE TITUS MODEL 350RL SUSPENDED CEILING GRILLES, 24"x24", MAX NC=30, WITH OPPOSED BLADE <br />DAMPER, NECK SIZE & CFM AS LISTED ON DRAWINGS. COLOR SELECTION BY ARCHITECT/OWNER. <br />15. ALL SIDEWALL DIFFUSERS SHALL BE TITUS MODEL 300FL REGISTERS, MAX NC=30, DOUBLE DEFLECTION, WITH OPPOSED BLADE DAMPER, SIZE & CFM AS LISTED ON <br />DRAWINGS. COLOR SELECTION BY ARCHITECT/OWNER. <br />16. ALL NEW SIDEWALL RETURN & TRANSFER GRILLES SHALL BE TITUS MODEL 355FL GRILLES, SLOPED BLADES, MAX NC=30, WITH OPPOSED BLADE DAMPER, SIZE & CFM AS <br />LISTED ON DRAWINGS. COLOR SELECTION BY OWNER. <br />17. PROVIDE MANUFACTURER'S SUPERVISED STARTUP AND FOUR HOURS OF TRAINING ON NEW AC EQUIPMENT, CONTROLS, AND OTHER NEW ITEMS. REVIEW OPERATING AND <br />MAINTENANCE PROCEDURES WITH OWNER'S APPROPRIATE PERSONNEL. PROVIDE OWNER WITH THREE SETS OF WARRANTY, OPERATION AND MAINTENANCE INFORMATION IN A <br />BINDER LABELED HVAC EQUIPMENT 0&M MANUAL. <br />18. PROVIDE THE SERVICES OF AN AABC AND NEBB CERTIFIED TEST AND BALANCE AGENCY TO COMPLETELY BALANCE THE HVAC SYSTEMS. PROVIDE THREE SETS OF REPORTS TO <br />THE OWNER (1 FOR THE ENGINEER). BALANCING SHALL BE COMPLETE PRIOR TO CEILING INSTALLATION. AFTER THE PROJECT RENOVATION AREA TEST AND BALANCE IS <br />COMPLETE, THE TEST AND BALANCE COMPANY SHALL PROVIDE BUILDING PRESSURIZATION TESTING ON EACH OF THE MAIN ENTRY DOORS OF THE BUILDING AND RECORD THE <br />BUILDING PRESSURIZATION. THE BUILDING SHALL BE OPERATE POSITIVELY PRESSURIZED (MINIMUM 0.02 INCHES W.G.) RELATIVE TO THE OUTDOOR PRESSURE. <br />19. ALL MATERIALS REMOVED AND DISPOSED OF SHALL BE DONE IN ACCORDANCE WITH ALL APPLICABLE CODES. <br />20. ALL EQUIPMENT PROVIDED AND INSTALLED SHALL CONFORM TO ALL APPLICABLE WIND CODES. <br />COMPRESSION STRAP ON FLEXDUCT <br />TO ENSURE AIRTIGHT JOINT <br />MINIMUM 3 EQUIVALENT DUCT <br />DIAMETERS OF STRAIGHT DUCT ON <br />AIR TERMINAL INLET RECOMMENDED. <br />INLET DUCT <br />CONTROL BOX - / <br />DAMPER SHAFT/ACTUATOR <br />MINIMUM 48" OF STRAIGHT DUCT DOWNSTREAM <br />UNIT BEFORE FIRST RUNOUT. INSIDE OF THE <br />DUCT SHOULD BE EQUAL TO DISCHARGE SIZE. <br />ELECTRIC HEATER <br />CONTROL AREA <br />VAV BOX D ETAI L <br />N.T.S. <br />DETAIL APPLIES TO CUT INSULATION TO PROPER <br />RECTANGLE AND ROUND DUCT LENGTH TO AVOID <br />STAPLE 2" FLANGE THEN COMPRESSION OF INSULATION <br />TAPE OVER THE JOINT. <br />ADD MASTIC TO PROVIDE 2" MINIMUM <br />VAPOR -TIGHT SEAL. THICKNESS FLEXIBLE <br />FIBERGLASS <br />INSULATION, R>! 8.0 <br />l � - <br />DUCT <br />SEAL ALL DUCT - <br />SEAMS AND JOINTS <br />WITH HARDCAST (TYP.) <br />NOTE <br />SECURE INSULATION WITH WELDED STICK <br />PINS ON DUCTWORK 24" AND LARGER. <br />TYPICAL DUCT WRAPPING DETAIL <br />SCALE: N.T.S. <br />SPIN -IN FITTING: <br />WITH AIR SCOOP & <br />VOLUME DAMPER <br />HANGER STRAP <br />(TYPICAL) <br />ROUND "SNAPLOCK" SHEET <br />METAL FOR RUN -OUTS WITH <br />INSULATION ® R=6.0 <br />SHEET METAL <br />90' ELBOW <br />�- L--------- <br />MINIMUM RADIUS EQUAL <br />TO THE FLEX DUCT <br />DIAMETER ! <br />SADDLE <br />FLEXIBLE DUCT: INSULATED, DO NOT SAG OR <br />KINK <br />WRAP INSULATION ABOVE CEILING DIFFUSER AND <br />PROVIDE CONTINUOUS VAPOR BARRIER FROM <br />DUCT AROUND ENTIRE DIFFUSER. AIR DEVICE D ETAI L <br />SCALE: N.T.S. <br />NOTE <br />1. HANGER SUPPORTS SHALL BE PER SMACNA AND APPLICABLE SPECIFICATIONS. <br />2. ELBOWS SHALL BE SQUARE NECK (SAME IN AND OUT DIMENSION) WITH 2" DOUBLE THICKNESS <br />TURNING VANES. <br />3. OFFSETS SHALL NOT EXCEED 30 DEGREE ANGLE, AND SHALL NOT REDUCE THE FREE AREA OF THE <br />DUCT. <br />4. TRANSITIONS SHALL NOT EXCEED 1:3 RATIO (4" TRANSITION PER FOOT SINGLE SIDED TRANSITION, AND <br />8" PER FOOT DOUBLE SIDED TRANSITION). <br />5. RECTANGULAR BRANCH CONNECTIONS SHALL BE 45 DEGREE ENTRY TYPE, WITH METAL SLEEVE & <br />CLINCH LOCK CONNECTION. ENTRY LENGTH SHALL BE 25% OF BRANCH DUCT WIDTH. <br />6. ROUND BRANCH DUCT CONNECTIONS SHALL BE SPIN -IN FITTINGS, WITH AIR SCOOP, DAMPER AND <br />HANDLE. <br />7. FLEXIBLE ROUND DUCT SHALL INCLUDE: BLANKET INSULATION AT A MINIMUM 6.0 R VALUE, AN <br />ALUMINUM FOIL OUTER VAPOR BARRIER, AND BE UL-181 APPROVED. <br />8. FLEXIBLE ROUND DUCT SHALL BE A MAXIMUM LENGTH OF 48" OR 105% OF THE DISTANCE BETWEEN <br />THE TWO SHEET METAL DUCT CONNECTIONS, WHICHEVER IS LESS. <br />DISCHARGE DUCT <br />STRAP HANGERS <br />TRAPEZE HANGERS <br />HANGER STRAPS <br />TRAP OR <br />ANGLE <br />SCREWS <br />ROD <br />HANGER STRAP <br />� <br />LOAD RATED <br />FASTENERS <br />L -LOAD RATED <br />FASTENERS <br />STRAP <br />50"DIA. MAX. <br />ATTACHMENT <br />24" DIA. MAX. <br />BAND OF SAME <br />HANGER <br />SIZE AS HANGER <br />RODS <br />STRAP <br />HANGER NUTS (TYP.) <br />RODS OR <br />STRAP <br />DUCT <br />HANGER D ETAI L ANGLE IRON (TYP.) <br />SCALE: N.T.S. <br />MAXIMUM <br />PAIR AT 10' <br />PAIR AT 8' <br />PAIR AT 5' <br />PAIR AT 4' <br />HALF OF <br />SPACING <br />SPACING <br />SPACING <br />SPACING <br />DUCT <br />STRAP <br />RODE <br />STRAP <br />RODE <br />STRAP <br />RODE <br />STRAP <br />RODE <br />PERIMETER <br />WIRE <br />WIRE <br />WIRE <br />WIRE <br />30" <br />1 "x22 GA. <br />10 GA" <br />(0.135 <br />1 "x22 GA. <br />10 GA » <br />(0.135 <br />1 "x22 GA. <br />12 GAS <br />(0.106 <br />1 "x22 GA. <br />12 GA" <br />(0.106 ) <br />- 72" <br />1 "x 18 GA. <br />3/8" <br />1 "x20 GA. <br />1 /4" <br />1 "x22 GA. <br />1 /4" <br />1 "x22 GA. <br />1 /4" <br />P = 96" <br />1 "x16 GA. <br />3/8" <br />1 "x18 GA. <br />3/8" <br />1 "x20 GA. <br />3/8" <br />1 "x22 GA. <br />1 /4" <br />- 120" <br />1.5"x 16 GA. <br />1/2" <br />1 "x 16 GA. <br />3/8" <br />1 "x 18 GA. <br />3/8" <br />1 "x20 GA. <br />1 /4" <br />= 168" <br />2 <br />1.5"x 16 GA. <br />1/2" <br />1.5"x 16 GA <br />1/2" <br />1 "x 16 GA. <br />3/8" <br />1 "x 18 GA. <br />3/8" <br />-- - 192" <br />--- <br />1/2" <br />1.5"x16 GA <br />1/2" <br />1"x16 GA. <br />3/8" <br />1"x16 GA. <br />3/8" <br />193" <br />UP <br />SPECIAL ANALYSIS REQUIRED <br />WHEN STRAPS ARE LAP JOINED <br />SINGLE HANGER MAXIMUM ALLOWABLE LOAD <br />USE THESE MINIMUM FASTENERS: <br />STRAP WIRE OR ROD (DIA) <br />1 "x 18, 20, 22 GA. - TWO <br />1 " 22 GA. - 260 LBS. 0.106" - 80 LBS. <br />#10 OR ONE 1 /4" BOLT <br />1" 20 GA. - 320 LBS. 0.135" - 120 LBS. <br />1 "x 16- TWO 1 /4" BOLT <br />1" 18 GA. - 420 LBS. 0.162" - 160 LBS. <br />1 "x 16- TWO 3/8" BOLT <br />1" 16 GA. - 700 LBS. 1 /4" - 270 LBS. <br />FASTENERS SHALL BE PLACED <br />1.5" 16 GA. - 1100 LBS. 3/8" - 680 LBS. <br />N SERIES NOT SIDE BY SIDE <br />1/2" - 1250 LBS. <br />5/8" - 2000 LBS. <br />3/4" - 3000 LBS. <br />NOTES: <br />1. DIMENSIONS OTHER THAN GAUGE ARE IN INCHES. <br />2. TABLES ALLOW FOR DUCT WEIGHT, 1 LB./SF. INSULATION WEIGHT AND NORMAL <br />REINFORCEMENT AND TRAPEZE WEIGHT, BUT NO EXTERNAL LOADS. <br />3. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL. <br />4. ALLOWABLE LOADS FOR P/2 ASSUME THAT DUCTS ARE 16 GA. MAX., EXCEPT THAT WHEN <br />MAX. DUCT DIMENSION (W) IS OVER 60" THEN P/2 MAX. IS 1.25 W. <br />uwozmp:' <br />URSANoR.DER.(t ,p„ i11c. <br />5001> �rri.rth .•INcro:; street .3 4F• f 5 <br />pRUy- t o.. .tampa mc. <br />These plane era mpynghted and ere subject b <br />copynpht pmtemm se an lerchdwho work' under <br />wbon 102 of The copyright ad 17 u e.c. se <br />amended Dearnber 1990 end known"emhi"cWrsl <br />works mpyoght pm"cbon act of 19% The <br />pm0ecbm includes but n not km-"d m u" Neae9 <br />V. m wd ee sr"ngement end mrnpneiam d <br />spec" and element. of the design under such <br />prabekm, unsudtmzW u" of these plans. work a <br />hmte mpeean"d. can Ugady result m But c"wdm <br />of mnabucbon a b."inp being owed N. <br />monetary mmpanwbm" URBANcRDEPYbur" sic <br />Fkelds "giebabm AA26DO2460. <br />ISSUE DATE <br />09/21 /2020 <br />REVISIONS <br />0 <br />co <br />- <br />- <br />m <br />L- <br />0 <br />L.L <br />L <br />ca <br />(j) <br />Q <br />- <br />w <br />- <br />"- <br />Nc <br />� <br />L <br />N <br />`< <br />00 <br />�. <br />MN <br />DATE: <br />11 /13/2020 <br />DRWN: <br />S.J.M. <br />CHKD: <br />S.J.M. <br />SCALE: <br />N.T.S. <br />SHEET NUMBER <br />M�4 <br />