SECTION 16050
<br />SECTION 16050
<br />SECTION 16070
<br />2.04 WARNING SIGNS
<br />V.
<br />Use expansion fittings or flexible conduit, properly bonded, to ensure ground continuity across
<br />expansion joints in floors and ceilings.
<br />BASIC REQUIREMENTS FOR ELECTRICAL SYSTEMS
<br />3.03
<br />DEMOLITION
<br />HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
<br />A.
<br />Provide warning signs called for by NFPA 70, NFPA 70E, OSHA, and the list included below.
<br />W.
<br />Terminate conduits for feeders and branch circuits directly into panelboard enclosures from which
<br />PART 1 -GENERAL
<br />A.
<br />Visit the site to observe existing conditions before submitting a bid.
<br />PART 1 - GENERAL
<br />B.
<br />Use Seton Name Plate Company products, 10" x 7" size, pressure -sensitive (PSPL) for indoor use, 30 ga.
<br />they are served without the use of pull boxes, junction boxes, wire ways, or auxiliary gutters. If the
<br />baked enamel for outdoor use (30 BE) with style numbers shown below.
<br />panelboard enclosure does not provide sufficient surface area for all conduits, notify the Engineer
<br />1.01
<br />SECTION INCLUDES
<br />B.
<br />Work in existing buildings shall be scheduled well in advance with the Owner's Representative. Work
<br />1.01
<br />WORK INCLUDED
<br />and request directions.
<br />shall be performed at such times and under such conditions as suit the convenience of the Owner's
<br />C.
<br />Danger - Electrical Hazard - Authorized Personnel Only, Style No. 161.
<br />A.
<br />Basic materials and methods, along with Division 1, General Requirements, that are applicable to Division 16
<br />Representative. Plan the Work to minimize disruption of normal operations. Notify Owner's
<br />A.
<br />Comply with the provisions of Sections 16050.
<br />1. Main electrical room(s),
<br />X.
<br />Failure to route conduit through building without interfering with other equipment and construction
<br />sections.
<br />Representative before any circuit is de -energized in occupied areas.
<br />2. Electrical equipment closet(s).
<br />shall not constitute a reason for an extra charge. Equipment, conduit, and fixtures shall fit into
<br />B.
<br />Provide a system of supporting devices and hangers for support or bracing of conduit, electrical
<br />available spaces in building and shall not be introduced into building at such times and manner as to
<br />B.
<br />Drawings and general provisions of the contract, including General and Supplementary Conditions and
<br />C.
<br />Reconnect circuits to other panelboards when required to complete the renovation shown.
<br />equipment, including safety switches, fixtures, panelboards, outlet boxes, junction boxes, and
<br />PART 3 - EXECUTION
<br />cause damage to structure. Equipment requiring servicing shall be readily accessible.
<br />Division 1 specification Sections apply to all Division 16 sections.
<br />cabinets.
<br />D.
<br />Remove abandoned wire and conduit back to source. Splice and terminate in junction boxes as
<br />3.01
<br />INSTALLATION
<br />Y.
<br />Provide 1/4" nylon pull rope in all primary power and incoming telephone service entrance conduits.
<br />1.02
<br />QUALITY ASSURANCE
<br />appropriate. Where entire circuit is to be removed, remove conduit and wire back to existing
<br />1.02
<br />RELATED WORK
<br />panelboard. Where such work would not be possible without disturbing areas not being renovated,
<br />A.
<br />Identify the following electrical equipment as called for herein:
<br />Z.
<br />No PVC shall emerge from the ground, concrete slab, or concrete encasement. PVC shall convert to
<br />A.
<br />Comply with applicable local, state, and federal codes.
<br />consult with the Architect prior to performing the work.
<br />A.
<br />Section 16110: Raceways and Conduit Systems
<br />1. Panelboards.
<br />galvanized rigid steel conduit at least 6 inches before exiting concrete slab or concrete encasement.
<br />2. Safety switches and disconnects.
<br />Schedule 80 PVC shall be used if shown on drawing.
<br />B.
<br />Turn over electrical equipment provided under this Division to the Owner in lubricated condition. Include
<br />E.
<br />Where a circuit is interrupted by removal of a device or fixture from that circuit, install wire and conduit
<br />B.
<br />Section 16131: Pull and Junction Boxes
<br />3. Individually mounted circuit breakers.
<br />instructions on further lubrication in the operating manual.
<br />as required to restore service to the remaining devices and fixtures on that circuit. Ensure proper
<br />4. Relays.
<br />AA.
<br />Where feeder or branch conduits enter pull boxes or junction boxes, clearly mark on conduit on the
<br />grounding is maintained.
<br />C.
<br />Section 16130: Outlet Boxes
<br />5. Shunt trip pushbuttons:
<br />entering and leaving side of each box the panel name and circuit number(s) contained within the
<br />C.
<br />Upon completion of contract and progressively as work proceeds, clean-up and remove dirt, debris and scrap
<br />a. CT -Scan disconnects.
<br />conduit using a permanent black marker.
<br />materials. Maintain premises neat and clean. Protect and preserve access to energized equipment at all
<br />F.
<br />Lighting fixtures, wiring devices, panelboards, equipment, conduits and conductors removed shall be
<br />1.03
<br />SUBMITTALS
<br />times. Clean items with factory finishes. Touch-up minor damage to surfaces; refinish entire piece of
<br />transported to the Owner's designated location and offered to the OWNER. If he chooses to retain
<br />End of Section
<br />3.02
<br />FLEXIBLE METAL CONDUIT
<br />equipment when sustained major damage. Use only factory supplied paints of matching color and formula.
<br />these items or a part of these items, turn those chosen over to him. Items rejected by the OWNER shall
<br />A.
<br />Submittals are not required.
<br />Schedule an off -hour shutdown of all electrical equipment during the 2-week period preceding substantial
<br />be removed completely from the project site and disposed of legally by the CONTRACTOR.
<br />SECTION 16110
<br />A.
<br />Conduits shall be 3/8" minimum size for lighting fixtures and 1/2" minimum size for utilization
<br />completion. During this shut down, clean all buses and insulators inside all switchgear, switchboards, bus
<br />PART 2 - PRODUCTS
<br />equipment other than lighting fixtures.
<br />ducts, collector buses and panelboards located inside or adjacent to the project limits.
<br />3.04
<br />CUTTING AND PATCHING
<br />RACEWAYS AND CONDUIT SYSTEMS
<br />2.01
<br />ACCEPTABLE MANUFACTURERS
<br />B.
<br />Fittings shall be made of either steel, or malleable iron only.
<br />1.03
<br />REGULATORY REQUIREMENTS
<br />A.
<br />Comply with provisions of Division 1
<br />PART 1 -GENERAL
<br />A.
<br />Erico Products, Inc
<br />C.
<br />A copper ground wire shall be installed as a jumper around flexible conduit. The jumper may be
<br />A.
<br />Perform Work specified in Division 16 in accordance with standards listed below of the latest applicable
<br />B.
<br />Repair or replace routine damage caused by cutting in performance of Work under this Division.
<br />1.01
<br />WORK INCLUDED
<br />installed inside of flexible conduit or outside of conduit to ensure continuity of ground.
<br />edition adopted by the authority having jurisdiction. Where these Specifications are more stringent, they shall
<br />B.
<br />Steel City
<br />take precedence. In case of conflict, obtain a decision from the Architect,.
<br />C.
<br />Correct unnecessary damage caused due to installation of electrical Work, brought about through
<br />A.
<br />Comply with the provisions of Sections 16050.
<br />D.
<br />Recessed lighting fixtures shall be connected with flexible metallic conduit from outlet box to fixture.
<br />1. Refer to cover sheet for code references
<br />carelessness or lack of coordination.
<br />C.
<br />Minerallac
<br />B.
<br />Provide a complete conduit system with associated couplings, connectors, and fittings.
<br />E.
<br />Install liquid tight flexible conduit in such a manner as to prevent liquids from running on the surface
<br />1.04
<br />RELATED WORK SPECIFIED UNDER OTHER DIVISIONS
<br />D.
<br />Holes cut through floor slabs shall be core drilled with drill designed for this purpose. All openings,
<br />D.
<br />Rayco Fasteners
<br />toward fittings.
<br />sleeves, and holes in slabs between floors shall be properly sealed, fire proofed and water proofed.
<br />1.02
<br />RELATED WORK
<br />A.
<br />Field painting, except such painting as is required to maintain shop coat painting and factory finish painting
<br />2.02
<br />TYPES OF SUPPORTING DEVICES
<br />F.
<br />Allow sufficient slack conduit to reduce the effect of vibration.
<br />E.
<br />Holes cut through walls shall be drilled or cut with tools designed for the purpose. Al[ openings,
<br />A.
<br />Section 16070: Hangers and Supports for Electrical Systems
<br />B.
<br />Flashing of conduits into roofing and outside walls
<br />sleeves and holes in walls that extend to underside of floor above shall be properly sealed and fire
<br />A.
<br />Unless otherwise directed in Specifications or Drawings, provide appropriate supporting devices and
<br />proofed.
<br />hangers for electrical equipment from this list of Caddy fasteners:
<br />1.03
<br />SUBMITTALS
<br />End of Section
<br />C.
<br />Fireproofing
<br />1. "Z" purlin clips - 1-1/4" maximum conduit
<br />F.
<br />Repairs shall be performed with materials which match existing materials and be installed in
<br />2. Conduit clips - 2" maximum conduit
<br />A.
<br />Submittal of products furnished under this Section are not required.
<br />SECTION 16121
<br />D.
<br />Cutting and patching for electrical Work, except for errors and omissions under this Division.
<br />accordance with appropriate sections of these Specifications.
<br />3. Beam clamps (rod hanger clamps and vertical flange damps) for support of threaded rods
<br />4. Beam clamps (set screw type) - 2" maximum conduit
<br />PART 2 - PRODUCTS
<br />LOW VOLTAGE ELECTRICAL POWER CONDUCTORS
<br />1.05
<br />RELATED WORK - OWNER FURNISHED EQUIPMENT AND SYSTEMS
<br />G.
<br />Contractor shall not be permitted to cut or modify any structural members without the written
<br />5. Beam clamps (universal) for support of boxes and combination conduit hanger clamps
<br />permission of the Architect.
<br />6. Combination push -in conduit clips - 1" maximum conduit
<br />2.01
<br />ACCEPTABLE MANUFACTURERS
<br />PART 1 -GENERAL
<br />A.
<br />Radiology equipment
<br />7. Combination conduit hanger clamps - 2" maximum conduit
<br />3.05
<br />INFECTION CONTROL REQUIREMENTS
<br />8. Flexible conduit clips - 1" maximum flexible conduit
<br />A.
<br />EMT and IMC shall be steel (ferrous) with a protective coating, and RMC conduit shall be steel (ferrous)
<br />1.01
<br />WORK INCLUDED
<br />B.
<br />Nurses call system equipment
<br />9. Special combination conduit dips - 1" maximum conduit
<br />with a protective coating or aluminum (nonferrous) by Allied, General Electric, Republic, Triangle, or
<br />A.
<br />Coordinate with the Owner the exact requirements for the infection control measures to be executed
<br />10. One hole steel straps
<br />Wheatland. Special use may be red brass or stainless steel.
<br />A.
<br />Comply with the provisions of Sections 16050.
<br />1.06
<br />OWNER FURNISHED INFORMATION
<br />and performed during the course of this Project.
<br />11. Conduit hangers - 4" maximum conduit
<br />12. Combination box/conduit hangers for supporting conduit within T-0" of a box are not acceptable
<br />B.
<br />Surface metal raceways shall be Wiremold.
<br />B.
<br />Provide a complete system of conductors for lighting, power, and systems throughout the project.
<br />A.
<br />To the extent the Owner has performed and made available as Owner Furnished Information an Infection
<br />B.
<br />r present o h Owner for royal a written execution Ian for each infection control
<br />Piro to execution, p s t t the pp p
<br />Control Risk Assessment (ICRA), the Contractor shall execute all requirements of the Contract Documents in
<br />measure.
<br />PART 3 - EXECUTION
<br />C.
<br />EMT, IMC, or RSC couplings, connectors, and fittings shall be steel as manufactured by Raco or equivalent.
<br />1.02
<br />RELATED WORK
<br />accordance with the ICRA, and shall perform and provide all labor, materials and supervision to execute the
<br />specific infection control measures identified therein.
<br />C.
<br />re needed with all other trades and disciplines.
<br />Coordinate infection control measures as de p
<br />3.01
<br />INSTALLATION REQUIREMENTS
<br />D.
<br />RAC couplings, connectors, and fittings shall be aluminum.
<br />A.
<br />Section 16050: Basic Requirements for Electrical Systems
<br />B.
<br />The Contract Documents do not necessarily depict all the work required by the ICRA, nor are the Contract
<br />D.
<br />Provide documentation of infection control measures to the Owner, as required and specified in the
<br />A.
<br />Secure conduits to within 3 feet of each outlet box, junction box, cabinet and fitting and at intervals not
<br />E.
<br />Erickson couplings shall be used where neither length of conduit can be rotated.
<br />B.
<br />Section 16110: Raceways and Boxes for Electrical Systems
<br />Documents responsible for the information contained in the ICRA. The Contractor shall request, and obtain if
<br />ICRA.
<br />to exceed ten feet in accordance with current edition of the National Electrical Code.
<br />available, the Owner's ICRA documentation, become familiar with its requirements and perform all work
<br />F.
<br />EMT box connectors and couplings shall be set screw type.
<br />1.03
<br />REFERENCES
<br />accordingly.
<br />3.06
<br />TESTING ELECTRICAL SYSTEMS
<br />B.
<br />Install clamps secured to structure for feeder and other conduits routed against the structure. Use drop
<br />rods and hangers to support conduits run apart from the structure.
<br />9 PP P
<br />G.
<br />Conduit, connectors, couplings and fittings shall be UL listed and labeled.
<br />A.
<br />- -
<br />NEMA WC 3 Rubber Insulated Wire and Cable for the Transmission and Distribution of Electrical
<br />1.07
<br />SUBMITTALS
<br />A.
<br />On completion of work, installation shall be completely operational and entirely free from grounds,
<br />Energy
<br />short circuits, and open circuits. Perform operational tests as required to demonstrate substantial
<br />C.
<br />Provide and install suitable angle iron, channel iron or steel metal framing with accessories to support
<br />2.02
<br />ELECTRICAL METALLIC TUBING (EMT)
<br />A.
<br />Comply with provisions of Division 1.
<br />completion of the Work. Balance circuits so that feeders to panels are not more than 10% out of
<br />or brace electrical equipment including safety switches, fixtures and panelboards.
<br />B.
<br />NEMA WC 5 - Thermoplastic -Insulated Wire and Cable for the Transmission and Distribution of
<br />balance between phases with all available load energized and operating. Furnish all labor, materials
<br />A.
<br />Use Electric Metallic Tubing (EMT) where shown on drawings or for:
<br />Electrical Energy
<br />1.08
<br />OPERATING AND MAINTENANCE MANUALS
<br />and instruments for above tests. All ampere readings shall be made with a true RMS reading meter.
<br />D.
<br />Paint all supporting metal not otherwise protected, with rust inhibiting primer and then with a finish
<br />1. Concealed in walls
<br />coat if appropriate to match the surrounding metal surfaces. (Prepainted or galvanized support
<br />2. Installed above suspended ceilings
<br />C.
<br />ANSI/UL 83 - Thermoplastic -Insulated Wire and Cables
<br />A.
<br />Provide manuals in accordance with Division 1.
<br />B.
<br />Perform megger tests of all service entrance circuits, feeder and branch circuits size #4 AWG and
<br />material is not required to be painted or repainted.)
<br />3. Installed exposed, above 6 feet
<br />larger. Provide a report of all such megger test results.
<br />D.
<br />NFPA 70 - National Electrical Code, latest edition
<br />B.
<br />In addition to required submittals, include copies of all test reports required in Part 3, "Execution" of section
<br />E.
<br />Use of chains, perforated iron strap, baling wire, or tie wire for supporting conduit runs will not be
<br />2.03
<br />RIGID STEEL CONDUIT (RSC)
<br />16050.
<br />C.
<br />Furnish the Architect a copy of test reports and required certification including but not limited to the
<br />permitted.
<br />1.04
<br />SUBMITTALS
<br />following:
<br />A.
<br />Use rigid steel conduit where shown an drawings or for:
<br />C.
<br />Provide completed warranty certificates for systems and equipment.
<br />1. Switchboard and panelboard load test - include ampere readings of all panels and major circuit
<br />F.
<br />Use of Caddy clips to support conduit to top of t-bar ceiling grid will not be permitted.
<br />1. Installed underground
<br />A.
<br />Submit the data sheets for products furnished under this Section.
<br />breakers
<br />2. Above ground service entrance
<br />1.09
<br />DELIVERY AND STORAGE
<br />2. Patient Care Area Grounding System Test
<br />G.
<br />For support of low voltage wiring not required to be in conduit, Contractor shall bundle cables together
<br />3. Medium voltage circuits
<br />1.05
<br />DELIVERY, STORAGE AND HANDLING
<br />3. Megger test results
<br />in a neat manner using approved nylon cable ties. Bundled cables shall be supported with "J" hooks
<br />4. For emergency feeders and critical branch circuits
<br />A.
<br />Insofar as possible, deliver items in manufacturer's original unopened packaging. Where this is not practical,
<br />4. Power System Analysis Report
<br />on telephone type bridle rings, a minimum of six feet on centers.
<br />5. Where protection from EMI is required
<br />A.
<br />Provide factory -wrapped waterproof flexible barrier material for covering wire and cable wood reels,
<br />cover items with protective materials to keep them from being damaged. Use care in loading, transporting,
<br />1. Maximum supported weight rating of "J" hooks shall not be exceeded.
<br />6. Exposed to severe mechanical damage
<br />where applicable, and weather resistant fiberboard containers for factory packaging of cable, wire
<br />unloading, and storage to keep items from being damaged.
<br />D.
<br />Prior to final observation and acceptance test, install all electrical systems and equipment complete
<br />2. Identification tape shall be provided at minimum intervals of 25 feet on center and within each
<br />and connectors, to protect against physical damage in transit. Damaged cable, wire or connectors
<br />and in satisfactory operating condition.
<br />individual space.
<br />2.04
<br />RIGID ALUMINUM CONDUIT (RAC)
<br />shall be removed from project site.
<br />B.
<br />Store items in a clean dry place and protect from damage. Evidence of damage from water or other
<br />contaminants will be cause for rejection.
<br />End of Section
<br />A.
<br />Use rigid aluminum conduit, RAC, where shown on the drawings or for:
<br />B.
<br />In their factory -furnished coverings, store cable, wire and connectors in a clean, dry indoor space,
<br />End of Section
<br />1. In coastal areas where saltwater vapor is present
<br />which provides protection against the weather.
<br />1.10
<br />RECORD DRAWINGS
<br />SECTION 16060
<br />2. As a substitute for rigid steel conduit when approved by engineer
<br />SECTION 16075
<br />PART 2 - PRODUCTS
<br />A.
<br />Comply with provisions of Division 1.
<br />GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
<br />PART 3 - EXECUTION
<br />IDENTIFICATION FOR ELECTRICAL SYSTEMS
<br />2.01
<br />ACCEPTABLE MANUFACTURERS
<br />PART
<br />2 - PRODUCTS
<br />PART 1 - GENERAL
<br />3.01
<br />INSTALLATION REQUIREMENTS
<br />PART 1 - GENERAL
<br />A.
<br />American Insulated Wire
<br />2.01
<br />MATERIALS AND EQUIPMENT
<br />1.01
<br />WORK INCLUDED
<br />A.
<br />Minimum size of conduits shall be 3/4"
<br />1.01
<br />WORK INCLUDED
<br />B.
<br />United Copper
<br />A.
<br />Equipment and materials furnished shall be listed by UL or other nationally accredited testing laboratory
<br />A.
<br />Comply with the provisions of Section 16050.
<br />B.
<br />Conduit joints shall be cut square, threaded, reamed smooth, and drawn up tight so conduit ends will butt in
<br />where available. When listing is not available for a piece of equipment, it shall be submitted in accordance
<br />A.
<br />Requirements for identification of electrical equipment, circuit identification, system color coding and
<br />couplings, connectors and fittings.
<br />C.
<br />Encore
<br />with Drawings and Specifications and shall be approved by the authorities having jurisdiction.
<br />B.
<br />The entire system of raceways and equipment shall be grounded in accordance with Articles 250 and
<br />warning signs.
<br />517 of the National Electrical Code and any local regulation or governing authority.
<br />C.
<br />Make bends or offsets with standard factory bends or field bends with an approved bender. Use of heat and
<br />D.
<br />Pyrotenax (Mineral Insulated applications)
<br />B.
<br />Specifications and Drawings indicate name, type and/or catalog number of materials and equipment to
<br />1.02
<br />RELATED WORK
<br />other non -approved methods will not be accepted. An approved factory built and UL tested PVC bender
<br />establish standards of quality. Submittals shall be based on the standards specified. The standards should
<br />1.02
<br />SUBMITTALS
<br />using heat is acceptable.
<br />E.
<br />Republic Wire
<br />not be construed as limiting competition.
<br />A.
<br />Section 16050: Common Work Results for Electrical
<br />A.
<br />Submittals are not required for products in this Section.
<br />D.
<br />Medium voltage conduits shall use long radius bends and fittings with a minimum radius of at least 12 times
<br />F.
<br />Southwire
<br />PART
<br />3 - EXECUTION
<br />1.03
<br />SUBMITTALS
<br />the diameter of the installed cables.
<br />PART 2 - PRODUCTS
<br />G.
<br />Superior Essex
<br />3.01
<br />COORDINATION
<br />A.
<br />Submittal of product furnished under this section is not required.
<br />E.
<br />Run concealed conduits in direct line with long radius bends or offsets. Run exposed conduits parallel to
<br />2.01
<br />REQUIREMENTS
<br />and at right angles to building lines. Group multiple conduit runs in banks and maintain proper separation to
<br />H.
<br />Cerrowire
<br />A.
<br />Install equipment in accordance with manufacturer's recommendations. Where conflicts occur between
<br />PART
<br />2 - PRODUCTS
<br />prevent any derating of cable.
<br />Contract Documents and these recommendations, request a ruling before proceeding with such Work.
<br />A.
<br />Ground clamps: OZ-Gedney, Type "CG", or equal by Steel City or Appleton.
<br />I.
<br />Okonite
<br />2.01
<br />IDENTIFICATION OF EQUIPMENT
<br />F.
<br />Conduit systems shall be electrically and mechanically continuous.
<br />B.
<br />Visit site and observe conditions under which work must be performed. No subsequent allowance will be
<br />PART 3 - EXECUTION
<br />J.
<br />General Cable
<br />made because of error or failure to obtain necessary information to completely estimate and perform work
<br />A.
<br />Identify electrical equipment with permanently attached phenolic plates with 1/4" white or black
<br />G.
<br />For interior locations where NEMA 1 enclosures are used, secure conduits to boxes and cabinets with
<br />required by these documents.
<br />3.01
<br />INSTALLATION REQUIREMENTS
<br />engraved lettering on the face of each, attached with two sheet metal screws. Provide nameplate
<br />double locknuts and bushing.
<br />2.02
<br />CONDUCTORS
<br />colors as specified in other parts of this section.
<br />C.
<br />Examine Specifications and Drawings to be familiar with items which require electrical connections and
<br />A.
<br />General
<br />H.
<br />For interior locations where NEMA 12 enclosures are used, secure conduits to boxes and cabinets with
<br />A.
<br />Provide 98% conductivity copper conductors with 600V insulation.
<br />coordination. Electrical Drawings are diagrammatic and shall not be scaled for exact sizes.
<br />1. Refer to National Electrical Code Article 517 and the drawings for grounding requirements.
<br />B.
<br />Include the following information on panelboard identification plates:
<br />sealing locknuts and bushing.
<br />2. Clean all conductive surfaces on equipment to be grounded, to ensure good electrical continuity.
<br />1. Panel Name
<br />B.
<br />For conductors No. 12 AWG and No. 10 AWG, provide stranded type THWN or THHN.
<br />D.
<br />Prior to commencement of installation, prepare coordination drawings for work under this division, as
<br />3. Effectively bond all grounding conductors to grounding electrodes, equipment enclosures and
<br />2. Name of panel serving it
<br />I.
<br />For damp or wet locations, indoor or outdoor locations where NEMA 4 or 4X enclosures are used, secure
<br />specified in Division 1 and as called for herein. Coordinate work under other divisions, including but not
<br />ground buses.
<br />3. Voltage and Phase
<br />conduits to boxes and cabinets with Myers Scru-Tite hub.
<br />C.
<br />For conductors No. 14 AWG and smaller, provide solid type THHN.
<br />limited to mechanical, plumbing, fire protection, telecommunication and miscellaneous steel to develop these
<br />4. Locate all grounding attachments away from areas subject to physical damage. Provide
<br />4. On service equipment, legibly mark in the field the maximum available fault current and the date
<br />coordination drawings that will serve as the agreed upon plan for a coordinated installation of work for all
<br />protective covering as required.
<br />that the fault current calculation was performed per NEC 120.24, 2011.
<br />J.
<br />Provide grounding bushings on all feeder conduits in critical care areas in accordance with NEC Article 517.
<br />D.
<br />For conductors No. 8 AWG and larger, provide stranded type THHN, or THWN applied consistently
<br />trades. Include electrical equipment, switchgear, panelboards, starters, disconnect switches, cable tray,
<br />with insulation ratings and NEC requirements.
<br />conduit racks and conduits 3" and larger on drawings confirming coordination with other trades. Incorporate
<br />B.
<br />Feeder/Branch Circuits:
<br />2.02
<br />CIRCUIT IDENTIFICATION
<br />K.
<br />Cap ends of conduits to prevent entrance of water and other foreign material during construction.
<br />the information onto the coordination drawings required under Division 1 and 15 to develop master
<br />1. Provide a separate green grounding conductor in the conduit of feeder circuits for the following
<br />E.
<br />Provide white or gray colored neutral conductors; provide color coded phase conductors.
<br />coordination drawings. Account for lighting fixture depths in the coordination. Inform Design Professional of
<br />equipment, sized in accordance with Table 250.122 of the National Electrical Code:
<br />A.
<br />Identify feeder j-boxes and pull boxes with designation of panelboard/switchboard source as "FROM"
<br />L.
<br />Complete conduit systems before pulling conductors.
<br />conflicts that cannot be resolved.
<br />a. Panelboards
<br />and load served as "TO" with permanent labels.
<br />F.
<br />Minimum conductor size shall be:
<br />2. Install a separate green grounding conductor in same conduit as phase and neutral conductor
<br />M.
<br />Support conduits as specified in Section 16070 and in accordance with National Electrical Code.
<br />1. #12 for power wiring
<br />E.
<br />Do NOT submit coordination drawings to Architect for review. Keep a copy on site for reference purposes.
<br />from panel ground bus to device for branch circuits. Install an equal number of grounding and
<br />B.
<br />Identify pull and junction boxes with the designation of panelboard and the circuit number of each
<br />2. #14 for hard wired controls unless otherwise specified
<br />Notify Architect of conflicts that cannot be resolved.
<br />neutral conductors. Size the grounding conductor in accordance with Table 250.122 of the
<br />circuit contained therein, with permanent marker. Clearly mark information on or in the box, not on the
<br />N.
<br />Provide cable supports in conduits rising vertically in accordance with the National Electrical Code, Article
<br />National Electrical Code.
<br />cover, so that the information is easily identifiable.
<br />300.
<br />3.02
<br />FEES AND PERMITS
<br />3. Bond the receptacle ground pin to its box using a bonding jumper, except where isolated ground
<br />receptacles are required.
<br />C.
<br />Identify circuits in conduits entering outlet boxes with the designation of panelboard and the circuit
<br />O.
<br />Provide insulated bushing on both ends of empty conduits.
<br />A.
<br />Obtain and pay for all necessary permits and inspection fees required for electrical installation.
<br />4. Flexible conduit will not be approved as a grounding means. Flexible conduit shall have a jumper
<br />number of each circuit contained therein, with permanent marker.
<br />wire sized to ampacity of branch breaker and connected to conduit system on both ends. This
<br />Conduits which pass through floor slabs (except ground floor) shall be sealed with UL listed fire -stopping
<br />3.03
<br />DEMOLITION
<br />applies to fixtures, motors, controls and other devices.
<br />2.03
<br />COLOR CODE IDENTIFICATION
<br />materials. Seal around conduits or other wiring materials passing through partitions, which extend to the
<br />underside of the slab above, and those passing through smoke partitions and fire rated walls. Use U.L.
<br />A.
<br />Visit the site to observe existing conditions before submitting a bid.
<br />A.
<br />Color code phenolic plates utilized to identify electrical equipment according to which branch of the
<br />listed materials to prevent passage of smoke or fire. See Division 7 for specific materials required.Conduits
<br />End of Section
<br />electrical system the equipment is connected to as follows:
<br />which enter crawl spaces, tunnels, and basements from outside the building shall be grouted -in to prevent
<br />B.
<br />Work in existing buildings shall be scheduled well in advance with the Owner's Representative. Work shall
<br />1. Normal - Black with white letters.
<br />entry of gases, vapors, insects or rodents to these spaces from street mains.
<br />be performed at such times and under such conditions as suit the convenience of the Owner's
<br />Representative. Plan the Work to minimize disruption of normal operations. Notify Owner's Representative
<br />B.
<br />If existing equipment identification nameplates are a different color, request a ruling from the design
<br />P.
<br />When four or more, 2 inch or larger conduits, are banked together below the ground floor slab they shall be
<br />before any circuit is de -energized in occupied areas.
<br />professional to determine what color scheme to follow.
<br />supported and separated using Carton, Snap-Loc type spacers. Backfill below, between, and above ducts in
<br />such a manner to prevent erosion and restore sub -grade preparation prior to concrete slab pour.
<br />C.
<br />Reconnect circuits to other panelboards when required to complete the renovation shown.
<br />C.
<br />Spot paint conduits every 10 to 15 feet and at least once above every room utilizing the color code
<br />above.
<br />Q.
<br />Where IMC or RMC conduit is connected to a panelboard, switchboard, cabinet, junction box, pull box or
<br />D.
<br />Remove abandoned wire and conduit back to source. Splice and terminate in junction boxes as appropriate.
<br />auxiliary gutter, conductors shall be protected by insulated bushings. Locknuts shall be installed on conduit
<br />Where entire circuit is to be removed, remove conduit and wire back to existing panelboard. Where such
<br />D.
<br />The color code as outlined below shall be used. In addition, on each panelboard, pull box, control
<br />outside and inside enclosure.
<br />work would not be possible without disturbing areas not being renovated, consult with the Architect prior to
<br />cabinet, or other electrical enclosure that contains circuits from more than one system, provide an
<br />performing the work.
<br />engraved phenolic plate and indentify the circuit conductors with the following color code:208Y/120,
<br />R.
<br />Where conduits stub up in conduit space beneath switchboards or switchgear and do not connect directly to
<br />Phase A, black, Phase B, red, Phase C, blue, grounded conductor, white, equipment grounding
<br />equipment enclosures, install malleable iron nylon insulated ground bushing complete with bonding
<br />E.
<br />Where a circuit is interrupted by removal of a device or fixture from that circuit, install wire and conduit as
<br />conductor, green, isolated equipment grounding conductor, green/yellow stripe. 480Y/277, Phase A,
<br />connection and bond to switchboard ground bus.
<br />required to restore service to the remaining devices and fixtures on that circuit. Ensure proper grounding is
<br />brown, Phase B, orange, Phase C, yellow, grounded conductor, gray, equipment grounding conductor,
<br />maintained.
<br />green, isolated equipment grounding conductor, green/red stripe.
<br />S.
<br />Install seal -off fittings in conduits entering hazardous areas and conduits entering cold temperature areas,
<br />such as freezers and refrigerators.
<br />F.
<br />Lighting fixtures, wiring devices, panelboards, equipment, conduits and conductors removed shall be
<br />transported to the Owner's designated location and offered to the OWNER. If he chooses to retain these
<br />T.
<br />Use expansion fittings or flexible conduit, property bonded, to ensure ground continuity across expansion
<br />items or a part of these items, turn those chosen over to him. Items rejected by the OWNER shall be
<br />joints in floors and ceilings.
<br />removed completely from the project site and disposed of legally by the CONTRACTOR.
<br />U.
<br />Terminate conduits for feeders and branch circuits directly into panelboard enclosures from which they are
<br />served without the use of pull boxes, junction boxes, wire ways, or auxiliary gutters. If the panelboard
<br />enclosure does not provide sufficient surface area for all conduits, notify the Engineer and request
<br />directions.
<br />AA 26001479
<br />Sheet Notes:
<br />Smith
<br />W"kSeckman
<br />Reid,lnc.
<br />301 North Cattlemen Road, Suite 300
<br />Sarasota, FL 34232
<br />(941) 907-7750
<br />FAX: (941) 907-7751
<br />www.ssr-inc.com
<br />Firm Certification - CA-0000857
<br />SSR# 166044.0
<br />Erick Phelps - PE #64598
<br />Christopher E. Durham - PE #76655
<br />``` %J 1111111/111
<br />QQ�FR EDWgRO
<br />01NSF• •.'py i
<br />No. 76655
<br />STATE OF
<br />/,//0NA„o
<br />Christopher Edward Durham
<br />PE License No. 76655
<br />FI i"_N miff k, 1 -0,1% M
<br />LVJ K I DA C"A N (-. E K
<br />E C I A L I S T
<br />Research Institute
<br />Key Plan
<br />MARK ISSUE DATE DESCRIPTION
<br />Issue Log
<br />CONSTRUCTION
<br />DOCUMENTS
<br />FLORIDA CANCER SPECIALISTS
<br />EQUIPMENT REPLACEMENT
<br />38010 MEDICAL CENTER AVE.
<br />ZEPHYRHILLS, FL 33540
<br />Drawing Title
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />VARTILI
<br />06/29/2016
<br />Scale
<br />Sheet Number
<br />E-002
<br />Drawn By KDS
<br />Approved By MLG
<br />Filename
<br />Sc atCo, LLC 2007
<br />
|