Laserfiche WebLink
L - - <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. Conductors shall be continuous from origin to panel or equipment termination without splices. <br />Where splices and taps are necessary or required, they shall be made in splice boxes. <br />B. Install pull boxes in circuits or feeders over 100' long. <br />C. Make splices and connections only in outlet, pull or junction boxes. Twist conductors together <br />before installing wire nuts or connectors. <br />D. Multi -wire branch circuits shall not be used. Install a separate grounded conductor, (neutral) for <br />each circuit. <br />E. Use powdered soapstone or pulling compound to pull conductors. <br />F. Deliver conductors to jobsite new and in original wrapping, package or reel. <br />G. Conductors and connections shall test free of grounds, shorts, and opens. <br />H. Provide No. 10 wire in lieu of No. 12 wire for any branch circuit in excess of 100 feet (120V) or <br />150 feet (277V) of circuit length to farthest device to prevent excessive voltage drop. <br />I. Use Ideal wire nuts, Scotchlok Type Y, R, G, or B connectors for fixture connections at outlet <br />boxes. <br />J. Make feeder taps and joints with approved compression sleeves. Insulate sleeves with heat <br />shrink tubing, rated 600V., 90 degree C., containing factory applied sealant. <br />K. Leave a minimum of 8" slack wire in every outlet box whether it be in use or left for future use. <br />L. Color code conductors as follows: <br />1. 120/208 Volt Systems: <br />a. Phase A - Black <br />b. Phase B - Red <br />C. Phase C - Blue <br />d. Neutral - White <br />e. Ground - Green <br />f. Isolated Ground - Green with Yellow stripe <br />2. 277/480 Volt Systems: <br />a. Phase A - Brown <br />b. Phase B - Orange <br />C. Phase C - Yellow <br />d. Neutral - Gray <br />e. Ground- Green <br />M. Use factory color coded conductors where commercially available. If not available, use black <br />conductors and band with color tape. <br />N. Install in each branch -circuit panelboard a legend explaining color code for ungrounded <br />conductors. <br />O. Complete conduit system, including bushings, before pulling wire and cable. <br />P. Maintain separation of electric light, power, Class 1, 2 and 3 wiring throughout raceway <br />systems. Comply with requirements of NFPA-70, paragraphs 300-3, 725-15 and 725-54. <br />3.02 FIELD TESTING <br />A. Visually check wire, cable, and connectors for physical damage and proper installation. <br />B. Check continuity of wire and cable using a low voltage DC tester. <br />C. Check for proper torque on all mechanical connections. <br />D. Perform a 1000 VDC megger test on all 600 volt insulated wire or cable #4 AWG and larger. <br />Check each wire to ground and to all other wires in the same cable or conduit by connecting <br />each wire not under test together and to ground. Wire or cable shall be disconnected at each <br />end and protected from current leakage during testing. <br />1. Feeder (600A & smaller) circuits and branch circuits <br />a. Use either a motor driven (Biddle 359) or a hand crank (Biddle MJ159) megger <br />b. Perform a dielectric absorption ratio test using a 60-second test period. Record the <br />megohm readings at 30 seconds and 60 seconds. Calculate the dielectric <br />absorption ratio (60 sec / 30 sec readings) and record <br />E. Provide 3 copies of the megger test report to the Engineer. The report shall be in a tabulated <br />format and shall include the following as a minimum. <br />1. Circuit identification <br />2. Type of raceway <br />3. Approximate length of circuit <br />4. Megohm readings <br />5. Polarization index or dielectric absorption ratio <br />6. Ambient temperature <br />7. Approximate humidity (dry, average, or humid) <br />F. Results <br />1. Acceptable <br />a. Megohms greater than (1.6 x 1000 / length) <br />b. Polarization index greater than 2.0 or a dielectric absorption ratio greater than 1.4 <br />2. Questionable (must be discussed with Engineer) <br />a. Polarization index range 1.0 < 2.0 or a dielectric absorption ratio range 1.0 < 1.4 <br />3. Unacceptable (wire or cable must be replaced) <br />a. Megohms less than (1.6 x 1000 / length) <br />b. Polarization index less than 1.0 or a dielectric absorption ratio less than 1.0 <br />End of Section <br />SECTION 16130 <br />OUTLET BOXES <br />PART 1-GENERAL <br />1.01 WORK INCLUDED <br />A. Comply with the provisions of Section 16050. <br />B. Provide each fixture, switch, receptacle, and other wiring device with a galvanized outlet box of <br />appropriate size and depth for its particular location and use. <br />1.02 RELATED WORK <br />A. Section 16070: Hangers and Supports for Electrical Systems. <br />B. Section 16110: Raceways and Conduit Systems. <br />C. Section 16075: Identification for Electrical Systems. <br />1.03 SUBMITTALS <br />A. Submittal of products furnished under this Section is not required. <br />PART 2-PRODUCTS <br />2.01 ACCEPTABLE MANUFACTURERS <br />A. National <br />B. Appleton. <br />C. Raco. <br />D. General Electric. <br />E. Steel City. <br />2.02 SUPPORTING DEVICES <br />A. Provide appropriate supporting devices for outlet boxes by Caddy Fasteners or equal as <br />follows: <br />1. "RB" box mounting brackets. <br />2. Screw gun box brackets. <br />3. "H" box mounting brackets. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION REQUIREMENTS <br />A. Locate boxes to prevent moisture from entering or accumulating within them. <br />B. Support outlet boxes independently of conduit, as required by the National Electrical Code. <br />C. Provide 4" octagonal x 1-1/2" deep ceiling outlet boxes. For increased cubic capacity, provide <br />4" octagonal x 2-1/8" , 4" square x 1-1/2" or 4-11/16" square x 2-1/8" ceiling outlet boxes. <br />D. Provide 4" square X 1-1/2" deep boxes for switch and receptacle outlets in drywall partitions. <br />Use square cut plaster rings installed within 1/4" of finished wall. <br />E. Provide 4" square x 2-1/2" deep boxes for telephone/data outlets in drywall partitions. Use <br />square cut plastic rings installed within 1/4" of finished wall. <br />F. Where required to hang a specified fixture, provide a fixture stud of the no -bolt, self-locking <br />type on ceiling outlets. <br />G. Provide 2-1/2" x 3-3/4" one gang masonry boxes for switches and receptacles installed in <br />concrete block walls not plastered. For increased cubic capacity, provide 3-1/2" x 3-3/4" one <br />gang masonry boxes. Where more than two conduits enter the box from one direction, provide <br />4" square boxes with square cut device covers not less than 1" deep specifically designed for <br />this purpose. Use round edge plaster rings only if the block walls are to be plastered. Use <br />sectional or gangable type outlet boxes only in drywall construction. <br />H. Provide 4-11 /16" square X 2" deep outlet boxes with square cut device comers for block walls <br />or round edge plaster rings for plastered walls for telephone outlets, data outlets, and private <br />intercom interphones. Single gang device boxes are not acceptable. <br />1. Provide fittings with threaded hubs for screw connections and with the proper type covers for <br />switches and receptacles served by exposed conduit. Use pressed steel outlets only for ceiling <br />fixture outlets. Provide condulets with threaded hubs and covers and with proper configurations <br />for all changes of direction of exposed conduits. Standard conduit ells may be used if they do <br />not interfere, damage, or mar the appearance of the installation. <br />J. Use boxes of sufficient cubic capacity to accommodate the number of conductors to be <br />installed in compliance with Article 314 of the NEC. <br />K. Effectively dose unused openings in boxes with metal plugs or plates. <br />L. Set boxes so that front edges of device extensions, plaster rings, etc are flush with finished <br />surfaces. <br />M. Caddy "H" type box mounting brackets shall not be used on exterior walls, chase walls, or in <br />any other installation where the backside of the stud wall will not be finished. Do not use 4" <br />brackets in thicker stud walls which will not provide adequate bracing. <br />N. Secure boxes to surfaces upon which they are mounted or embed boxes in concrete masonry. <br />Support boxes from structural members with approved braces. <br />O. Install blank device plates on outlet boxes left for future use. <br />P. Provide bushings in holes through which cords or conductors pass. <br />Q. Install boxes so that the covers will be accessible at all times. <br />R. Electrical outlet boxes may be installed in vertical fire resistive assemblies classified as <br />fire/smoke and smoke partitions without affecting the fire classification, provided such openings <br />occur on one side only in each framing space, that openings do not exceed sixteen square <br />inches and that boxes on opposite faces of a partition are separated horizontally not less than <br />24 inches. All clearances between such outlet boxes and the gypsum board shall be <br />completely filled with joint compound or approved fire -resistive compound. The wall shall be <br />built around outlet boxes larger than sixteen square inches so as not to interfere with the wall <br />rating. <br />S. Comply with the requirements of the USG Cavity Shaftwall Systems Folder SA 926 (most <br />current edition) for installation of outlet boxes in rated shaftwall systems. Do not exceed the <br />depth of the C - H stud with any part of the installation of an outlet box. Provide outlet box with <br />a trim plate so that the top layer of the two required face layers of gypsum board are <br />overlapped without a common joint. Do not penetrate the single layer of 1" shaftwall liner panel <br />with outlet or switch boxes. Do not exceed 16 square inches of surface area with any <br />individual outlet box or a total aggregate surface area of 100 square inches for all boxes in a <br />shaftwall on a floor (per the U.L. Fire Resistance Directory). <br />T. Use individual boxes to separate Essential System and Normal System light switches mounted <br />adjacent to one another. Do not use gangable boxes. <br />U. Install outlet boxes on opposite sides of the same wall offset to avoid back to back mounting <br />where possible. <br />End of Section <br />SECTION 16140 <br />MT La <br />PART1-GENERAL <br />1.01 WORK INCLUDED <br />A. Comply with the provisions of Section 16050. <br />B. Provide switches, receptacles, and other wiring devices as indicated on drawings. <br />1.02 SUBMITTALS <br />A. Submit product data for review. <br />PART 2-PRODUCTS <br />2.01 ACCEPTABLE MANUFACTURERS <br />A. Arrow Hart <br />B. Eagle <br />C. Hubbell <br />D. Leviton <br />E. Pass and Seymour <br />F. Novitas, Inc <br />G. Hubbell numbers are used unless otherwise noted, but products of equivalent quality by named <br />manufacturers will be acceptable. <br />2.02 DEVICE COLORS <br />A. Provide IVORY colored devices where available, unless otherwise noted. <br />B. Provide RED colored devices where available when connected to the emergency power <br />system, unless otherwise noted. If red devices are not available, use a black device with a red <br />plate. <br />2.03 SWITCHES <br />A. 20-Amp, 120/277 VAC, Heavy Duty, Specification Grade: <br />1. Single pole toggle: Hubbell No. HBL12211 (normal), HBL1221R (emergency) <br />2. Double pole toggle: Hubbell No. HBL12221 (normal), HBL1222R (emergency) <br />3. Three-way toggle: Hubbell No. HBL12231 (normal), HBL1223R (emergency). <br />2.04 RECEPTACLES <br />A. 20-Amp, 125 VAC: <br />1. Hospital grade duplex: Hubbell No. HBL83001 (normal), HBL830ORED (emergency). <br />2. Duplex type: Hubbell No. HBL53621 (normal), HBL5362R (emergency). <br />3. Ground fault circuit interrupter, tamper & weather resistant, Hospital grade: Hubbell No. <br />GF83001TR (normal), GF830ORTR (emergency). <br />4. Ground fault circuit interrupter, tamper & weather resistant: Hubbell No. GF53621TR <br />(normal), GF5362RTR (emergency). <br />5. Hospital grade, tamper resistant: Hubbell No. HBL830OSGIA (normal), HBL830OSGRA <br />(emergency). <br />6. Duplex, tamper resistant: Hubbell No. HBL830OSGIA (normal), HBL830OSGRA <br />(emergency). <br />7. Duplex, weather resistant, Hubbell HBL53621WR (normal), HBL5362RWR (emergency). <br />8. Duplex, isolated ground, Hubbell IG5362 (normal), IG5362R (emergency). <br />9. Single outlet, Hubbell HBL53611, (normal), HBL5361 BK unless red is available, use a red <br />plate (emergency). <br />PART 3 - EXECUTION <br />3.01 INSTALLATION REQUIREMENTS <br />A. Install Hospital grade receptacles in all patient care areas and corridors leading to patient care <br />areas. Patient care areas are defined as patient rooms, treatment and examination rooms, <br />critical care areas and any spaces where patients are domiciled, examined, evaluated or <br />treated. <br />B. Install Hospital grade tamper resistant receptacles in all pediatric patient care areas including <br />corridors, waiting rooms and therapy or play areas. <br />C. Install weather resistant receptacles in damp and wet locations. <br />D. Mounting: <br />1. Mount switches 46" above the finished floor to center line of switch unless noted <br />otherwise. <br />2. Mount receptacles 18" above the finished floor to center line of receptacle unless noted <br />otherwise. <br />3. Install receptacles shown on the drawings as "special mounting height" at mounting <br />height indicated on drawings. Where no mounting height is given and receptacles are <br />above counters, mount receptacles with centers 4" above top of counter. If the counter <br />has a backsplash, receptacles shall be mounted with centers 4" above top of backsplash. <br />Where special mounting height receptacles are not above counters and no mounting <br />height is indicated, receptacle mounting heights shall match adjacent light switches or <br />above counter receptacles. Coordinate the installation of all special mounting height <br />receptacles with architectural design. <br />4. Work devices to nearest block course using proper type outlet boxes as specified under <br />Section 16130. Check architectural and furniture drawings for counter (desk, special <br />booth, etc.) locations. Mount devices above work counters. Verify other special mounting <br />conditions and locate devices as required. <br />E. Polarity: Wire receptacles so that the hot wire, neutral wire and ground wire connect to the <br />proper terminals. <br />F. Wiring: Spade type insulated terminals shall be used on stranded wire. Feed thru feature shall <br />not be used. Feed thru circuits shall be connected using proper wire nuts with a jumper wire <br />connection to receptacle. <br />G. Terminal connection: Push -in type wire connections shall not be used. All terminations shall be <br />made using the screw terminals with proper torque. <br />H. Grounding: Install a No. 12 green ground wire from device grounding terminal back to <br />grounding bus in panelboard. <br />I. Install floor boxes or poke -through fittings where shown on drawings with receptacle and/ r <br />p 9 9 90 <br />communication outlet quantities as shown on drawings. <br />1. Install one 3/4" conduit from power compartment to a junction box above accessible <br />ceiling for each floor box. Box configuration to allow interconnection from end power <br />compartment to opposite end power compartment. <br />2. Install one dedicated 1" conduit from each communications compartment, stubbed out <br />above accessible ceiling for each floor box. <br />J. Install receptacles with ground pin up. <br />K. In renovation and/or addition projects, if existing receptacles are not installed with ground pin <br />up, request a ruling from the Facilities Director. <br />L. For GFCI receptacles, do not utilize feed-thru feature, unless indicated so by drawings. If <br />feed-thru is used, all downstream receptacles must have a GFCI Protected label on them. <br />M. The feed-thru connection of the receptacle shall not be used when 15 ampere receptacles are <br />installed on a 20 ampere circuit. The feed-thru circuit and incoming circuit must be connected <br />with proper wire nuts with a pigtail out to the receptacle. <br />N. The push in connection shall not be used. All connections shall be made using screw type <br />terminals. <br />O. Where stranded wire is used, proper sized, spade type, insulated terminals shall be used. <br />P. A single receptacle installed on an individual branch circuit shall have an ampere rating of not <br />less than that of the branch circuit. <br />End of Section <br />SECTION 16141 <br />WIRING DEVICE PLATES <br />PART 1 -GENERAL <br />1.01 WORK INCLUDED <br />A. Comply with the provisions of Section 16050. <br />B. Provide device plates on switches, receptacles, telephone outlets and miscellaneous devices. <br />1.02 RELATED SECTIONS <br />A. Section 16140: Wiring Devices <br />1.03 SUBMITTALS <br />A. Submit product data for review. <br />1.04 ACCEPTABLE MANUFACTURERS <br />A. Arrow Hart <br />B. Eagle <br />C. Hubbell <br />D. Leviton <br />E. Pass & Seymour <br />F. Novitas, Inc. <br />1.05 PRODUCTS <br />A. Provide specification grade nylon device plates from the wiring device manufacturer. Provide <br />device plates in colors to match the associated devices. <br />B. Provide cast alloy or stamped metal plates on surface mounted switches, receptacles, and <br />other devices. <br />C. All receptacles and switches shall have engraved cover plates to indicate the panel board and <br />circuit numbers powering the device. <br />PART 2 - EXECUTION <br />2.01 INSTALLATION REQUIREMENTS <br />A. Install device plates in full contact with wall surface. Plates shall not project out from the wall. <br />B. Install device plates in full contact with surface mounted box. Plates shall not project out from <br />the edge of the box. <br />C. All receptacles and switches shall have engraved cover plates to indicate the panel board and <br />circuit numbers powering the device. <br />End of Section <br />SECTION 16441 <br />PANELBOARDS <br />PART 1-GENERAL <br />1.01 WORK INCLUDED <br />A. Comply with the provisions of Section 16050. <br />B. Provide circuit breaker type panelboards as indicated on drawings and as specified hereinafter, <br />1.02 RELATED SECTIONS <br />A. Section 16121: Low -Voltage Electrical Power Conductors and Cables <br />B. Section 16060: Grounding and Bonding for Electrical Systems <br />C. Section 16075: Identification for Electrical Systems <br />1.03 REFERENCES <br />A. UL 67 Panelboards <br />B. UL 50 Cabinets and Boxes <br />C. NEMA PB 1 <br />D. Federal Spec W-P-115C <br />1.04 SUBMITTALS <br />A. Submit the following product data for review: <br />1. Shop drawings showing circuit breaker or fusible switch layout, dimensions, voltage, <br />phasing, continuous current capacity, short circuit rating, series rating (if applicable) <br />2. Conduit entry location, cable termination sizes, mounting <br />PART 2-PRODUCTS <br />2.01 ACCEPTABLE MANUFACTURERS <br />A. Square D <br />2.02 PANELBOARD TYPES <br />A. Circuit breaker type power distribution panelboards for 277/480 volts, 3-phase, 4-wire service <br />shall be equipped with circuit breakers having AIC rating as indicated on the drawings. Where <br />AIC ratings are not shown on drawings, obtain the rating requirements from the Architect. <br />Panelboards shall be equal to: <br />1. Square D, "I -Line" series distribution type <br />2. Square D, "NF power type <br />B. Bus bars shall be copper. <br />C. Power distribution panelboards shall be a minimum 36" in width. <br />D. Power distribution panelboards shall be furnished with full -height bussing. <br />2.03 REQUIRED FEATURES <br />A. Provide circuit breakers with lugs (both main and branch circuit lugs) suitable and UL listed for <br />both aluminum and copper conductors and rated for minimum 75 degrees C. <br />B. Provide electrically isolated factory installed neutral bus. Neutral bus shall have at least 100% <br />connection points based on panel circuit rating. <br />C. Provide a second, fully rated electrically isolated factory installed, neutral bus where called for <br />on the drawings. <br />D. Provide separate ground bars complete with lugs or connectors on bar. Provide an additional <br />copper isolated/insulated ground bar where indicated on drawings. <br />E. Panelboard assembly shall be enclosed in a steel cabinet. The size of the wiring gutters shall <br />be in accordance with U.L. Standard 67. Fronts shall have door with matching trim, be of code <br />gauge full finished steel with rust inhibiting primer and baked enamel finish. <br />F. Cabinets shall be equipped with spring latch and tumbler lock on door of trim. Doors over 48" <br />long shall be equipped with three point latch and vault lock. All locks shall be keyed alike. <br />G. Surface mounted panelboards shall be provided with hinged trims such that devices, lugs, and <br />gutters may be exposed without completely removing trim. Flush mounted panelboards shall <br />have "easy -to -remove" or "door -in -door" covers. <br />H. Provide thermal magnetic circuit breakers which are fully rated and temperature rated for a 40 <br />degrees C ambient. Breakers shall be quick -make, quick -break type with trip indication shown <br />by handle position other than ON or OFF and with a common trip on all multi -pole breakers. <br />I. Refer to drawings for numbers of branch circuits, their ratings, number of poles and <br />arrangements. <br />J. Exposed external surfaces of the enclosure and cover shall be properly cleaned and painted <br />gray, ANSI 61. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION REQUIREMENTS <br />A. Install per manufacturer's recommendations and contract documents. <br />B. Ground separate ground bars to panel boxes and to the main service entrance ground bus with <br />a code -sized equipment grounding conductor installed in the same conduit as the phase and <br />neutral conductors. <br />C. Install branch circuits using a separate neutral for each circuit. Mulitwire circuit are not <br />acceptable. <br />D. Provide typed directory cards under plastic on the doors of branch circuit panelboards. <br />Directories shall indicate devices being served including space numbers or space names in <br />which devices or fixtures are located. Space names and numbers shall match the graphics <br />installed if different from the space names and numbers on the drawings. <br />E. Check tightness of all accessible mechanical and electrical connections to assure they are <br />torqued to the minimum acceptable manufacturer's recommendations. <br />F. Check all installed panels for proper grounding, fastening, and alignment. <br />G. Remove debris from panelboards and wipe dust and dirt from all components. <br />H. Repaint marred and scratched surfaces with touch-up paint to match original finish. <br />I. Where panelboards are installed flush mounted, provide a minimum of (6)-1" spare conduits <br />stubbed out above ceiling for future use by owner. <br />J. Where multiple panels are flush mounted in public areas, provide enclosures and covers of <br />matching dimensions. <br />End of Section <br />SECTION 16705 <br />LOW VOLTAGE SYSTEM ROUGH -IN REQUIREMENTS <br />PART 1-GENERAL <br />1.01 WORK INCLUDED <br />A. Comply with the provisions of Section 16050. <br />B. Provide rough -in including backboxes, backboards, conduit, conduits stubbed up, etc. as <br />required for the following systems being supplied by the Owner or others: <br />1. Telephone System. <br />2. Information/Data Systems. <br />C. Interior systems will be selected and furnished by Owner. <br />D. Provide conduit, outlet boxes and cover plates, sleeves, cabinets and plywood backboards. <br />E. Install interior systems risers and branch circuit cables. <br />1.02 RELATED WORK <br />A. Section 16060: Grounding and Bonding for Electrical Systems <br />B. Section 16070: Hangers and Supports for Electrical Systems <br />C. Section 16110: Raceways and Conduit Systems <br />D. Section 16131: Pull and Junction Boxes <br />E. Section 16130: Outlet Boxes <br />F. Section 16141: Wiring Device Plates <br />PART2-PRODUCTS <br />2.01 EQUIPMENT AND MATERIALS <br />A. Interior systems components provided by Owner/Others will include system equipment, special <br />outlet box receptacles, power unit cabinets, special outlet boxes, and cable. <br />B. Provide 4'x8'x3/4" plywood backboards, painted with two coats of flat black fire retardant, paint <br />where shown on drawings. <br />C. Install outlet boxes with conduit stubbed up above nearest accessible ceiling or to cable tray. <br />Where nearest accessible ceiling does not provide direct access to cable tray or nearest <br />telecom closet, provide associated quantity and size of sleeves in walls and cable supports <br />suitable for cable as required to gain access to cable tray or nearest telecom closet. <br />D. Install underground service entrance conduit for telephone/CATV service to the main <br />equipment room as shown on drawings. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION REQUIREMENTS <br />A. Schedule systems deliveries and installation with Owner and vendor. <br />B. Receive, inventory, store, and protect equipment and cable furnished by Owner. <br />C. Install special outlet boxes provided by Owner for dictation, computer, and CAN systems as <br />directed by Owner and vendors. <br />D. The Contractor shall have the local telephone utility, the systems vendors, and the Owner <br />review the drawings to verify that provisions on the drawings will accommodate the installation <br />of the proposed services and systems. Report discrepancies promptly to Architect. <br />E. Schedule systems start-up, inspections, and certifications with owner and vendors. <br />F. Service Entrance Requirements: <br />1. Provide trenching and backfilling required for installation of service entrance conduits <br />2. Install a pull wire or rope for installation of service cables. <br />3. Coordinate service entrance with local service provider. <br />G. Provide a complete conduit system for cable installation. <br />H. Install a separate conduit stubbed up and bushed above accessible ceilings, and bushed into <br />the corridor ceiling space or and bushed 6 inches above the systems cable tray to serve each <br />device outlet. Size conduit in accordance with the wiring schematic furnished by the Owner. <br />Install a minimum size of 3/4 inch conduit, terminated with insulated bushing. <br />I. Cable concealed in walls or above inaccessible ceilings shall be installed in conduit. <br />J. Where open cable is run above dropped ceilings and penetrates a smoke or fire rated wall, <br />furnish and install an empty metal conduit sleeve, extending at least 6" on both sides of <br />partition with bushing on both ends. For sleeve or cable penetrations through fire or smoke <br />rated walls or partitions, provide a U.L. 1479 listed "Through Penetration Firestop" system for <br />each sleeve or cable penetration. <br />End of Section <br />SECTION 16725 - FIRE DETECTION AND ALARM SYSTEM <br />1.02 SUBMITTALS <br />A. Submit the following in accordance with Conditions of Contract and Division 1 <br />Specification Sections; <br />1. Product data sheets for system components hightlighted to indicate the specific products, <br />features or functions required to meet the specifications. <br />2. Complete conduit and wiring layout showing the addition and point-to-point wiring diagram <br />showing the point of connection to existing circuits being utilized. Include location of all devices <br />and FACP. <br />3. System power and battery charts with performance graphs and voltage drop calculations to <br />assure the system will operate per the prescribed backup time periods and under all voltage <br />conditions per UL and NFPA standards and providing for a minimum of 10% spare capacity in <br />each. <br />4. Provide voltage drop calculations for signaling circuits. <br />5. Select strobe candela rating to provide coverage per NFPA 72 guidelines, ADA <br />accessibility guidelines, and Manufacturer's recommendation. <br />6. Provide above information signed and sealed bu a Registered Florida Engineer for <br />submission to the local authority having jurisdiction. <br />2.01 ACCEPTABLE MANUFACTURERS <br />A. Provide equipment and devices used for the expansion of the exisitng system to match the <br />existing system devices or provide the next generation devices that are compatible with the <br />existing control panel. The exisitng equipment is manufactured by: <br />1. Exisitng system to remain. Specifications are for reference only. <br />2.02 EQUIPMENT <br />A. Alarm Notification Applisnces <br />1. Combination Audible/Visual Devices. Provide UL 1480 listed device with the following: <br />a. Red, impact resistant and flame retardand thermoplastic covers. <br />b. High quality voice and tone reproduction, 4" speaker with matching transformer having taps <br />for 1/4, 1/2, 1 or 2 watts at 25 or 70.7 VRMS input. <br />c. Xenon flash tube and associated lens/reflector system with different flash intensities of 15, <br />15/75, 30, 75 and 110 candela. Furnish witha visible label inside the lens to indicate the listed <br />candela rating. <br />2. Visual Only Strobe. Provide UL 1971 listed device with the following: <br />a. Xenon flash tube and associated lens/reflector system. <br />b. Provide with different flash intensities 15, 15/75, 30, 75 and 110 candela. <br />c. Provide a visible label inside the lens ti indicate the listed candela rating. <br />d. Mount with red, impact resistant and flame retardant thermoplastic cover. <br />e. Wall or ceiling mounted as show on drawings with the "FIRE" lettering oriented for easy <br />reading. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION REQUIREMENTS <br />A. Provide services of a factory authorized service representative to supervise the field <br />assembly and connection of components and the pre -testing, testing and adjustment of the <br />system. Manufacturer's representatives to be available on a 24-hour basis within 150 miles of <br />this project. <br />B. Provide system complete, in accordance with drawings, specifications and with <br />manufacturer's instructions, including conduit, boxes, wiring and accessories. <br />C. Maintain the existing system fully operational at all times while the addition to the system is <br />being constructed. <br />D. Device labeling: <br />1. Coordinate all system programming, including device descriptors, with Owner in advance. <br />Submit final programming for approval prior to implementation. <br />2. Label all initiating devices and associated remote indicating devices with the specific <br />descriptor of that device. Coordinate with Owner for proper descriptors of each device. Provide <br />a minimum 3/8-inch high lettering, located on device so ut is visible from the ground. <br />E. Wiring Installation <br />1. Install wiring in conduit and tag wires at junction points. <br />2. Obtain from Fire Alarm system Manufacturer written instruction regarding the appropriate <br />wire/cable to be used for this installation. Make no deviation from thei written instructions without <br />prior written approval from the Fire Alarm System manufacturer and engineer of record. <br />3. Color -code fire alarm conductors differently from normal building power wiring. Use one color <br />code for alarm initiating circuit wiring and a different color ocde for supervisory circuits. Color <br />code notification appliance circuits differently from alarm initiating circuits. <br />S a ILtC ®, ILILC <br />Sheet Notes: <br />AA 26001479 <br />Smith <br />Seckman <br />Reid, Inc. <br />301 North Cattlemen Road, Suite 300 <br />Sarasota, FL 34232 <br />(941) 907-7750 <br />FAX: (941) 907-7751 <br />www.ssr-inc.com <br />Firm Certification - CA-0000857 <br />SSR# 1636044.0 <br />Erick Phelps - PE #64598 <br />Christopher E. Durham - PE #76655 <br />EDW <br />• AR4p ��� <br />o.7 55 <br />STATE OF <br />i����•• F�ORIDP.•'•G��� <br />ONAL <br />�flllllll <br />Christopher Edward Durham <br />PE License No. 76655 <br />F I r,\ " <br />u-iKIDACANCER <br />SPEC I 'Research Institute <br />Key Plan <br />MARK ISSUE DATE DESCRIPTION <br />Issue Log <br />CONSTRUCTION <br />DOCUMENTS <br />FLORIDA CANCER SPECIALISTS <br />EQUIPMENT REPLACEMENT <br />38010 MEDICAL CENTER AVE. <br />ZEPHYRHILLS, FL 33540 <br />Drawing Title <br />ELECTRICAL <br />SPECIFICATIONS <br />71604 <br />06/29/2016 <br />Scale <br />Sheet Number <br />E003 <br />Drawn By KIDS <br />Approved By MLG <br />Filename <br />Sa1tCo, LLC 2007 <br />