gir <br />40"T's <br />FURNMON1 <br />I <br />1 <br />I <br />I <br />i <br />I <br />0 NEW WORK PLAN <br />SCALE %" =1'-0" <br />EF-1 <br />EXISTING DUCT SUPPORTS. <br />STRUCTURAL / <br />SEE DETAIL 3 \\\ <br />COLUMN CAP ON SHEET M4.0 \ <br />(TYPICAL) \ <br />/ <br />/ <br />/ <br />/ <br />RTU-1 <br />/ <br />/ <br />SEE DETAIL 4 <br />ON SHEET M4.0 <br />0 FOR ANCHORING <br />I �xi I <br />1 <br />❑ ❑ <br />D D <br />SF-1 <br />OUTSIDE <br />AIR <br />INTAKE <br />E F-4 <br />NEW WORK NOTES: <br />1. ANCHOR ROOFTOP EQUIPMENT AS DETAILED ON SHEET M4.0. <br />2. INSTALL ROOFTOP UNIT OUTSIDE AIR INTAKE AT MINIMUM 3'-0" ABOVE FINSIHED ROOF. <br />3. MAINTAIN OUTSIDE AIR INTAKE A MINIMUM 25'-0" FROM ANY EXHUAST (FAN) OUTLETS. <br />4. MAINTAIN OUTSIDE AIR INTAKES A MINIMUM 25'-0" FROM ANY PLUMBING VENTS. <br />IF VENT OUTLETS ARE ABOVE OUTSIDE AIR INTAKE, MINIMUM DISTANCE CAN BE 10'-0". <br />5. RUN CONDENSATE PIPING TO ROOF DRAIN. ANCHOR CONDENSATE PIPING TO ROOF. <br />6. REFER TO ARCHITECTURAL DRAWINGS FOR ROOFING AND FLASHING DETAILS. <br />Project No. 10003.00 <br />M2.02 <br />$DATE$ $TIME$ $FILEA$ <br />© 2009 BH/PK Architects, Inc. <br />