GENERAL NOTE: VERIFY ALL PIPE SIZES, EQUIPMENT LOCATIONS AND
<br />CONSTRUC-nOISLDETAILS WITH DENTAL EQUIPMENT SUPPLIER PRIOR TO
<br />ANY CONSTRUCTION ACTNRY OR QRDERING MATERIALS. IN CASE OF
<br />1 MEDICAL GAS PLAN
<br />P-3 SCALE: 1/4" = 1'-0"
<br />►1,12 C�liil
<br />MEDICAL GAS LEGEND
<br />AIR — AIR
<br />— D D D —
<br />N20 N20
<br />N2 — N2
<br />02 02
<br />VAC VAC
<br />—
<br />-V--- V - - -V
<br />--
<br />COMPRESSED AIR PIPING
<br />DRAIN PIPING
<br />NITROUS OXIDE PIPING
<br />NITROGEN PIPING
<br />OXYGEN PIPING
<br />VACUUM PIPING
<br />VENT PIPING
<br />KEYED NOTES: O
<br />1. NEW MEDICAL AIR COMPRESSOR BY DENTAL EQUIPMENT SUPPLIER (DES). PROVIDE ALL OPTIONS
<br />AND ACCESSORIES AS REQUIRED BY DES. PROVIDE 2" PVC INTAKE PIPE TO ROOF CAP & MAINTAIN
<br />10 FEET CLEARANCE FROM ALL EXHAUSTS.
<br />2. NEW VACUUM PUMP BY DES. PROVIDE ALL OPTIONS AND ACCESSORIES AS REQUIRED BY DES.
<br />PROVIDE 2" PVC INTAKE PIPE TO ROOF CAP & MAINTAIN 10 FEET CLEARANCE FROM ALL EXHAUSTS.
<br />ROUTE DRAIN PIPE INDIRECT TO FLOOR DRAIN WITH MIN. 1 " AIR GAP.
<br />3. NEW DENTAL UTILITY STATION BY DES.
<br />4. NEW AIR OUTLET LOCATED ABOVE COUNTERTOP.
<br />5. NEW VACUUM INLET LOCATED ABOVE COUNTERTOP.
<br />6. NEW AREA ALARM BY DES. CONNECT POWER VIA CORD/PLUG TO RECEPTACLE LOCATED ABOVE
<br />CEILING.
<br />7. NEW MASTER CONTROL VALVE BY DES. CONNECT POWER VIA CORD/PLUG TO RECEPTACLE LOCATED
<br />ABOVE CEILING.
<br />8. NEW OXYGEN AND NITROUS OXIDE BOTTLE TANK STORAGE CLOSET. MANIFOLD TANKS TOGETHER
<br />ACCORDING TO DES DETAILS. PROVIDE FULLY LOUVERED CLOSET DOOR FOR VENTILATION TO BE
<br />PROVIDED BY FAN IN BREAK ROOM.
<br />MEDICAL GAS SPECIFICATIONS
<br />1.GENERAL
<br />A.PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM AS OUTLINED IN THE CONTRACT DRAWINGS AND
<br />THESE SPECIFICATIONS.
<br />B. NOTE THAT DRAWINGS ARE DIAGRAMMATIC ONLY AND INTENDED TO SHOW THE GENERAL ARRANGEMENT OF SYSTEMS, NOT EVERY
<br />MINUTE DETAIL.
<br />C.DO NOT SCALE PLANS.
<br />D.PROVIDE ALL NECESSARY FITTINGS, TRANSITITONS, CONNECTORS, ETC. WHETHER SHOWN OR NOT ON PLANS.
<br />E.ALL WORK IS NEW UNLESS OTHERWISE NOTED.
<br />FALL WORK SHALL CONFORM TO THE FOLLOWING CODES (AS APPLICABLE) AS WELL AS ALL LOCAL REGULATIONS, ORDINANCES, AND
<br />AMENDMENTS:
<br />2007 FLORIDA BUILDING CODE W/ 2009 SUPPLEMENT
<br />2002 NFPA 99
<br />2.SCOPE OF WORK
<br />PROVIDE NEW MEDICAL GAS PIPING, EQUIPMENT, AND ACCESSORIES AS SHOWN ON THIS PLAN AND THE DENTAL EQUIPMENT SUPPLY
<br />DRAWINGS.
<br />3.ITEMS FURNISHED BY CONTRACTOR
<br />IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE ALL MATERIALS, EQUIPMENT, AND ACCESSORIES NECESSARY TO MAKE
<br />A COMPLETE INSTALLATION. ALL EQUIPMENT SHALL BE STORED IN A SAFE, DRY PLACE IN THE MANUFACTURER'S ORIGINAL PACKAGING
<br />UNTIL READY FOR USE. THE OWNER SHALL NOT BE RESPONSIBLE FOR PROVIDING ANY PART OF THE PROJECT, UNLESS SPECIFICALLY
<br />NOTED. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR PAYING ALL REQUIRED FEES, OBTAINING ALL PERMITS, AND ARRANGING FOR
<br />ALL INSPECTIONS.
<br />4.WORK IN EXISTING BUILDINGS
<br />A.DO NOT USE POWDER DRIVEN FASTENERS OF ANY TYPE.
<br />BALL ITEMS REMOVED AND NOT RE -USED SHALL BE TURNED OVER TO THE OWNER. CONTRACTOR SHALL REMOVE ANY UNSATISFACTORY
<br />ITEMS FROM THE PROJECT SITE.
<br />C.SOME EXISTING ITEMS TO REMAIN WITHOUT WORK ARE SHOWN FOR CLARITY OR REFERENCE ONLY. NOTE THAT ADDITIONAL ITEMS
<br />WITHOUT WORK MAY ALSO BE PRESENT.
<br />D.DRAWINGS OF EXISTING SYSTEMS ARE BASED ON EXISTING DOCUMENTS AND FIELD CONDITIONS, SOME OF WHICH MAY BE UNVERIFIED.
<br />PRIOR TO SUBMITTING A BID, CONTRACTOR SHALL STUDY THE PLANS AND VISIT THE PROJECT SITE IN ORDER TO BECOME FAMILIAR
<br />WITH EXISTING CONDITIONS. ANY DISCREPANCIES IN THE CONTRACT DOCUMENTS WHICH COULD SIGNIFICANTLY IMPACT THE PROJECT
<br />BUDGET OR SCHEDULE MUST BE REPORTED TO THE ENGINEER IN WRITING IMMEDIATELY. FAILURE TO DO SO WILL NOT BE SUFFICIENT
<br />CAUSE FOR DELAYS OR CHANGES LATER IN THE PROJECT. CHANGE ORDERS RESULTING FROM FAILURE TO PROPERLY INVESTIGATE
<br />EXISTING FIELD CONDITIONS WILL NOT BE ACCEPTED. ALL WORK IS NEW UNLESS OTHERWISE NOTED.
<br />E.MODIFICATIONS TO EXISTING SYSTEMS NECESSARY TO CONNECT TO NEW WORK SHALL BE CONSIDERED TO BE PART OF THE BASIC
<br />WORK OF THIS CONTRACT.
<br />F. COORDINATE ALL WORK SCHEDULES WITH THE OWNER TO MINIMIZE DISRUPTIONS TO EXISTING SYSTEMS OUTSIDE THIS SCOPE OF WORK.
<br />5.000RDINATION
<br />ALL WORK ON THIS PROJECT SHALL BE COORDINATED WITH ALL OTHER TRADES. CONTRACTOR SHALL REVIEW PLANS OF ALL DISCIPLINES
<br />INVOLVED AND ADVISE THE ARCHITECT IN WRITING OF ANY CONFLICTS, CODE OR SAFETY ISSUES THAT MAY EXIST PRIOR TO ANY
<br />FABRICATION OR ORDERING OF EQUIPMENT. PROVIDE ROUTING AND OFFSETS NECESSARY TO AVOID CONFLICTS WITH STRUCTURE, FINISHES,
<br />AND WORK OF OTHERS. CONTRACTOR SHALL PROVIDE ALL CORE PENETRATIONS AND PATCHING FOR PIPING FLOOR PENETRATIONS.
<br />6.MEDICAL GAS GENERAL
<br />A.ALL MEDICAL GAS SYSTEMS INSTALLATION SHALL BE COORDINATED WITH THE OWNER, ARCHITECT, AND DENTAL EQUIPMENT SUPPLIER
<br />PRIOR TO ROUGH IN. IN CASE OF CONFLICTS THE DENTAL EQUIPMENT SUPPLIER DRAWINGS & SPECS SHALL GOVERN.
<br />B.INSTALL ALL WORK IN COMPLIANCE WITH ADA REQUIREMENTS AS NECESSARY.
<br />CALL PIPING SHALL BE CONCEALED IN WALLS, FLOORS, CHASES, CEILINGS, ETC. UNLESS SPECIFICALLY NOTED ON DRAWINGS. ANY PIPING
<br />OR ACCESSORIES THAT MUST BE EXPOSED SHALL HAVE A POLISHED CHROME FINISH.
<br />D.000RDINATE THE ELECTRICAL CHARACTERISTICS OF ALL ELECTRICAL EQUIPMENT WITH THE ELECTRICAL CONTRACTOR PRIOR TO ORDERING.
<br />E.PROVIDE LABELS AT REGULAR INTERVALS FOR ALL PIPING ABOVE GROUND. LABELS SHALL STATE THE TYPE OF FLUID OR PIPE SERVICE
<br />AND FLOW DIRECTION.
<br />7.MEDICAL GAS PIPING
<br />A.ALL MEDICAL GAS PIPING SHALL BE CONSTRUCTED OF OXYGEN GRADE TYPE "L" COPPER WITH SILVER SOLDERED JOINTS.
<br />BALL PIPING SHALL BE SIZED PER THE DRAWINGS OR NFPA 99, WHICHEVER SIZE IS GREATER.
<br />CALL VACUUM PIPING SHALL BE MIN. 3✓4" SIZE.
<br />D.PIPING FOR ALL OTHER GASES SHALL BE MIN 16" SIZE.
<br />E.ALL PIPING SHALL BE RUN BELOW FLOOR AS SHOWN TO INDICATED INLET & OUTLET LOCATIONS. FOR ALL PIPING BELOW FLOORS,
<br />MAKE EVERY ATTEMPT POSSIBLE TO MINIMIZE THE NUMBER OF JOINTS BELOW THE FLOOR.
<br />8.MEDICAL GAS EQUIPMENT AND ACCESSORIES
<br />A.PROVIDE AND INSTALL ALL EQUIPMENT AS SPECIFIED BY THE MEDICAL OR DENTAL EQUIPMENT SUPPLIER.
<br />B.PROVIDE SHUTOFF VALVES AT ALL CONNECTIONS TO MEDICAL GAS EQUIPMENT.
<br />C.PROVIDE DISCONNECT SWITCHES WITH ALL ELECTRICAL EQUIPMENT,
<br />D.PROVIDE ZONE ISOLATION AND CONTROL VALVES AT LOCATIONS SPECIFIED ON DRAWINGS OR ELSEWHERE AS REQUIRED BY NFPA 99.
<br />A.MOUNT ALL WALL DEVICES MIN 42" A.F.F. OR 6" ABOVE COUNTER, UNLESS OTHERWISE NOTED ON DRAWINGS. COORDINATE EXACT
<br />LOCATION WITH OWNER, MEDICAL/DENTAL EQUIPMENT SUPPLIER, AND ARCHITECT PRIOR TO ROUGH IN.
<br />9. PENETRATIONS
<br />A.ALL PENETRATIONS THROUGH RATED WALLS OR FLOORS SHALL BE SEALED WITH AN APPROVED FIREPROOFING TO MAINTAIN THE
<br />INTEGRITY OF THE WALL OR FLOOR.
<br />B.ALL PIPING PASSING THROUGH BUILDING STRUCTURE OR RATED WALLS OR FLOORS SHALL BE SLEEVED.
<br />C.ALL PIPE SLEEVES SHALL BE SIZED AND INSTALLED TO ALLOW FOR PIPE EXPANSION.
<br />D.SUBMIT ALL SLEEVE SIZES AND LOCATIONS TO THE STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO STARTING WORK.
<br />10. WARRANTIES AND MAINTENANCE
<br />A.ALL FIXTURES SHALL BE TESTED, CLEANED, AND PLACED IN GOOD OPERATING CONDITION BY THE CONTRACTOR. CONTRACTOR SHALL
<br />GUARANTEE ALL EQUIPMENT, MATERIALS, AND WORKMANSHIP TO BE FREE OF DEFECTS FOR A PERIOD OF ONE YEAR FROM THE DATE
<br />OF ACCEPTANCE BY THE OWNER AND THE CONTRACTOR SHALL REPAIR ANY SUCH DEFECTS AT NO COST TO THE OWNER. ALL
<br />EQUIPMENT INCLUDED IN THE PROJECT SHALL BE COVERED BY THE MANUFACTURER'S WARRANTY FOR THE DURATION OF THAT
<br />WARRANTY. COPIES OF ALL MANUFACTURER'S WARRANTIES AND CONTRACTOR WARRANTIES SHALL BE PROVIDED TO THE OWNER AT FINAL
<br />ACCEPTANCE.
<br />B.CONTRACTOR SHALL RECORD DRAWINGS DURING CONSTRUCTION AND NOTE LOCATIONS OF ANY OFFSETS OR OTHER DEVIATIONS FROM
<br />THE ORIGINAL CONTRACT DOCUMENTS. AT THE CLOSE OF THE PROJECT, CONTRACTOR SHALL PROVIDE A COPY OF THESE DRAWINGS TO
<br />THE OWNER AS "AS-BUILTS".
<br />DCH PROJECT NUMBER: 11-002
<br />TO THE BEST OF THE KNOWLEDGE OF THE ARCHITECTS AND
<br />ENGINEERS, SAID PLANS AND SPECIFICATIONS COMPLY WITH THE
<br />2007 FLORIDA BUILDING CODE WITH 2O09 SUPPLEMENTS AND THE
<br />APPLICABLE MINIMUM FIRE SAFETY STANDARDS.
<br />ALL DIMENSIONS AND JOB CONDITIONS SHALL BE VERIFIED BY THE
<br />CONTRACTOR, ANY AND ALL DISCREPANCIES SHALL BE REPORTED
<br />TO THE ARCHITECT PRIOR TO COMMENCEMENT OF CONSTRUCTION.
<br />THE DRAWINGS & DESIGN ARE VALID FOR 12 MONTHS FROM DATE
<br />OF ORIGINAL SEAL.
<br />ISSUE
<br />DATE
<br />REVIEW
<br />1 /27/11
<br />PERMIT
<br />1 /27/11
<br />REV.
<br />REV.
<br />REV,
<br />REV.
<br />THESE DOCUMENTS, DESIGNS, NOTES, DETAILS AND
<br />SPECIFICATIONS AND CONCEPTS ARE THE SOLE
<br />PROPERTY OF FRAZE DESIGN, INC. AND SHALL NOT BE
<br />REPRODUCED, RE -USED OR COPIED FOR OTHER
<br />PROJECTS, IN WHOLE OR PART WITHOUT THE WRITTEN
<br />CONSENT OF FRANK FRAZE, ARCHITECT, AIA.
<br />ALL RIGHTS ARE RESERVED BY THE ARCHITECT IN
<br />ACCORDANCE WITH U.S. COPYRIGHT AND PATENT
<br />LAWS. UNAUTHORIZED REPRODUCTION WILL BE
<br />PROSECUTED TO THE FULL EXTENT OF THE LAW.
<br />PROFESSIONAL SEAL
<br />®�oottt®ieoo+
<br />o®�® t LEOn j,(� 00
<br />��e 4 � • • • • ° e i�w®I�I
<br />e 1U
<br />.• NS�c ®v,
<br />O ° O
<br />e
<br />® • $ ® (�I
<br />SOf ' 4U
<br />O•a
<br />VINE z �RDO
<br />FLO Gar *ji 009
<br />W)
<br />00
<br />O
<br />o
<br />N
<br />�
<br />m
<br />V)
<br />M
<br />00
<br />�
<br />QI
<br />00
<br />z
<br />N
<br />U
<br />a
<br />00
<br />A
<br />w
<br />w
<br />W
<br />ao
<br />N
<br />M
<br />N
<br />w
<br />W
<br />E
<br />°�z
<br />b�A
<br />OO
<br />m
<br />�
<br />OD
<br />N
<br />m
<br />w
<br />�
<br />o�
<br />w
<br />�
<br />a
<br />SHEET TITLE
<br />MEDICAL GAS
<br />PLANS
<br />SHEET
<br />Pttttt>.
<br />NUMBER
<br />
|