s <br />Q <br />1 I 2 I 3 1 4 I 5 1 6 1 7 1 8 1 9 1 10 1 11 1 12 1 13 1 14 1 15 1 16 1 17 1 18 <br />19 1 20 <br />Im <br />1 <br />P <br />0 <br />N <br />M <br />L <br />KI <br />J <br />H <br />G <br />FI <br />E <br />D <br />c <br />B <br />AI <br />3 <br />4 <br />6 <br />7 <br />LOUVER SCHEDULE <br />MARK <br />MANUF <br />MODEL <br />LIST SIZE (LAN) <br />CFM <br />MIN FREE <br />AREA <br />MAX VEL <br />ACCESSORIES <br />DESCRIPTION <br />LV-1 <br />GREENHECK <br />ESS-501 D <br />24x12 <br />225 <br />.39 SF <br />700 FPM <br />BIRDSCREEN <br />SIGHTPROOF STATIONARY LOUVER <br />ALL LOUVERS TO HAVE FLANGES. ALL LOUVERS MUST MEET LOCAL WIND REQUIREMENT. <br />EXHAUST FAN SCHEDULE <br />MARK <br />MANUFACTURER <br />MODEL <br />CFM <br />ESP <br />DRIVE <br />PEED/SONES <br />ELEC <br />WATTS <br />DESCRIPTION <br />NOTES <br />EF-1 <br />GREENHECK <br />SP-B110 <br />75 <br />0.5 <br />DIRECT <br />801 / 1.5 <br />120/1/60 <br />80 <br />CEILING EXHAUST FAN <br />1, 2, 3 <br />EF-2 <br />GREENHECK <br />SP-B110 <br />75 <br />0.5 <br />DIRECT <br />801 / 1.5 <br />120/1/60 <br />80 <br />CEILING EXHAUST FAN <br />1, 2, 3 <br />EF-3 I <br />GREENHECK <br />SP-B110 <br />75 <br />l 0.5 <br />DIRECT <br />1 801 / 1.5 <br />1 120/1/60 <br />1 80 <br />CEILING EXHAUST FAN <br />1, 2, 3 <br />ACCEPTABLE MANUFACTURERS ARE: FANTECH, COOK, GREENHECK, AND PENN. <br />NOTES: <br />1 WITH FACTORY MOUNTED SPEED CONTROLS. ADJUST TO MATCH CFM SHOWN. <br />2 PROVIDE BACKDRAFT DAMPER AT FAN OUTLET <br />3 FANS TO BE OPERATED BY LIGHTING MOTION SWITCH, SEE ELECTRICAL PLANS. SET FOR MINIMUM 10 MINUTE DELAY. <br />8 ' 9 <br />10 <br />SET THE THERMOSTAT LOCKOUT OPTION USING THE <br />FOLLOWING PROCEDURE. <br />SET LOCKOUT OPTION #1 (TEMPORARY OCCUPIED / <br />UNOCCUPIED) <br />Proper keypad sequences activate the lockout features. To <br />change the keypad lockout state: <br />1. Enter Installer Setup: press and hold both the Run <br />Schedule and Copy keys until DEG F displays. <br />2. Press Q until KYLCK displays. <br />3. Use the up ♦ or down ♦ key to change the setting. <br />Options are: <br />• 0: No lockout <br />• 1: Lockout all keys except Temporary Occupied, <br />Temporary Not Occupied, up ♦ , down ♦ and(D <br />• 2: Lockout all keys except ( . <br />NOTES: <br />- Options 1 and 2 do not allow adjustments on <br />dehumidification high limit. <br />-- No options lockout special keypresses. See the <br />Special Functions section for details. <br />4. Once the proper option is chosen, exit Installer setup <br />by pressing Run Schedule. <br />5. The display prompts SAVE CFG (save configuration). If <br />you want to save it, use the up ♦ or down ♦ key to <br />change NO to YES before pressing Run Schedule again <br />12 <br />THERMOSTAT HEATING & COOLING SCHEDULE <br />MANUFACTURER: <br />HONEYWELL <br />MODEL: <br />173508 <br />GRANGER PART NUMBER: <br />I 1YMG4 <br />COOLING HEATING <br />OCCUPIED SET POINT 72 DEGREES OCCUPIED SET POINT 70 DEGREES <br />UNOCCUPIED SET POINT 178 DEGREES UNOCCUPIED SET POINT 165 DEGREES <br />OCCUPIED TIMES <br />DAY OF WEEK <br />ON <br />OFF <br />MONDAY-SATURDAY <br />8 AM <br />19745 PM <br />SUNDAY <br />110 AM <br />8:45 PM <br />OCCUPIED TIMES <br />DAY OF WEEK <br />ON <br />OFF <br />MONDAY-SATURDAY <br />8 AM <br />9:45 PM <br />SUNDAY <br />110 AM <br />8:45 PM <br />HOLDAY'S TO BE SCHEDULED <br />AS UNOCCUPIED SET POINT <br />EASTER <br />THANKSGIVING <br />CHRISTMAS <br />APRIL 16 2017 <br />NOVEMBER 23 2017 <br />DECEMBER 25 2017 <br />APRIL 1 2018 <br />NOVEMBER 22 2018 <br />DECEMBER 25 2018 <br />APRIL 21 2019 <br />NOVEMBER 28 2019 <br />DECEMBER 25 2019 <br />APRIL 12 2020 <br />NOVEMBER 26 2020 <br />DECEMBER 25 2020 <br />APRIL 4 2021 <br />NOVEMBER 25 2021 <br />DECEMBER 25 2021 <br />APRIL 17 2022 <br />NOVEMBER 24 2022 <br />DECEMBER 25 2022 <br />APRIL 9 2023 <br />NOVEMBER 23 2023 <br />1 DECEMBER 25 2023 <br />1. THERMOSTATS SUPPLIED BY B.O.S., INSTALLED AND CONNECTED BY CONTRACTOR. <br />2. REPLACE EXISTING THERMOSTATS WITH NEW THERMOSTATS AND INSTALL NEW CABLE TO RTU. <br />3. PROGRAM THERMOSTATS AS INDICATED ON THIS SCHEDULE. <br />4. PROGRAM THERMOSTATS FOR DAYLIGHT SAVINGS TIME, VERIFY DATES FOR EACH YEAR. <br />5. O/A DAMPERS SHALL CLOSE IN UNOCCUPIED MODE. <br />6. PROGRAM LOCKOUT OPTION #1 AS INDICATED AT LEFT. <br />13 <br />14 <br />15 <br />MECHANICAL LEGEND AND NOTES <br />RTU'S ARE EXISTING. REPLACE ALL FILTERS. <br />DUCTWORK IS NEW AND EXISTING. NEW DUCTWORK SHALL BE METAL OR FLEX <br />WITH R-6 INSULATION. INSTALLATION AND MATERIAL SHALL COMPLY WITH ALL <br />ENERGY REQUIREMENTS. <br />INSTALL NEW THERMOSTATS WHERE SHOWN AND CONNECT TO RTU'S. <br />THERMOSTATS SUPPLIED BY B.O.S., INSTALLED AND WIRED BY CONTRACTOR. <br />PROGRAM THERMOSTATS AS SCHEDULED. <br />TRUNK DUCTS MAY BE THE EQUIVALENT RECTANGULAR SIZE. <br />DUCT SMOKE DETECTORS AND TEST / RESET DEVICES ARE SHOWN ON THE FIRE <br />ALARM DRAWINGS. SEE FIRE ALARM DRAWINGS FA101, FA102 AND FA103 FOR <br />REQUIREMENTS AND INSTALLATION. DEVICES ARE SUPPLIED AND INSTALLED BY <br />FIRE ALARM CONTRACTOR. <br />THERMOSTAT. UNIT <br />© <br />CONTROLLED AS INDICATED. <br />INSTALL AT 48" AFF <br />F.D. <br />FIRE DAMPER - SEE DETAIL <br />—�V <br />LOUVER <br />i� <br />DUCT UP <br />DUCT DOWN <br />VOLUME DAMPER <br />i <br />TRANSITION <br />16 <br />CD <br />CEILING DIFFUSER <br />SR <br />SIDEWALL REGISTER <br />CR <br />CEILING REGISTER <br />RG <br />RETURN GRILLE <br />DRG <br />DUCT MTD. RETURN GRILLE <br />SRG <br />SIDEWALL RETURN GRILLE <br />DR <br />DUCT MOUNTED REGISTER <br />EG <br />EXHAUST GRILLE <br />AFF <br />ABOVE FINISHED FLOOR <br />MECHANICAL PLAN N <br />1 /8" = 1 --0" <br />17 <br />18 <br />CONSULTING ENGINEERS, LLC <br />5300 Paylor Lane <br />Sarasota, FL 34240 <br />Tel: 941-748-1319 Fax: 941-361-1221 <br />www.me3-engr.com Sidney@me3-engr.com <br />Designed: BAK ME3 Job No: B17-1166 <br />Checked: BAK Date: 09/29/2017 <br />Drawn: KCC C.O.A.27552 <br />Copyright 2017 ME3 All rights reserved <br />P <br />IN <br />N <br />M <br />L <br />J <br />H <br />G <br />F <br />REV. DESCRIPTION I DATE <br />BID & PERMIT SET E <br />09.29.17 <br />CURRENT ISSUE STATUS: <br />"To the best of the Architect's or <br />Engineer's knowledge, the plans <br />and specifications comply with the <br />applicable minimum building codes <br />and applicable fire safety standards <br />as determined by local authority in <br />accordance with Chapter 553 and <br />663 of Florida Statutes." <br />C D <br />l°�q /l ? <br />Kay C. Clem <br />Florida License # 53270 <br />WBR(IIIIIIII10C <br />ARCHITECTS ENGINEERS <br />8130 Lakewood Main Street Phone: 941-556-0757 <br />Suite 210 Fax: 941-556-0759 <br />Lakewood Ranch, FL 34202 www.wbrcae.com <br />Firm Lic. # AA26001395 & 27389 Douglas W.Whitney AIA <br />BEALLS OUTLET #542 <br />ZEPHYRHILLS <br />PROJECT: 6030 Gall Blvd, Zephyrhills, FL 33542 B <br />MECHANICAL PLAN <br />SHEET TITLE <br />WBRC CAD FILE <br />PROJECT No. 3542XX GRAPHIC SCALE: <br />On � u <br />SCALE: As Indicated I I A <br />PROJECT MANAGER: <br />SHEET No. <br />DRAWN BY: M 101 <br />CHECKED BY: <br />19 20 <br />