ELECTRICAL DEMOLITION PLAN <br />SCALE <br />3/16" = V-0" <br />DEMOLITION NOTES: <br />1. COORDINATION: DRAWINGS ARE TO BE USED ONLY AS A GUIDELINE FOR <br />DEMOLITION. COORDINATE ALL DEMOLITION WORK WITH OTHER TRADES, <br />WITH NEW WORK INDICATED ON CONSTRUCTION PLANS, AND WITH <br />ACTUAL FIELD CONDITIONS. <br />2. LOCKOUT/TAGOUT: VERIFY ALL SOURCES OF ELECTRICAL POWER TO <br />AREA OF WORK ARE DISCONNECTED AND LOCKOUT/TAGOUT <br />PROCEDURES ARE FOLLOWED PER OSHA REQUIREMENTS. <br />3. NOT IN CONTRACT AREAS: LOCATE, IDENTIFY, AND PROTECT ELECTRICAL <br />SERVICES (E.G. POWER, CONTROL, COMMUNICATION, SECURITY, SIGNAL, <br />LIFE SAFETY, AND FIRE ALARM) PASSING THROUGH DEMOLITION AREA <br />AND SERVING OTHER AREAS OUTSIDE THE RENOVATION LIMITS. <br />MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN <br />SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY SERVICE FOR <br />AFFECTED AREAS. <br />4. CONTINUITY OF SERVICE: ANY CIRCUITS FEEDING THROUGH DEVICES OR <br />EQUIPMENT BEING REMOVED, RELOCATED, REWORKED, OR ABANDONED <br />AND SERVING OTHER ELECTRICAL DEVICES, AND/OR EQUIPMENT SHALL <br />BE MAINTAINED BY REWORKING EXISTING WIRING TO RESTORE <br />CONTINUITY OF THE INTERRUPTED CIRCUITS. <br />5. LIFE SAFETY: EXISTING EMERGENCY LIGHTING, EGRESS LIGHTING, AND <br />FIRE ALARM SYSTEM AND NOTIFICATION APPLIANCES SHALL BE <br />SALVAGED, MAINTAINED IN PROPER OPERATION, AND RECONFIGURED AS <br />REQUIRED TO COMPLY WITH APPLICABLE CODES AND STANDARDS FOR <br />EACH PHASE OF CONSTRUCTION. <br />6. CODE VIOLATIONS: NOTIFY ENGINEER UPON DISCOVERY OF ANY <br />EXISTING CODE VIOLATIONS FOR CORRECTIVE ACTIONS. <br />7. EXISTING CIRCUITRY: THE CONTRACTOR MAY REUSE EXISTING <br />CIRCUITRY AS FIELD CONDITIONS PERMIT AND WHERE DESIGN INTENT <br />CAN BE MET. EC SHALL VERIFY THAT TOTAL NEW LOAD DOES NOT <br />EXCEED 80% OF THE BREAKER CONTINUOUS CURRENT RATING. <br />8. COMPLETE REMOVAL: ELECTRICAL EQUIPMENT AND DEVICES SHALL BE <br />REMOVED COMPLETE INCLUDING CONDUIT, WIRE, HANGERS, AND <br />SUPPORTS BACK TO SOURCE. <br />9. PROTECTION BARRIERS: PROTECT ADJACENT MATERIALS INDICATED TO <br />REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS TO KEEP <br />DIRT, DUST, AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS. <br />REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION IS COMPLETE. <br />10. SALVAGE FOR REUSE: EXISTING EQUIPMENT NOTED TO REMAIN OR BE <br />RELOCATED SHALL BE SALVAGED, REPAIRED, AND CLEANED FOR FUTURE <br />USE. REPLACE MISSING HARDWARE OR DAMAGED EQUIPMENT AS <br />REQUIRED. <br />11. STORAGE: CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL, <br />PRESERVATION, STORAGE, AND PROTECTION OF ALL EQUIPMENT AND <br />DEVICES DESIGNATED TO BE REMOVED AND REINSTALLED. EQUIPMENT <br />SHALL BE STORED IN A MANNER TO AVOID DAMAGE UNTIL REINSTALLED. <br />12. OWNER RETENTION: THE CONTRACTOR SHALL REMOVE ALL EQUIPMENT <br />NOT INDICATED TO BE REUSED TO A DESIGNATED LOCATION AT THE <br />PROJECT SITE. AFTER THE EQUIPMENT HAS BEEN ASSEMBLED FOR THE <br />OWNER'S INSPECTION AND POSSIBLE RETENTION, ALL EQUIPMENT NOT <br />TO BE RETAINED BY THE OWNER SHALL BE REMOVED FROM THE SITE BY <br />THE CONTRACTOR. <br />13. PANELBOARD CIRCUIT DIRECTORY: ALL PANELBOARDS SHALL BE <br />FURNISHED WITH REVISED TYPEWRITTEN CIRCUIT DIRECTORY CARDS <br />WITH THE EQUIPMENT AND SPACE SERVED PROPERLY DESIGNATED. <br />EXISTING EQUIPMENT SHALL BE RE -IDENTIFIED AS REQUIRED TO <br />COORDINATE WITH PROPOSED DESIGN. <br />14. SPARED OUT CIRCUITS: BRANCH CIRCUIT BREAKERS MADE SPARE AS A <br />RESULT OF DEMOLITION ACTIVITIES SHALL BE SWITCHED TO THE 'OFF' <br />POSITION AND LABELED AS "SPARE". <br />15. RAISED CEILINGS: WHERE ARCHITECTURAL CEILINGS ARE TO BE RAISED, <br />THE EC SHALL REWORK EXISTING OVERHEAD CONDUIT AND <br />CONDUCTORS, IF ANY, TO ALLOW FOR THE CEILING TO BE RAISED. <br />16. HARD CEILINGS: WHERE NEW HARD CEILING IS TO BE INSTALLED, EC <br />SHALL REWORK AND RELOCATE ALL JUNCTION BOXES OUT FROM ABOVE <br />NEW HARD CEILING. NEW JUNCTION BOX LOCATIONS SHALL BE IN AN <br />ACCESSIBLE AREA ABOVE CEILING. <br />DEMOLITION LEGEND: <br />REFER TO DEMOLITION PLANS FOR ADDITIONAL NOTES AND REQUIREMENTS. <br />(d) SUBSCRIPT DENOTES EXISTING TO BE REMOVED. DISCONNECT AND <br />REMOVE WIRE AND CONDUIT BACK TO SOURCE. MAINTAIN SERVICE TO <br />REMAINING DEVICES. <br />(e) SUBSCRIPT DENOTES EXISTING TO REMAIN. MAINTAIN SERVICE VIA <br />EXISTING CIRCUIT. <br />(r) SUBSCRIPT DENOTES EXISTING TO BE RELOCATED. MATCH EXISTING <br />WIRING AND CONDUIT AND EXTEND TO PROPOSED LOCATION. <br />(er) SUBSCRIPT DENOTES EXISTING DEVICE/FIXTURE TO BE REPLACED IN <br />SAME LOCATION AS EXISTING. DISCONNECT AND REMOVE EXISTING <br />DEVICE/FIXTURE AND MAINTAIN SERVICE VIA EXISTING CIRCUIT. <br />— — — — DASHED LINES INDICATE EXISTING TO BE REMOVED, EXISTING TO BE <br />RELOCATED, OR EXISTING TO BE REPLACED. <br />LIGHT LINES INDICATE EXISTING TO REMAIN. <br />KEYED NOTES: <br />OELECTRICAL DEMOLITION: COORDINATE WITH GENERAL CONTRACTOR AND <br />REFER TO ARCHITECTURAL PLANS FOR DEMOLITION SCOPE. DISCONNECT <br />AND REMOVE EXISTING BRANCH CIRCUIT WIRING AND LOW VOLTAGE TO <br />ACCOMMODATE PROPOSED FLOOR PLAN. <br />OELECTRICAL PANELS: EXISTING ELECTRICAL PANELS AND CONTROL <br />EQUIPMENT TO REMAIN. <br />QEXISTING CEILING GRID AND LIGHT FIXTURES TO BE REMOVED: DISCONNECT <br />AND REMOVE EXISTING INTERIOR LIGHTING IN THIS ROOM/AREA. <br />OEQUIPMENT REMOVAL: EXISTING EQUIPMENT TO BE REMOVED. DISCONNECT <br />EXISITNG BRANCH CIRCUIT CONDUIT AND CONDUCTORS FROM EACH LOAD <br />BACK TO SOURCE. SWITCH EXISTING BRANCH CIRCUIT BREAKER TO "OFF" <br />POSITION AND LABEL AS SPARE. <br />OEXISTING WALK-IN COOLER DOOR TO BE REMOVED: DISCONNECT AND <br />REMOVE EXISTING DOOR LIGHTS. <br />OEXISTING ATM TO BE RELOCATED: REMOVE CONDUIT AND WIRING FROM LOAD <br />BACK TO PREVIOUS SOURCE. <br />OEXISTING HAND DRYER TO BE REMOVED: DISCONNECT AND REMOVE <br />EXISTING HAND DRYER. REMOVE CONDUIT AND WIRE FROM LOAD BACK TO <br />SOURCE. PATCH AND REPAIR SURFACE EFFECTED AREA FROM DEMOLITION. <br />TNOT IN SCOPE OF WORK: <br />UEXISTING AUTOMATIC TANK GAUGE TO BE RELOCATED: REMOVE CONDUIT <br />AND WIRING BACK TO PREVIOUS SOURCE. <br />rn <br />M <br />O <br />0 <br />m <br />ca <br />w <br />a <br />N <br />O <br />g <br />L <br />N <br />w <br />a', <br />W <br />0 <br />z <br />INFINITY ENGINEERING <br />GROUP, LLC <br />1208 East Kennedy Boulevard <br />Suite 230 <br />Tampa, Florida 33602 <br />[p]: 813.434.4770 <br />[fJ: 813.445.4211 <br />www.iegroup.net <br />Cert. of Auth. No. 27889 <br />Client Name and Address <br />1201 OAKFIELD DRIVE, NO. 109 <br />BRANDON, FLORIDA 33509 <br />0111993idgs� <br />�` FL•f I� 77 <br />o <br />0 <br />• 0 7 .0 - •'• .t <br />S OF <br />ate: <br />z <br />CV <br />A <br />ch <br />J <br />� <br />z <br />v7 <br />J <br />O <br />W <br />-� <br />-j <br />O <br />w <br />cc o <br />W <br />J <br />0 <br />m <br />J <br />J <br />y N <br />LO <br />m <br />a� <br />W <br />z <br />a� J <br />W <br />tom_ <br />C <br />L <br />a <br />u� <br />Project No. <br />Sheet <br />140-88.00 <br />E-101 <br />Date <br />05/03/2019 <br />Scale <br />k. AS NOTED <br />