SPLIT SYSTEM SCHEDULE <br />MARK <br />AH/CU: 1-3 <br />AH/CU: 2-2 <br />AH/CU-2-3 <br />SYSTEM <br />TYPE <br />CLG/ELEC HTG <br />CLG/ELEC HTG <br />CLG/ELEC HTG <br />AREA <br />SERVED <br />SEE PLANS <br />SEE PLANS <br />SEE PLANS <br />410A <br />410A <br />410A <br />AIR <br />HANDLER DATA: <br />MANUFACTURER <br />MITSUBISHI <br />TRANE <br />TRANE <br />MODEL NO. <br />MSY-D36 <br />TEMSAOC60 <br />TEM4AOC48 <br />WEIGHT (LBS) <br />40 <br />185 <br />160 <br />CABINET TYPE (VERT/HORIZ) <br />WALL MOUNTED <br />SEE PLANS <br />SEE PLANS <br />CFM TOTAL <br />350-798 <br />1600 <br />1280 <br />CFM O.A. <br />- <br />SEE OA SCHED <br />SEE <br />OA SCHED <br />E. S. P. ( " W. G. ) <br />- <br />.75 <br />.75 <br />H. P. /F. L. A. <br />175 WATTS/. 76 <br />. 75/6. 8 <br />. 75/6. 0 <br />RPM ( SPEED) <br />4 SPEED <br />( HIGH) <br />( HIGH) <br />ELECTRIC HEATER KW <br />--- <br />7.2 <br />7.2 <br />HEATER STAGES <br />--- <br />1 <br />1 <br />HEAT LOCATION (DUCT/INT.) <br />--- <br />INTERNAL <br />INTERNAL <br />VOLTAGE (V/PH/60) <br />208/1/60 <br />208/1/60 <br />208/1/60 <br />POWER CONN. (SINGLE/MULTI) <br />FROM CU <br />SINGLE <br />SINGLE <br />MAX FUSE <br />60 <br />60 <br />CONDENSING <br />UNIT DATA: <br />MANUFACTURER <br />MITSUBISHI <br />TRANE <br />TRANE <br />MODEL NO. <br />MUY-D36 <br />4TTR6060 <br />4TTR4048 <br />WEIGHT (LBS) <br />126 <br />280 <br />220 <br />COMP. QTY <br />1 <br />1 <br />1 <br />COMP. R. L. A. EA. <br />15.0 <br />23,7 <br />18.5 <br />COMP. L. R. A. EA. <br />20.0 <br />152.5 <br />124 <br />TY <br />CONDQFAN H. P. ( EA) <br />214 WATTS <br />1 /5 <br />1 /5 <br />COND FAN F. L. A. ( EA) <br />93 <br />1.05 <br />1.05 <br />VOLTAGE (V/PH/60) <br />208/1/60 <br />208/1/60 <br />208/1/60 <br />MCA <br />21.0 <br />32 <br />24 <br />MAX FUSE <br />25 <br />50 <br />40 <br />DIMEN <br />33X13X34 <br />51x36x39 <br />30x38x35 <br />SYSTEM <br />DATA 95 DEG F AMB : <br />TOTAL COOLING (TMBH) <br />34.6 <br />58.0 <br />47.5 <br />SENSIBLE CAPACITY (SMBH <br />21.5 <br />41.3 <br />33.8 <br />ENT. A I R TEMP. (F) (DB WB <br />80/67 <br />80/67 <br />80 67 <br />COMPRESSOR STAGES S%� <br />28%-100% <br />0/100 <br />0/100 <br />HEATPUMP CAPACITY (MBH) <br />- <br />N/A <br />N/A <br />A. R. <br />I . SYSTEM EFFICIENCIES: <br />SEER HSPF <br />15. 1/- <br />15.25/- <br />14. 5/- <br />EER IPLV/COP <br />-/-/- <br />12.75/-/- <br />12.0/-/- <br />REMARKS: <br />SEE BELOW <br />SEE BELOW <br />SEE BELOW <br />SPLIT SYSTEM NOTES: <br />1. <br />SELECTION BASED ON TRANE, PROVIDE TRANS, CARRIER OR APPROVED EQUAL. <br />2. <br />ALL UNITS MUST BE UL LISTED AND ARI CERTIFIED. <br />3. <br />PROVIDE LIQUID LINE FILTER -DRYER SIGHT -GLASS AND SOLENOID <br />VALVE. <br />4. <br />PROVIDE SERVICE VALVES ON SUCTION AND LIQUID LINES. <br />5. <br />PROVIDE ONE YEAR WARRANTY ON UNIT, 5 YEAR WARRANTY ON <br />COMPRESSOR. <br />6. <br />PROVIDE BUILT-IN FACTORY WIRED UL ELECTRIC HEATER <br />W/HEATER CONTROL PACKAGE. <br />7. <br />PROVIDE PROPER VIBRATION ISOLATION AS PER DRAWINGS AND <br />SPECIFICATION, IF NOT SHOWN, AS PER MANUFACTURER'S <br />RECOMMENDATION. <br />8. <br />SIZE AND RUN COPPER REFRIGERANT PIPING AS PER <br />MANUFACTURERS PUBLISHED RECOMMENDATIONS TO PROVIDE LISTED <br />SENSIBLE AND TOTAL MBH. <br />9. <br />PROVIDE AUX. DRAIN PAN AND A/C CONDENSATE DRAIN LINES <br />WITH A TRAP AND CLEANOUT. <br />10. <br />PROVIDE 3/8" THICK ARMAFLEX FIRE RETARDANT PIPING <br />INSULATION ON A/C CONDENSATE LINES, 1/2" THICK ON REFRIGERANT <br />SUCTION LINES 2-5/8" AND SMALLER, AND 3/4" ON ALL LINES LARGER <br />THAN 2-5/8". PROVIDE AN ALUMINUM JACKET TO PROTECT THE <br />INSULATION ON ALL PIPING OUTDOORS AND IN MECHANICAL ROOMS. <br />OVERLAP END OF JACKET BY THREE INCHES AND SECURE WITH <br />STAINLESS STEEL BANDING. <br />11. <br />PROVIDE FILTER BOX AND TWO SETS OF 1" MERV 11, 60% FILTERS <br />BY <br />TRI-DIM ES60M THROW AWAY FILTERS (800 937-1450). <br />12. <br />E. S. P. DOES NOT INCLUDE COIL OR CABINET LOSSES. <br />13. <br />UNLESS OTHERWISE NOTED CAPACITIES AND EFFICIENCIES ARE AT <br />ARI CONDITIONS: <br />14. <br />COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR <br />ORDERING ANY EQUIPMENT. <br />15. <br />SEE GENERAL, AIR CONDITIONING, DUCTWORK, AND COORDINATION <br />NOTES FOR OTHER FIELD SUPPLIED ITEMS. <br />16. <br />PROVIDE A/C UNITS WITH WIFI PROGRAMMABLE HEATING AND COOLING T-STAT <br />WITH FAN ON -OFF -AUTO SWITCH. SET STAT FOR FAN IN AUTO MODE. <br />FAN SHALL NOT RUN UNLESS THE COMPRESSOR OR HEATER IS ON. <br />HONEYWELL 9000 SERIES OR EQUAL. <br />17. <br />PROVIDE SINGLE POINT POWER ENTRY WITH INTERGAL CIRCUIT BREAKER. <br />FAN SCHEDULE <br />MARK <br />EF: 2-4, 2-5 <br />QUANITY <br />2 <br />TYPE <br />CEILING <br />SERVICE <br />SHOWER <br />MANUFACTURE <br />GREENHECK <br />MODEL NO. <br />SP-A110 <br />WEIGHT <br />17 <br />AIR DATA: <br />C. F. M. <br />100 <br />S. P. <br />125 <br />RPM <br />900 <br />B. H. P. ( WATTS) <br />(29) <br />TIP SPEED <br />- <br />SONES <br />1.2 <br />MOTOR DATA: <br />DRIVE <br />DIRECT <br />M( <br />H. P. (WATTS) <br />(29) <br />VOLT-PH-HZ <br />277/1/60 <br />REMARKS <br />1, 2, 3, 4 <br />FAN NOTES <br />1. SELECTION BASED ON GREENHECK, <br />PROVIDE EQUAL BY BROAN, PENN, <br />LORAN COOK, OR ACME. <br />2. PROVIDE MOTOR STARTERS AND ALL <br />ASSOCIATED CONTROLS ON ALL <br />FANS. <br />3. PROVIDE BACK DRAFT DAMPER FOR <br />ALL EXHAUST FANS. <br />4. SWITCH WITH LIGHT. <br />GENERAL NOTES: <br />1. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, <br />EQUIPMENT, ACCESS PANELS, CONTROL SYSTEMS, DEVICES, PERMITS <br />AND SERVICES NECESSARY FOR FURNISHING AND INSTALLING OF A <br />COMPLETE SERVICEABLE MECHANICAL SYSTEM. <br />2. ALL MECHANICAL SYSTEMS ARE TO BE INSTALLED IN <br />ACCORDANCE WITH ALL APPLICABLE SECTIONS OF THE NFPA <br />STANDARDS, ANSI STANDARDS, THE LOCAL BUILDING CODE, PLANS <br />AND SPECIFICATIONS. <br />3. ALL MATERIALS SHALL BE NEW (UNLESS OTHERWISE <br />INDICATED) AND ANY DAMAGED EQUIPMENT SHALL BE REPLACED. <br />4. CONTRACTOR WILL WARRANTY ALL MECHANICAL SYSTEMS, <br />EQUIPMENT, PARTS AND LABOR, INSTALLED UNDER HIS CONTRACT, <br />FOR A PERIOD OF ONE (1) YEAR AFTER C.O. <br />5. PROVIDE SUBMITTALS IN PDF FORMAT FOR REVIEW BY <br />ARCH/ENGR PRIOR TO PURCHASING ANY EQUIPMENT OR MATERIALS. <br />SUBMITTALS SHALL INCLUDE ALL ITEMS AND MATERIALS SUPPLIED <br />BY CONTRACTOR. SUBMITTALS SHALL HAVE A SUMMARY SHEET <br />SHOWING ALL SCHEDULED INFORMATION. ANY EQUIPMENT OR <br />MATERIALS INSTALLED WITHOUT REVIEWED SUBMITTALS SHALL BE <br />REMOVED AND REINSTALL AT ARCH/ENGR DISCRETION WITH NO <br />ADDITIONAL COMPENSATION TO CONTRACTOR. CONTRACTOR SHALL <br />COORDINATE ALL ASPECTS OF HIS EQUIPMENT WITH ALL OTHER <br />TRADES. <br />5. PROVIDE 2 SETS (PLUS PDF COPY) OF MAINTENANCE AND <br />OPERATION MANUALS ON ALL MECHANICAL EQUIPMENT OR SYSTEMS. <br />7. ALL CUTTING, PATCHING, STRUCTURAL STEEL, WEATHER <br />PROOFING, PAINTING, AND WALL OPENINGS SHALL BE BY THE <br />GENERAL CONTRACTOR. <br />8. ALL LOUVERS, GRILLES, PIPING, ETC. SHALL BE PAINTED TO <br />MATCH SURROUNDING COLOR AND TEXTURES AS REQUIRED BY <br />ARCHITECT. VERIFY COLOR AND TEXTURE WITH ARCHITECT. <br />9. ALL OPENINGS IN BUILDING STRUCTURE, FOR DUCTWORK, <br />PIPING, ETC. TO BE 1/2" LARGER (ON ALL SIDES) THEN THE <br />OUTSIDE DIMENSIONS. FILL VOIDS WITH FIRE RETARDANT <br />SILICONE (I.E. 3MT FIRE BARRIER SILICONE CARTRIDGE <br />2000+, .) . <br />COORDINATION NOTES: <br />1. A/C CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE HIS <br />WORK FOR SIZE, LOCATION, CLEARANCE, ACCESS AND ELECTRICAL <br />CHARACTERISTICS WITH ALL OTHER TRADES AND TO PROVIDE SHOP <br />DRAWINGS TO THE ENGINEER FOR REVIEW BEFORE INSTALLATION OF <br />DUCTWORK OR EQUIPMENT. SHOP DRAWING WILL INCLUDE BEAM OR <br />STRUCTURE ELEVATION & REQUIRED EQUIPMENT ACCESS AREAS. <br />2. WALL, ROOF, AND CEILING OPENINGS INDICATED ON <br />CONTRACTOR DRAWINGS ARE NOMINAL DIMENSIONS ONLY AND ALL <br />DUCT, PIPE OR EQUIPMENT PENETRATIONS SHALL BE SLEEVED AND <br />FIRE RATED AS REQUIRED, ADJUST OPENINGS <br />3. COORDINATE LOCATION OF CEILING DIFFUSERS, GRILLES AND <br />REGISTERS IN THE FIELD WITH LIGHTS, SPRINKLERS AND <br />ARCHITECTURAL ELEMENTS. <br />4. COORDINATE LOCATION OF A/C UNITS, THERMOSTATS, FANS <br />AND DUCTWORK WITH BUILDING STRUCTURE AND OTHER TRADES SO <br />THAT NO INTERFERENCES OCCUR. <br />5. IN GENERAL, DUCT OFFSETS HAVE NOT BEEN SHOWN. A/C <br />CONTRACTOR TO COORDINATE THESE AS REQUIRED. <br />6. MECHANICAL PLANS IN GENERAL, ARE DIAGRAMMATIC IN <br />NATURE, AND ARE TO BE READ IN CONJUNCTION WITH ARCH. <br />PLUMBING, ELECTRICAL AND STRUCTURAL PLANS. DUCT AND PIPING <br />OFFSETS, BENDS AND TRANSITIONS WILL BE REQUIRED TO PROVIDE <br />AND INSTALL A COMPLETE FUNCTIONAL SYSTEM AND SHALL BE <br />PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE <br />OWNER. <br />7. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR <br />TO BIDDING, ORDERING, FABRICATION OR INSTALLATION OF <br />MATERIALS OR EQUIPMENT. ADVISE ENGINEER OF ANY <br />DISCREPANCIES. <br />MECHANICAL EQUIPMENT NOTES: <br />1. ALL MECHANICAL EQUIPMENT SHALL BE ARI & U.L. LISTED <br />WHERE APPLICABLE AND RATED FOR THE REQUIRED SERVICE, <br />PRESSURES, TEMPERATURES, AND SHALL BE PROVIDED WITH ALL <br />NECESSARY TRANSFORMERS, SEALS, VALVES, CONNECTIONS, ETC. TO <br />FUNCTION PROPERLY. <br />2. MOUNT ALL WALL THERMOSTATS AT 48" AFF DUE TO ADA <br />REQUIREMENTS. <br />3. INSTALL ALL EQUIPMENT TO COMPLY WITH THE MANUFACTURERS <br />SPECIFICATIONS AND CLEARANCE REQUIREMENTS. <br />4. ALL INSULATION WILL HAVE FIRE/SMOKE RATING LESS THAN <br />25/50. <br />5. PROVIDE A MIN. OF 3' CLEARANCE IN FRONT OF ALL 120-240 <br />VOLT RATED AND 4' CLEARANCE IN FRONT OF ANY 277-480 VOLT <br />RATED PANELS AND DISCONNECTS. PROVIDE ADEQUATE SIDE <br />CLEARANCE PER NEC. <br />6. PROVIDE IONIZATION TYPE AIR DUCT SMOKE DETECTORS WITH <br />ACCESS DOORS, WHERE INDICATED ON PLANS. ALL SMOKE <br />DETECTORS SHALL BE BY ONE MANUFACTURE, COORDINATE VOLTAGE <br />ETC. WITH ELECTRICAL CONTRACTOR AND FIRE ALARM SYSTEM <br />BEFORE ORDERING. UPON DETECTION, SMOKE DETECTORS SHALL <br />SHUT DOWN ASSOCIATED AIR MOVING EQUIPMENT AND ALL AIR <br />MOVING EQUIPMENT SERVING THAT COMMON PLENUM. CONNECT SMOKE <br />DETECTOR TO BUILDING CENTRAL FIRE ALARM SYSTEM. THE <br />ACTUATION OF A DUT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE <br />AND AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED <br />LOCATION. IF THE BUILDING DOES NOT HAVE A CENTRAL FIRE <br />ALARM SYSTEM, PROVIDE REMOTE ANNUNCIATOR/TEST STATION WITH <br />VISIBLE AND AUDIBLE SIGNAL IN AN APPROVED LOCATION. (PER <br />NFPA 90A CH 4-4. 4 AND FMC 606. 4. 1) . DUCT SMOKE DETECTOR <br />SHALL BE "SYSTEM SENSOR" - DH400ACDCI WITH APA451 <br />ANNUNCIATOR OR EQUAL. <br />7. PROVIDE FLEXIBLE DUCT CONNECTORS, RATED AS REQUIRED, <br />TO ALL FANS, A/C UNITS, OR MECHANICAL EQUIPMENT, EXCEPT <br />FANS USED FOR GREASE EXHAUST. <br />8. PROVIDE VIBRATION ISOLATORS ON ALL MECHANICAL <br />EQUIPMENT AS CALLED FOR IN THE SPECIFICATIONS OR DETAILS. <br />IF NOT SPECIFIED, AS RECOMMENDED BY MANUFACTURER FOR QUIET <br />AND VIBRATION FREE OPERATION. <br />9. PROVIDE A MIN. OF 10' CLEARANCE BETWEEN O/A INTAKES <br />AND VTR OR EXHAUST OPENINGS. <br />10. HVAC CONTRACTOR SHALL TEST AND BALANCE ALL MECHANICAL <br />EQUIPMENT, AIR DEVICES, EXTRACTORS, DAMPERS, A/C UNITS, <br />FANS, ETC. TO PROVIDE THE DESIGN QUANTITIES AS SHOWN ON THE <br />PLANS OR SCHEDULES. T&B WORK SHALL INCLUDE ADJUSTING (OR <br />REPLACING) PULLEYS AND DRIVE SETTINGS AS REQUIRED TO <br />PROVIDE AIR FLOWS INDICATED. PROVIDE A WRITTEN T & B <br />REPORT IN ACCORDANCE WITH THE AIR BALANCE COUNCIL <br />STANDARDS. <br />11. RUN CONDENSATE DRAINS TO LANDSCAPE AREA. GRAVITY <br />CONDENSATE DRAINS SHALL BE A MINIMUM OF 3/4" UP TO 10 TONS, <br />1" UP TO 25 TONS. SIZES ARE FOR TOTAL CONNECTED TONNAGE. <br />CONDENSATE DRAINS SHALL BE SCHEDULE 40 PVC. INSULATE ALL <br />CONDENSATE PIPING INSIDE THE BUILDING WITH 1/2" ARMAFLEX. <br />12. MOUNT ALL OUTDOOR EQUIPMENT FOR WIND LOADS AND <br />MOUNTING HEIGHTS AS REQUIRED BY LOCAL CODES. <br />13. PROVIDE STRANDED COPPER CONTROL WIRING. <br />14. ALL PIPING AND DUCTWORK SHALL BE SLEEVED THRU WALLS, <br />BEAMS, SLABS, ETC, AS REQUIRED AND COORDINATED WITH THE <br />STRUCTURAL ENGINEER. PROVIDE NECESSARY TRANSITIONS AS <br />REQUIRED FOR DUCTWORK INSTALLATION. <br />15. CONTRACTOR SHALL PROVIDE A COMPLETE PREVENTIVE <br />MAINTENANCE FOR EXISTING UNITS. PREVENTIVE MAINTENANCE <br />SHALL INCLUDE AS A MINIMUM, CLEANING EVAPORATOR COIL, <br />CONDENSER COIL, AND CONDENSATE DRAIN PAN, CHECK REFRIGERANT <br />PRESSURES, AND REPLACE FILTERS. <br />16. CONTRACTOR WILL PROTECT THE AIR-CONDITIONING UNITS AND <br />DUCTWORK IN THE FOLLOWING MANNER FOR BOTH NEW AND EXISTING <br />EQUIPMENT. PRE -FILTER ALL RETURN AIR GRILLES WITH ROLL <br />TYPE FILTER MEDIA AND REPLACE IT AS NEEDED THROUGHOUT THE <br />CONSTRUCTION PERIOD. EQUIPMENT MUST NOT BE STARTED FOR ANY <br />PURPOSE UNTIL THE DRYWALL SANDING, ETC. IS COMPLETED. ONCE <br />DRYWALL SANDING IS COMPLETED, THE UNITS MAY BE STARTED ONCE <br />THE ABOVE PRE -FILTERING IS COMPLETED. <br />DUCTWORK & ACCESSORIES NOTES : <br />1. ALL DUCTWORK SHALL BE AS FOLLOWS OR APPROVED EQUAL: <br />a) SUPPLY - MANVILLE SUPERDUCT 1-1/2" 3/4 LB FIBERGLASS <br />DUCTBOARD R=6. 0. <br />b) RETURN - MANVILLE SUPERDUCT 1-1/2" 3/4 LB FIBERGLASS <br />DUCTBOARD R=6. 0. <br />c) FLEX DUCT - THERMAFLEX G-KM R=6.0, UL-181 CLASS 1. <br />d) ROUND SUPPLY AND RETURN BETWEEN TRUNKDUCT AND <br />FLEXDUCT - (SNAPLOCK) GALVANIZED SHEET METAL, 28 GA MIN., <br />WITH 2" -3/4 PSF R=6. 0 DUCT WRAP. <br />e) O/A - GALV. SHEETMETAL, 28 GA MIN. W/ 1" 3/4 LB WRAP <br />f) EXHAUST - GALV. SHEETMETAL 28 GA MINIMUM. <br />2. ASSEMBLE, INSTALL, AND SEAL DUCTWORK IN ACCORDANCE <br />WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARD". UNLESS <br />OTHERWISE NOTED ON PLANS CONSTRUCT DUCTWORK TO 2" DUCT <br />CLASS, SEAL TO 100% CLOSURE. <br />3. SEAL ALL SHEETMETAL DUCTS JOINTS WITH RCD #8 MASTIC. <br />4. MAKE JOINTS FOR DUCT WRAP AND DUCTBOARD WITH GLASS <br />FABRIC AND VAPOR BARRIER COATING TO 30 MILL DRY FILM <br />THICKNESS, RCD #9. <br />5. CONTRACTOR SHALL PROTECT ALL FIBERGLASS INSULATION <br />PRODUCTS FROM DAMAGE. INSULATION PRODUCTS SHALL NOT BE <br />ALLOWED TO GET WET. INSULATION DAMAGED AS A RESULT OF <br />MOISTURE, VANDALISM, OR CONSTRUCTION TRAFFIC SHALL BE <br />REPLACED. <br />6. PROVIDE MANUFACTURES PREMOLDED INSULATION BLANKET (R=6 <br />MIN) WHEN AVAILABLE. IF NOT AVAILABLE, INSULATE NECKS AND <br />BELLS OF OF ALL SUPPLY AIR DIFFUSERS WITH 1-1/2" R=6.0 <br />BLANKET INSULATION. SECURE INSULATION TO DIFFUSER NECK <br />WITH STAINLESS STEEL DUCT CLAMPS. NYLON DRAWBANDS MAY BE <br />USED IN NON PLENUM CEILINGS. <br />7. PROVIDE RUSK I N " D I BD2" TYPE "B" FIRE DAMPERS (UL 555 <br />DYNAMIC RATING) WITH ACCESS DOORS WHERE INDICATED ON PLANS. <br />8. USE RADIUS RECTANGULAR FITTINGS OR TURNING VANES IN <br />ALL SUPPLY DUCT ELBOWS, CONICAL BRANCH TAKE -OFFS, SPLITTER <br />DAMPERS WHERE INDICATED ON DRAWINGS AND VOLUME CONTROL <br />EXTRACTORS IN ALL BRANCH DUCTS OR DIFFUSER CONNECTIONS. <br />USE YOUNG'S REGULATOR "YR 270-275" OR APPROVED EQUAL ON <br />BRANCH VOLUME DAMPER ABOVE NON ACCESSABLE CEILING. <br />9. WALL CAPS SHALL BE "GREENHECK: EHV-550D" WALL LOUVER <br />WITH A 18" PLENUM BOX BEHIND LOUVER, SLOPE BOTTOM OF PLENUM <br />TOWARDS LOUVER. WALL CAPS SHALL BE SIZED AS FOLLOWS: <br />a) 12X12 WALL CAP FOR 6" RND DUCT MAX. <br />b) 18X12 WALL CAP FOR 8" RND DUCT MAX, <br />c) 24X12 WALL CAP FOR 10" RND DUCT MAX. <br />10. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. <br />11. PLANS ARE DIAGRAMMATIC. IN GENERAL DUCT OFFSETS HAVE <br />NOT BEEN SHOWN. A/C CONTRACTOR SHALL COORDINATE THESE AS <br />REQUIRED WITH BUILDING STRUCTURE AND OTHER TRADES. <br />12. CONTRACTOR SHALL INSPECT AND MATCH EXISTING AIR <br />DISTRIBUTION DEVICES FOR STYLE, FIRE RATING, AND <br />PERFORMANCE PRIOR TO SUBMITTING OR ORDERING ANY MATERIALS. <br />DESIGN IS BASED ON THE FOLLOWING "TITUS" MODELS. REPORT <br />ANY DEFICIENCIES TO ARCHITECT AND ENGINEER. <br />a) CD CEILING DIFFUSER MODEL TDCA-AA, TYPE 1 BORDER, <br />ADJUSTABLE THROWS, WITH SQUARE OR ROUND NECK. PROVIDE 4- <br />WAY ADJUSTABLE AIR PATTERNS UNLESS OTHERWISE SHOWN ON <br />PLANS. <br />b) PD PERFORATED DIFFUSER PAS. <br />c) RAG PERFORATED AIR GRILLE PAR. <br />d) TG TRANSFER AIR GRILLE MODEL PAR. <br />SEAL: <br />CONSULTANT: <br />d M <br />SA <br />Z. <br />o . <br />(� <br />w <br />o <br />Mho <br />Z �r- <br />�J, <br />10 <br />IL <br />W <br />W DATE: t1713112© <br />�� PROJECT: <br />200271Yo037 <br />Z ° r. DRAWN: KG <br />ELIgW CHECKED: DWG <br />� W � <br />z� <br />Z M a;` <br />< W <br />V <br />M2 <br />oo <br />HVAC NOTES AND <br />\ I SCHEDULES <br />