Laserfiche WebLink
SECTION 16050 <br />SECTION 16050 <br />SECTION 16070 <br />2.04 WARNING SIGNS <br />V. <br />Use expansion fittings or flexible conduit, properly bonded, to ensure ground continuity across <br />expansion joints in floors and ceilings. <br />BASIC REQUIREMENTS FOR ELECTRICAL SYSTEMS <br />3.03 <br />DEMOLITION <br />HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS <br />A. <br />Provide warning signs called for by NFPA 70, NFPA 70E, OSHA, and the list included below. <br />W. <br />Terminate conduits for feeders and branch circuits directly into panelboard enclosures from which <br />PART 1 -GENERAL <br />A. <br />Visit the site to observe existing conditions before submitting a bid. <br />PART 1 - GENERAL <br />B. <br />Use Seton Name Plate Company products, 10" x 7" size, pressure -sensitive (PSPL) for indoor use, 30 ga. <br />they are served without the use of pull boxes, junction boxes, wire ways, or auxiliary gutters. If the <br />baked enamel for outdoor use (30 BE) with style numbers shown below. <br />panelboard enclosure does not provide sufficient surface area for all conduits, notify the Engineer <br />1.01 <br />SECTION INCLUDES <br />B. <br />Work in existing buildings shall be scheduled well in advance with the Owner's Representative. Work <br />1.01 <br />WORK INCLUDED <br />and request directions. <br />shall be performed at such times and under such conditions as suit the convenience of the Owner's <br />C. <br />Danger - Electrical Hazard - Authorized Personnel Only, Style No. 161. <br />A. <br />Basic materials and methods, along with Division 1, General Requirements, that are applicable to Division 16 <br />Representative. Plan the Work to minimize disruption of normal operations. Notify Owner's <br />A. <br />Comply with the provisions of Sections 16050. <br />1. Main electrical room(s), <br />X. <br />Failure to route conduit through building without interfering with other equipment and construction <br />sections. <br />Representative before any circuit is de -energized in occupied areas. <br />2. Electrical equipment closet(s). <br />shall not constitute a reason for an extra charge. Equipment, conduit, and fixtures shall fit into <br />B. <br />Provide a system of supporting devices and hangers for support or bracing of conduit, electrical <br />available spaces in building and shall not be introduced into building at such times and manner as to <br />B. <br />Drawings and general provisions of the contract, including General and Supplementary Conditions and <br />C. <br />Reconnect circuits to other panelboards when required to complete the renovation shown. <br />equipment, including safety switches, fixtures, panelboards, outlet boxes, junction boxes, and <br />PART 3 - EXECUTION <br />cause damage to structure. Equipment requiring servicing shall be readily accessible. <br />Division 1 specification Sections apply to all Division 16 sections. <br />cabinets. <br />D. <br />Remove abandoned wire and conduit back to source. Splice and terminate in junction boxes as <br />3.01 <br />INSTALLATION <br />Y. <br />Provide 1/4" nylon pull rope in all primary power and incoming telephone service entrance conduits. <br />1.02 <br />QUALITY ASSURANCE <br />appropriate. Where entire circuit is to be removed, remove conduit and wire back to existing <br />1.02 <br />RELATED WORK <br />panelboard. Where such work would not be possible without disturbing areas not being renovated, <br />A. <br />Identify the following electrical equipment as called for herein: <br />Z. <br />No PVC shall emerge from the ground, concrete slab, or concrete encasement. PVC shall convert to <br />A. <br />Comply with applicable local, state, and federal codes. <br />consult with the Architect prior to performing the work. <br />A. <br />Section 16110: Raceways and Conduit Systems <br />1. Panelboards. <br />galvanized rigid steel conduit at least 6 inches before exiting concrete slab or concrete encasement. <br />2. Safety switches and disconnects. <br />Schedule 80 PVC shall be used if shown on drawing. <br />B. <br />Turn over electrical equipment provided under this Division to the Owner in lubricated condition. Include <br />E. <br />Where a circuit is interrupted by removal of a device or fixture from that circuit, install wire and conduit <br />B. <br />Section 16131: Pull and Junction Boxes <br />3. Individually mounted circuit breakers. <br />instructions on further lubrication in the operating manual. <br />as required to restore service to the remaining devices and fixtures on that circuit. Ensure proper <br />4. Relays. <br />AA. <br />Where feeder or branch conduits enter pull boxes or junction boxes, clearly mark on conduit on the <br />grounding is maintained. <br />C. <br />Section 16130: Outlet Boxes <br />5. Shunt trip pushbuttons: <br />entering and leaving side of each box the panel name and circuit number(s) contained within the <br />C. <br />Upon completion of contract and progressively as work proceeds, clean-up and remove dirt, debris and scrap <br />a. CT -Scan disconnects. <br />conduit using a permanent black marker. <br />materials. Maintain premises neat and clean. Protect and preserve access to energized equipment at all <br />F. <br />Lighting fixtures, wiring devices, panelboards, equipment, conduits and conductors removed shall be <br />1.03 <br />SUBMITTALS <br />times. Clean items with factory finishes. Touch-up minor damage to surfaces; refinish entire piece of <br />transported to the Owner's designated location and offered to the OWNER. If he chooses to retain <br />End of Section <br />3.02 <br />FLEXIBLE METAL CONDUIT <br />equipment when sustained major damage. Use only factory supplied paints of matching color and formula. <br />these items or a part of these items, turn those chosen over to him. Items rejected by the OWNER shall <br />A. <br />Submittals are not required. <br />Schedule an off -hour shutdown of all electrical equipment during the 2-week period preceding substantial <br />be removed completely from the project site and disposed of legally by the CONTRACTOR. <br />SECTION 16110 <br />A. <br />Conduits shall be 3/8" minimum size for lighting fixtures and 1/2" minimum size for utilization <br />completion. During this shut down, clean all buses and insulators inside all switchgear, switchboards, bus <br />PART 2 - PRODUCTS <br />equipment other than lighting fixtures. <br />ducts, collector buses and panelboards located inside or adjacent to the project limits. <br />3.04 <br />CUTTING AND PATCHING <br />RACEWAYS AND CONDUIT SYSTEMS <br />2.01 <br />ACCEPTABLE MANUFACTURERS <br />B. <br />Fittings shall be made of either steel, or malleable iron only. <br />1.03 <br />REGULATORY REQUIREMENTS <br />A. <br />Comply with provisions of Division 1 <br />PART 1 -GENERAL <br />A. <br />Erico Products, Inc <br />C. <br />A copper ground wire shall be installed as a jumper around flexible conduit. The jumper may be <br />A. <br />Perform Work specified in Division 16 in accordance with standards listed below of the latest applicable <br />B. <br />Repair or replace routine damage caused by cutting in performance of Work under this Division. <br />1.01 <br />WORK INCLUDED <br />installed inside of flexible conduit or outside of conduit to ensure continuity of ground. <br />edition adopted by the authority having jurisdiction. Where these Specifications are more stringent, they shall <br />B. <br />Steel City <br />take precedence. In case of conflict, obtain a decision from the Architect,. <br />C. <br />Correct unnecessary damage caused due to installation of electrical Work, brought about through <br />A. <br />Comply with the provisions of Sections 16050. <br />D. <br />Recessed lighting fixtures shall be connected with flexible metallic conduit from outlet box to fixture. <br />1. Refer to cover sheet for code references <br />carelessness or lack of coordination. <br />C. <br />Minerallac <br />B. <br />Provide a complete conduit system with associated couplings, connectors, and fittings. <br />E. <br />Install liquid tight flexible conduit in such a manner as to prevent liquids from running on the surface <br />1.04 <br />RELATED WORK SPECIFIED UNDER OTHER DIVISIONS <br />D. <br />Holes cut through floor slabs shall be core drilled with drill designed for this purpose. All openings, <br />D. <br />Rayco Fasteners <br />toward fittings. <br />sleeves, and holes in slabs between floors shall be properly sealed, fire proofed and water proofed. <br />1.02 <br />RELATED WORK <br />A. <br />Field painting, except such painting as is required to maintain shop coat painting and factory finish painting <br />2.02 <br />TYPES OF SUPPORTING DEVICES <br />F. <br />Allow sufficient slack conduit to reduce the effect of vibration. <br />E. <br />Holes cut through walls shall be drilled or cut with tools designed for the purpose. Al[ openings, <br />A. <br />Section 16070: Hangers and Supports for Electrical Systems <br />B. <br />Flashing of conduits into roofing and outside walls <br />sleeves and holes in walls that extend to underside of floor above shall be properly sealed and fire <br />A. <br />Unless otherwise directed in Specifications or Drawings, provide appropriate supporting devices and <br />proofed. <br />hangers for electrical equipment from this list of Caddy fasteners: <br />1.03 <br />SUBMITTALS <br />End of Section <br />C. <br />Fireproofing <br />1. "Z" purlin clips - 1-1/4" maximum conduit <br />F. <br />Repairs shall be performed with materials which match existing materials and be installed in <br />2. Conduit clips - 2" maximum conduit <br />A. <br />Submittal of products furnished under this Section are not required. <br />SECTION 16121 <br />D. <br />Cutting and patching for electrical Work, except for errors and omissions under this Division. <br />accordance with appropriate sections of these Specifications. <br />3. Beam clamps (rod hanger clamps and vertical flange damps) for support of threaded rods <br />4. Beam clamps (set screw type) - 2" maximum conduit <br />PART 2 - PRODUCTS <br />LOW VOLTAGE ELECTRICAL POWER CONDUCTORS <br />1.05 <br />RELATED WORK - OWNER FURNISHED EQUIPMENT AND SYSTEMS <br />G. <br />Contractor shall not be permitted to cut or modify any structural members without the written <br />5. Beam clamps (universal) for support of boxes and combination conduit hanger clamps <br />permission of the Architect. <br />6. Combination push -in conduit clips - 1" maximum conduit <br />2.01 <br />ACCEPTABLE MANUFACTURERS <br />PART 1 -GENERAL <br />A. <br />Radiology equipment <br />7. Combination conduit hanger clamps - 2" maximum conduit <br />3.05 <br />INFECTION CONTROL REQUIREMENTS <br />8. Flexible conduit clips - 1" maximum flexible conduit <br />A. <br />EMT and IMC shall be steel (ferrous) with a protective coating, and RMC conduit shall be steel (ferrous) <br />1.01 <br />WORK INCLUDED <br />B. <br />Nurses call system equipment <br />9. Special combination conduit dips - 1" maximum conduit <br />with a protective coating or aluminum (nonferrous) by Allied, General Electric, Republic, Triangle, or <br />A. <br />Coordinate with the Owner the exact requirements for the infection control measures to be executed <br />10. One hole steel straps <br />Wheatland. Special use may be red brass or stainless steel. <br />A. <br />Comply with the provisions of Sections 16050. <br />1.06 <br />OWNER FURNISHED INFORMATION <br />and performed during the course of this Project. <br />11. Conduit hangers - 4" maximum conduit <br />12. Combination box/conduit hangers for supporting conduit within T-0" of a box are not acceptable <br />B. <br />Surface metal raceways shall be Wiremold. <br />B. <br />Provide a complete system of conductors for lighting, power, and systems throughout the project. <br />A. <br />To the extent the Owner has performed and made available as Owner Furnished Information an Infection <br />B. <br />r present o h Owner for royal a written execution Ian for each infection control <br />Piro to execution, p s t t the pp p <br />Control Risk Assessment (ICRA), the Contractor shall execute all requirements of the Contract Documents in <br />measure. <br />PART 3 - EXECUTION <br />C. <br />EMT, IMC, or RSC couplings, connectors, and fittings shall be steel as manufactured by Raco or equivalent. <br />1.02 <br />RELATED WORK <br />accordance with the ICRA, and shall perform and provide all labor, materials and supervision to execute the <br />specific infection control measures identified therein. <br />C. <br />re needed with all other trades and disciplines. <br />Coordinate infection control measures as de p <br />3.01 <br />INSTALLATION REQUIREMENTS <br />D. <br />RAC couplings, connectors, and fittings shall be aluminum. <br />A. <br />Section 16050: Basic Requirements for Electrical Systems <br />B. <br />The Contract Documents do not necessarily depict all the work required by the ICRA, nor are the Contract <br />D. <br />Provide documentation of infection control measures to the Owner, as required and specified in the <br />A. <br />Secure conduits to within 3 feet of each outlet box, junction box, cabinet and fitting and at intervals not <br />E. <br />Erickson couplings shall be used where neither length of conduit can be rotated. <br />B. <br />Section 16110: Raceways and Boxes for Electrical Systems <br />Documents responsible for the information contained in the ICRA. The Contractor shall request, and obtain if <br />ICRA. <br />to exceed ten feet in accordance with current edition of the National Electrical Code. <br />available, the Owner's ICRA documentation, become familiar with its requirements and perform all work <br />F. <br />EMT box connectors and couplings shall be set screw type. <br />1.03 <br />REFERENCES <br />accordingly. <br />3.06 <br />TESTING ELECTRICAL SYSTEMS <br />B. <br />Install clamps secured to structure for feeder and other conduits routed against the structure. Use drop <br />rods and hangers to support conduits run apart from the structure. <br />9 PP P <br />G. <br />Conduit, connectors, couplings and fittings shall be UL listed and labeled. <br />A. <br />- - <br />NEMA WC 3 Rubber Insulated Wire and Cable for the Transmission and Distribution of Electrical <br />1.07 <br />SUBMITTALS <br />A. <br />On completion of work, installation shall be completely operational and entirely free from grounds, <br />Energy <br />short circuits, and open circuits. Perform operational tests as required to demonstrate substantial <br />C. <br />Provide and install suitable angle iron, channel iron or steel metal framing with accessories to support <br />2.02 <br />ELECTRICAL METALLIC TUBING (EMT) <br />A. <br />Comply with provisions of Division 1. <br />completion of the Work. Balance circuits so that feeders to panels are not more than 10% out of <br />or brace electrical equipment including safety switches, fixtures and panelboards. <br />B. <br />NEMA WC 5 - Thermoplastic -Insulated Wire and Cable for the Transmission and Distribution of <br />balance between phases with all available load energized and operating. Furnish all labor, materials <br />A. <br />Use Electric Metallic Tubing (EMT) where shown on drawings or for: <br />Electrical Energy <br />1.08 <br />OPERATING AND MAINTENANCE MANUALS <br />and instruments for above tests. All ampere readings shall be made with a true RMS reading meter. <br />D. <br />Paint all supporting metal not otherwise protected, with rust inhibiting primer and then with a finish <br />1. Concealed in walls <br />coat if appropriate to match the surrounding metal surfaces. (Prepainted or galvanized support <br />2. Installed above suspended ceilings <br />C. <br />ANSI/UL 83 - Thermoplastic -Insulated Wire and Cables <br />A. <br />Provide manuals in accordance with Division 1. <br />B. <br />Perform megger tests of all service entrance circuits, feeder and branch circuits size #4 AWG and <br />material is not required to be painted or repainted.) <br />3. Installed exposed, above 6 feet <br />larger. Provide a report of all such megger test results. <br />D. <br />NFPA 70 - National Electrical Code, latest edition <br />B. <br />In addition to required submittals, include copies of all test reports required in Part 3, "Execution" of section <br />E. <br />Use of chains, perforated iron strap, baling wire, or tie wire for supporting conduit runs will not be <br />2.03 <br />RIGID STEEL CONDUIT (RSC) <br />16050. <br />C. <br />Furnish the Architect a copy of test reports and required certification including but not limited to the <br />permitted. <br />1.04 <br />SUBMITTALS <br />following: <br />A. <br />Use rigid steel conduit where shown an drawings or for: <br />C. <br />Provide completed warranty certificates for systems and equipment. <br />1. Switchboard and panelboard load test - include ampere readings of all panels and major circuit <br />F. <br />Use of Caddy clips to support conduit to top of t-bar ceiling grid will not be permitted. <br />1. Installed underground <br />A. <br />Submit the data sheets for products furnished under this Section. <br />breakers <br />2. Above ground service entrance <br />1.09 <br />DELIVERY AND STORAGE <br />2. Patient Care Area Grounding System Test <br />G. <br />For support of low voltage wiring not required to be in conduit, Contractor shall bundle cables together <br />3. Medium voltage circuits <br />1.05 <br />DELIVERY, STORAGE AND HANDLING <br />3. Megger test results <br />in a neat manner using approved nylon cable ties. Bundled cables shall be supported with "J" hooks <br />4. For emergency feeders and critical branch circuits <br />A. <br />Insofar as possible, deliver items in manufacturer's original unopened packaging. Where this is not practical, <br />4. Power System Analysis Report <br />on telephone type bridle rings, a minimum of six feet on centers. <br />5. Where protection from EMI is required <br />A. <br />Provide factory -wrapped waterproof flexible barrier material for covering wire and cable wood reels, <br />cover items with protective materials to keep them from being damaged. Use care in loading, transporting, <br />1. Maximum supported weight rating of "J" hooks shall not be exceeded. <br />6. Exposed to severe mechanical damage <br />where applicable, and weather resistant fiberboard containers for factory packaging of cable, wire <br />unloading, and storage to keep items from being damaged. <br />D. <br />Prior to final observation and acceptance test, install all electrical systems and equipment complete <br />2. Identification tape shall be provided at minimum intervals of 25 feet on center and within each <br />and connectors, to protect against physical damage in transit. Damaged cable, wire or connectors <br />and in satisfactory operating condition. <br />individual space. <br />2.04 <br />RIGID ALUMINUM CONDUIT (RAC) <br />shall be removed from project site. <br />B. <br />Store items in a clean dry place and protect from damage. Evidence of damage from water or other <br />contaminants will be cause for rejection. <br />End of Section <br />A. <br />Use rigid aluminum conduit, RAC, where shown on the drawings or for: <br />B. <br />In their factory -furnished coverings, store cable, wire and connectors in a clean, dry indoor space, <br />End of Section <br />1. In coastal areas where saltwater vapor is present <br />which provides protection against the weather. <br />1.10 <br />RECORD DRAWINGS <br />SECTION 16060 <br />2. As a substitute for rigid steel conduit when approved by engineer <br />SECTION 16075 <br />PART 2 - PRODUCTS <br />A. <br />Comply with provisions of Division 1. <br />GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS <br />PART 3 - EXECUTION <br />IDENTIFICATION FOR ELECTRICAL SYSTEMS <br />2.01 <br />ACCEPTABLE MANUFACTURERS <br />PART <br />2 - PRODUCTS <br />PART 1 - GENERAL <br />3.01 <br />INSTALLATION REQUIREMENTS <br />PART 1 - GENERAL <br />A. <br />American Insulated Wire <br />2.01 <br />MATERIALS AND EQUIPMENT <br />1.01 <br />WORK INCLUDED <br />A. <br />Minimum size of conduits shall be 3/4" <br />1.01 <br />WORK INCLUDED <br />B. <br />United Copper <br />A. <br />Equipment and materials furnished shall be listed by UL or other nationally accredited testing laboratory <br />A. <br />Comply with the provisions of Section 16050. <br />B. <br />Conduit joints shall be cut square, threaded, reamed smooth, and drawn up tight so conduit ends will butt in <br />where available. When listing is not available for a piece of equipment, it shall be submitted in accordance <br />A. <br />Requirements for identification of electrical equipment, circuit identification, system color coding and <br />couplings, connectors and fittings. <br />C. <br />Encore <br />with Drawings and Specifications and shall be approved by the authorities having jurisdiction. <br />B. <br />The entire system of raceways and equipment shall be grounded in accordance with Articles 250 and <br />warning signs. <br />517 of the National Electrical Code and any local regulation or governing authority. <br />C. <br />Make bends or offsets with standard factory bends or field bends with an approved bender. Use of heat and <br />D. <br />Pyrotenax (Mineral Insulated applications) <br />B. <br />Specifications and Drawings indicate name, type and/or catalog number of materials and equipment to <br />1.02 <br />RELATED WORK <br />other non -approved methods will not be accepted. An approved factory built and UL tested PVC bender <br />establish standards of quality. Submittals shall be based on the standards specified. The standards should <br />1.02 <br />SUBMITTALS <br />using heat is acceptable. <br />E. <br />Republic Wire <br />not be construed as limiting competition. <br />A. <br />Section 16050: Common Work Results for Electrical <br />A. <br />Submittals are not required for products in this Section. <br />D. <br />Medium voltage conduits shall use long radius bends and fittings with a minimum radius of at least 12 times <br />F. <br />Southwire <br />PART <br />3 - EXECUTION <br />1.03 <br />SUBMITTALS <br />the diameter of the installed cables. <br />PART 2 - PRODUCTS <br />G. <br />Superior Essex <br />3.01 <br />COORDINATION <br />A. <br />Submittal of product furnished under this section is not required. <br />E. <br />Run concealed conduits in direct line with long radius bends or offsets. Run exposed conduits parallel to <br />2.01 <br />REQUIREMENTS <br />and at right angles to building lines. Group multiple conduit runs in banks and maintain proper separation to <br />H. <br />Cerrowire <br />A. <br />Install equipment in accordance with manufacturer's recommendations. Where conflicts occur between <br />PART <br />2 - PRODUCTS <br />prevent any derating of cable. <br />Contract Documents and these recommendations, request a ruling before proceeding with such Work. <br />A. <br />Ground clamps: OZ-Gedney, Type "CG", or equal by Steel City or Appleton. <br />I. <br />Okonite <br />2.01 <br />IDENTIFICATION OF EQUIPMENT <br />F. <br />Conduit systems shall be electrically and mechanically continuous. <br />B. <br />Visit site and observe conditions under which work must be performed. No subsequent allowance will be <br />PART 3 - EXECUTION <br />J. <br />General Cable <br />made because of error or failure to obtain necessary information to completely estimate and perform work <br />A. <br />Identify electrical equipment with permanently attached phenolic plates with 1/4" white or black <br />G. <br />For interior locations where NEMA 1 enclosures are used, secure conduits to boxes and cabinets with <br />required by these documents. <br />3.01 <br />INSTALLATION REQUIREMENTS <br />engraved lettering on the face of each, attached with two sheet metal screws. Provide nameplate <br />double locknuts and bushing. <br />2.02 <br />CONDUCTORS <br />colors as specified in other parts of this section. <br />C. <br />Examine Specifications and Drawings to be familiar with items which require electrical connections and <br />A. <br />General <br />H. <br />For interior locations where NEMA 12 enclosures are used, secure conduits to boxes and cabinets with <br />A. <br />Provide 98% conductivity copper conductors with 600V insulation. <br />coordination. Electrical Drawings are diagrammatic and shall not be scaled for exact sizes. <br />1. Refer to National Electrical Code Article 517 and the drawings for grounding requirements. <br />B. <br />Include the following information on panelboard identification plates: <br />sealing locknuts and bushing. <br />2. Clean all conductive surfaces on equipment to be grounded, to ensure good electrical continuity. <br />1. Panel Name <br />B. <br />For conductors No. 12 AWG and No. 10 AWG, provide stranded type THWN or THHN. <br />D. <br />Prior to commencement of installation, prepare coordination drawings for work under this division, as <br />3. Effectively bond all grounding conductors to grounding electrodes, equipment enclosures and <br />2. Name of panel serving it <br />I. <br />For damp or wet locations, indoor or outdoor locations where NEMA 4 or 4X enclosures are used, secure <br />specified in Division 1 and as called for herein. Coordinate work under other divisions, including but not <br />ground buses. <br />3. Voltage and Phase <br />conduits to boxes and cabinets with Myers Scru-Tite hub. <br />C. <br />For conductors No. 14 AWG and smaller, provide solid type THHN. <br />limited to mechanical, plumbing, fire protection, telecommunication and miscellaneous steel to develop these <br />4. Locate all grounding attachments away from areas subject to physical damage. Provide <br />4. On service equipment, legibly mark in the field the maximum available fault current and the date <br />coordination drawings that will serve as the agreed upon plan for a coordinated installation of work for all <br />protective covering as required. <br />that the fault current calculation was performed per NEC 120.24, 2011. <br />J. <br />Provide grounding bushings on all feeder conduits in critical care areas in accordance with NEC Article 517. <br />D. <br />For conductors No. 8 AWG and larger, provide stranded type THHN, or THWN applied consistently <br />trades. Include electrical equipment, switchgear, panelboards, starters, disconnect switches, cable tray, <br />with insulation ratings and NEC requirements. <br />conduit racks and conduits 3" and larger on drawings confirming coordination with other trades. Incorporate <br />B. <br />Feeder/Branch Circuits: <br />2.02 <br />CIRCUIT IDENTIFICATION <br />K. <br />Cap ends of conduits to prevent entrance of water and other foreign material during construction. <br />the information onto the coordination drawings required under Division 1 and 15 to develop master <br />1. Provide a separate green grounding conductor in the conduit of feeder circuits for the following <br />E. <br />Provide white or gray colored neutral conductors; provide color coded phase conductors. <br />coordination drawings. Account for lighting fixture depths in the coordination. Inform Design Professional of <br />equipment, sized in accordance with Table 250.122 of the National Electrical Code: <br />A. <br />Identify feeder j-boxes and pull boxes with designation of panelboard/switchboard source as "FROM" <br />L. <br />Complete conduit systems before pulling conductors. <br />conflicts that cannot be resolved. <br />a. Panelboards <br />and load served as "TO" with permanent labels. <br />F. <br />Minimum conductor size shall be: <br />2. Install a separate green grounding conductor in same conduit as phase and neutral conductor <br />M. <br />Support conduits as specified in Section 16070 and in accordance with National Electrical Code. <br />1. #12 for power wiring <br />E. <br />Do NOT submit coordination drawings to Architect for review. Keep a copy on site for reference purposes. <br />from panel ground bus to device for branch circuits. Install an equal number of grounding and <br />B. <br />Identify pull and junction boxes with the designation of panelboard and the circuit number of each <br />2. #14 for hard wired controls unless otherwise specified <br />Notify Architect of conflicts that cannot be resolved. <br />neutral conductors. Size the grounding conductor in accordance with Table 250.122 of the <br />circuit contained therein, with permanent marker. Clearly mark information on or in the box, not on the <br />N. <br />Provide cable supports in conduits rising vertically in accordance with the National Electrical Code, Article <br />National Electrical Code. <br />cover, so that the information is easily identifiable. <br />300. <br />3.02 <br />FEES AND PERMITS <br />3. Bond the receptacle ground pin to its box using a bonding jumper, except where isolated ground <br />receptacles are required. <br />C. <br />Identify circuits in conduits entering outlet boxes with the designation of panelboard and the circuit <br />O. <br />Provide insulated bushing on both ends of empty conduits. <br />A. <br />Obtain and pay for all necessary permits and inspection fees required for electrical installation. <br />4. Flexible conduit will not be approved as a grounding means. Flexible conduit shall have a jumper <br />number of each circuit contained therein, with permanent marker. <br />wire sized to ampacity of branch breaker and connected to conduit system on both ends. This <br />Conduits which pass through floor slabs (except ground floor) shall be sealed with UL listed fire -stopping <br />3.03 <br />DEMOLITION <br />applies to fixtures, motors, controls and other devices. <br />2.03 <br />COLOR CODE IDENTIFICATION <br />materials. Seal around conduits or other wiring materials passing through partitions, which extend to the <br />underside of the slab above, and those passing through smoke partitions and fire rated walls. Use U.L. <br />A. <br />Visit the site to observe existing conditions before submitting a bid. <br />A. <br />Color code phenolic plates utilized to identify electrical equipment according to which branch of the <br />listed materials to prevent passage of smoke or fire. See Division 7 for specific materials required.Conduits <br />End of Section <br />electrical system the equipment is connected to as follows: <br />which enter crawl spaces, tunnels, and basements from outside the building shall be grouted -in to prevent <br />B. <br />Work in existing buildings shall be scheduled well in advance with the Owner's Representative. Work shall <br />1. Normal - Black with white letters. <br />entry of gases, vapors, insects or rodents to these spaces from street mains. <br />be performed at such times and under such conditions as suit the convenience of the Owner's <br />Representative. Plan the Work to minimize disruption of normal operations. Notify Owner's Representative <br />B. <br />If existing equipment identification nameplates are a different color, request a ruling from the design <br />P. <br />When four or more, 2 inch or larger conduits, are banked together below the ground floor slab they shall be <br />before any circuit is de -energized in occupied areas. <br />professional to determine what color scheme to follow. <br />supported and separated using Carton, Snap-Loc type spacers. Backfill below, between, and above ducts in <br />such a manner to prevent erosion and restore sub -grade preparation prior to concrete slab pour. <br />C. <br />Reconnect circuits to other panelboards when required to complete the renovation shown. <br />C. <br />Spot paint conduits every 10 to 15 feet and at least once above every room utilizing the color code <br />above. <br />Q. <br />Where IMC or RMC conduit is connected to a panelboard, switchboard, cabinet, junction box, pull box or <br />D. <br />Remove abandoned wire and conduit back to source. Splice and terminate in junction boxes as appropriate. <br />auxiliary gutter, conductors shall be protected by insulated bushings. Locknuts shall be installed on conduit <br />Where entire circuit is to be removed, remove conduit and wire back to existing panelboard. Where such <br />D. <br />The color code as outlined below shall be used. In addition, on each panelboard, pull box, control <br />outside and inside enclosure. <br />work would not be possible without disturbing areas not being renovated, consult with the Architect prior to <br />cabinet, or other electrical enclosure that contains circuits from more than one system, provide an <br />performing the work. <br />engraved phenolic plate and indentify the circuit conductors with the following color code:208Y/120, <br />R. <br />Where conduits stub up in conduit space beneath switchboards or switchgear and do not connect directly to <br />Phase A, black, Phase B, red, Phase C, blue, grounded conductor, white, equipment grounding <br />equipment enclosures, install malleable iron nylon insulated ground bushing complete with bonding <br />E. <br />Where a circuit is interrupted by removal of a device or fixture from that circuit, install wire and conduit as <br />conductor, green, isolated equipment grounding conductor, green/yellow stripe. 480Y/277, Phase A, <br />connection and bond to switchboard ground bus. <br />required to restore service to the remaining devices and fixtures on that circuit. Ensure proper grounding is <br />brown, Phase B, orange, Phase C, yellow, grounded conductor, gray, equipment grounding conductor, <br />maintained. <br />green, isolated equipment grounding conductor, green/red stripe. <br />S. <br />Install seal -off fittings in conduits entering hazardous areas and conduits entering cold temperature areas, <br />such as freezers and refrigerators. <br />F. <br />Lighting fixtures, wiring devices, panelboards, equipment, conduits and conductors removed shall be <br />transported to the Owner's designated location and offered to the OWNER. If he chooses to retain these <br />T. <br />Use expansion fittings or flexible conduit, property bonded, to ensure ground continuity across expansion <br />items or a part of these items, turn those chosen over to him. Items rejected by the OWNER shall be <br />joints in floors and ceilings. <br />removed completely from the project site and disposed of legally by the CONTRACTOR. <br />U. <br />Terminate conduits for feeders and branch circuits directly into panelboard enclosures from which they are <br />served without the use of pull boxes, junction boxes, wire ways, or auxiliary gutters. If the panelboard <br />enclosure does not provide sufficient surface area for all conduits, notify the Engineer and request <br />directions. <br />AA 26001479 <br />Sheet Notes: <br />Smith <br />W"kSeckman <br />Reid,lnc. <br />301 North Cattlemen Road, Suite 300 <br />Sarasota, FL 34232 <br />(941) 907-7750 <br />FAX: (941) 907-7751 <br />www.ssr-inc.com <br />Firm Certification - CA-0000857 <br />SSR# 166044.0 <br />Erick Phelps - PE #64598 <br />Christopher E. Durham - PE #76655 <br />``` %J 1111111/111 <br />QQ�FR EDWgRO <br />01NSF• •.'py i <br />No. 76655 <br />STATE OF <br />/,//0NA„o <br />Christopher Edward Durham <br />PE License No. 76655 <br />FI i"_N miff k, 1 -0,1% M <br />LVJ K I DA C"A N (-. E K <br />E C I A L I S T <br />Research Institute <br />Key Plan <br />MARK ISSUE DATE DESCRIPTION <br />Issue Log <br />CONSTRUCTION <br />DOCUMENTS <br />FLORIDA CANCER SPECIALISTS <br />EQUIPMENT REPLACEMENT <br />38010 MEDICAL CENTER AVE. <br />ZEPHYRHILLS, FL 33540 <br />Drawing Title <br />ELECTRICAL <br />SPECIFICATIONS <br />VARTILI <br />06/29/2016 <br />Scale <br />Sheet Number <br />E-002 <br />Drawn By KDS <br />Approved By MLG <br />Filename <br />Sc atCo, LLC 2007 <br />