Laserfiche WebLink
D <br />service weight cast iron fittings with compression gasket hub and spigot <br />joints (use in Meat Cutting, Deli and Bakery Areas below floor). <br />2.4.4.3 Vent Piping Option: All vent piping above grade may be copper DWV, <br />with copper drainage fittings, solder as for hot and cold water. <br />2.4.5 Provide field fabricated DWV copper or cast brass traps with an integral clean out at <br />bottom of traps for stainless steel utility sinks, for discharge to a floor sink. <br />2.5. Valves, Stops, Specialties <br />2.5.1 Materials: Valves 2 inch and smaller shall be bronze, screwed ends, Valves 2-1/2 <br />inch and larger shall be iron body bronze mounted 125 lb. ASA flanged, faced and <br />drilled. Bronze castings shall be material meeting ASTM A-126 specification. <br />Furnish union adjacent to all screwed valves and at all connections to equipment. <br />2.5.2 Domestic Hot and Cold Water <br />2.5.2.1 Bronze ball valves 2" and smaller size. <br />Hammond 8301-01 <br />Milwaukee BA-200 <br />NIBCO T590Y <br />2.5.2.2 Iron gate valves 2 1/2" and larger, <br />Crane 461 <br />NIBCO F-619 <br />2.5.3 Steam, I 00 psi or less. <br />2.5.3.1 Steel ball valves 1 1/2" and smaller size. <br />NIBCO T-560-CS-R-25 <br />Milwaukee 20 CCOR <br />2.5.3.2 Iron gate valves 2-3 inch size. <br />NIBCO F-617-0 <br />Milwaukee F2885 <br />Stockham G-623 <br />25.4 Check Valves� <br />2.5.4.1 Silent check valves, sizes 2" and smaller, bronze, center guided. <br />NIBCO T-480 <br />Mueller 101 M-BP <br />2.5.5 Gas Valves� <br />25.5.1 UL Listed gas plug valve with wrench flat operator, min. 250 psi working <br />pressure. <br />Rockwell <br />Milliken 170M <br />Resun CS Series, R1430-CS <br />Dezurik Figure 425 <br />2.5.5.2 LP - liquid valves shall be rated for min. 350 psi working pressure. <br />2.5.6 Interior Hose Bibbs and Stops <br />2.5.6.1 Stops: <br />Eastman Type SM12 or approved equal of all brass construction <br />2.5.6.2 Interior Hose Bibbs: <br />Chicago 4387 Brass 3/4" R.C.P W/Watts No. 8A Vacuum Breaker. <br />2.6. Miscellaneous: <br />2.6.1 Vacuum Breakers: Shall be installed on all fixtures where required. <br />2.6.2 Unions: Malleable iron groundjoint equivalent and similar to Crane 519, up to and <br />including 2 inch. Over 2 inch shall be cast iron flanged with a Garlock 7022 Gasket. <br />2.7. Pipe Insulation: <br />2.7.1 Hot water lines shall be insulated with I inch thick fiberglass pipe insulation. <br />Insulation shall be fiberglass #25 ASJ/SSL or prior approved equal. <br />2.8. Pipe Hangers and Supports� <br />2.8.1 Piping shall be firmly held -in place by hangers, supports and pipe rests, located <br />adjacent to fittings, at each offset or change of direction, at the ends of branches <br />over 5 feet long, at riser pipes and along piping where necessary to prevent sags, <br />bends, or vibration. <br />2.8.2 For supporting PVC, steel, or cast iron piping 6" size and smaller, use Clevis hanger <br />Grinnell Fig. 260, galvanized (MSS - SP69 type 1). <br />2.8.3 For supporting copper tubing 2 1/2" size and smaller, use coated pipe ring hanger <br />Grinnell Fig. 97C (MSS- SP69 type 9). <br />2.8.4 Pipe straps shall be heavy gauge galvanized iron factory fabricated to fit against <br />supporting surface when installed. Makeshift devices are not acceptable. No <br />plumbing tape is allowed. Use insulation shields at each pipe hanger and support. <br />2,8.5 The maximum spacing between hangers or supports measured along the piping shall <br />be per local plumbing code. Where PVC piping is used, hanger spacing shall be 48 <br />in. on center or less. <br />2.9. Roof flashings: All vent and roofdrains shall be flashed by Roofing Contractor with lead <br />flashing furnished by the Plumbing Contractor. Flashing shall turn down 2" into vent pipes. <br />2.10. Dielectric Isolating Couplings: Provide dielectric protection for gas and water main risers <br />inside building. Isolate connections ofcopper and steel pipe with dielectric isolating <br />unions. Acceptable Manufacturers: <br />EPCO <br />W & K Dielectric <br />F.H. Maloney <br />3. Execution <br />3.1. Examination <br />3.1.1 Verify all field dimensions and locations of equipment and fixtures within the layout <br />as established by the General Contractor to insure close, neat fit, with other trades <br />work. <br />3.1.2 Examine all work of others. Notify Architect in writing if any conditions exist <br />which will prevent satisfactory installation of materials or equipment. Start of work <br />without notification indicates acceptance of work in place. <br />3.2. Excavation: <br />3.2.1 Perform excavation for trenches under slab and outside building lines as required for <br />installation. Excavate true to lines and grades shown to achieve adequate fall on <br />drain lines and as needed for refrigeration drainage. <br />3.2.2 Bell holes shall be dug to allow soil pipe to lie fully supported. <br />3.2.3 Rock shall be excavated 3 inches below the laying depth, and the trench shall be <br />backfilled with sand 3 inches deep. <br />3.2.4 Over -excavation shall be added in 12 inch lifts (max) and mechanically compacted. <br />Flooding or puddling not permitted. <br />3.2.5 All piping which will be under walks, planters, arcades, parking lots, concrete or <br />asphalt shall be mechanically compacted in 12 inch lifts (max). <br />3.3 � Interface with Site Utilities- <br />3.3.1 Coordinate with other work. Connect to site supplies and storm drain at 5'-O" <br />demising line, <br />3.3.2 Provide waste connection to site sewer at 5'-O" demising line. Provide grease - <br />bearing waste connection to grease trap and from grease trap to waste line located as <br />shown on the Drawings or otherwise indicated. <br />3.4� Pipe lnstallation� <br />3.4.1 Install horizontal sanitary and drain piping, to a uniform grade of not less than 1/8" <br />per foot, unless otherwise noted. Grease waste shall be installed at minimum 1/4" <br />per foot. <br />3.4.2 Openings in pipes, drains, fitting, apparatus and equipment shall be kept covered or <br />plugged to prevent accumulating obstructions in the piping. <br />3.4.3 Run piping free of traps, sags, bends or other defects, grade and valve for complete <br />drainage and control of the system. <br />3.4.4 All waste, vent and water lines shall be concealed, and all water lines shall be <br />overhead. <br />3.4.5 Maintain headroom and keep passageways clean, offset to maintain the required <br />clearance and conform with architectural and structural features of building. Run <br />parallel and straight with adjacent walls or ceilings to present a uniform appearance. <br />Group long runs together. Run concealed in finished rooms, <br />3.4.6 All rough -ins shall be set exactly to measurements furnished by manufacturer. <br />Batteries of fixtures shall have rough outlets set in straight lines at equal spacing. <br />3.4.7 Flush out all lines to insure that they are clear of obstructions prior to the setting of <br />refrigerated cases. If lines are not clear and a case is set, the Plumbing Contractor <br />shall be responsible for the removal and re -set cost. <br />3.4.8 Water piping shall not be embedded in concrete nor concealed within the floor slab <br />within the building (unless shown on drawings). Isolate copper piping from concrete <br />with tar paper or felt. <br />3.4.9 All piping shall be installed to prevent unusual noise from the flow of water under <br />normal conditions, Install pipe isolators at ring hangers consisting of a metal sheath <br />with end flanges assuring positive retention in the ring hangers. Separate cold lines <br />from hot lines by 6". <br />3.4.10 Provide dirt pockets on low point of vertical gas piping. Install full pipe size drip <br />pockets at low point in change of grade. <br />3.4.11 For refrigeration case drains, stub up a line I" above floor, no hub required. <br />3.4.12 Sleeves for copper or brass piping shall be made of PVC or the same materials as <br />the piping. <br />3.4.13 Annular space between piping and sleeve shall be caulked with oakum ' except, use <br />adequate safing insulation where fire rated assemblies are penetrated. <br />3.5. Pipe, joints, fittings, and connection -installation <br />3.5.1 Cast Iron Soil Pipe: Pack tight with first quality oakum to within I inch of end hub. <br />Fill remaining space with one pouring of molten lead and caulk tight, or make-up <br />with neoprene gaskets. <br />3.5.2 Screwed Piping� Make up with pipe dope, applied only to male thread, Remake <br />leaky joints with new material without use of thread cement or caulking. Paint <br />exposed threads of all pipe with asphaltic paint. <br />3.5.3 Copper Tubing� Solder with 95-5 (no -lead solder) and a noncorrosive flux, except <br />that main piping and all u.g. piping shall be joined with silvalloy copper - <br />phosphorus brazing compound (no -lead). Thoroughly clean inside and outside <br />surfaces with sandpaper or wire brush before assembly. Defective joints shall be <br />dismantled, cleaned, and resoldered. Do not use acid Solder. <br />3.5.4 Copper, brass pipe and chromed, polished or painted connections from fixtures shall <br />show no tool marks. <br />3.5.5 PVC Joints: Clean socket and pipe ends with cleaner recommended by cement <br />manufacturer. Liberally apply solvent cement to both socket and pipe ends. Make up <br />joint firmly. <br />3.5.6 Gas Piping: <br />15.6.1 At each equipment, provide shutoff valve, union, drip leg (minimum four <br />times pipe diameter, capped) and flexible pipe connection. <br />3.5.6.2 Extend gas reliefs and vents to a safe discharge point at least 10 feet above <br />grade, at least 10 feet from any source of ignition, <br />3.5.63 LP gas storage containers shall be secured, protected from damage, and <br />located at least 25 feet from any source of ignition. <br />3.5.7 Springing, bending or forcing of pipe will not be allowed. Use fittings for all offsets <br />or changes in alignment of piping. Center hubs so cast iron or clay pipe will lay <br />straight without pinched joints. <br />3.5.8 Street elbows, bushings, and long screw fittings will not be allowed. <br />3.5.9 Cleanly cut pipe and tubing and remove burrs to full diameter of pipe. Excessive <br />reaming will not be permitted. Remove metal particles from ends of pipe and clear <br />each section of foreign material before assembling, <br />3.5.10 Cut pipe threads to full depth of die and screw up tight to fully engage thread in <br />fitting. Threads to comply with ASA No B 2. 1, and be cut with clean sharp dies. <br />3.5.11 Cleanouts: Cleanouts shall be placed as shown on Drawings, or max. 50' o.c., at <br />bases of stacks, at major changes in direction, and at the ends of all lines that have 2 <br />or more openings going into that line, or as required by code. Cleanouts shall be as <br />indicated on Drawings. If PVC is used include hub adaptor. <br />3.5.12 Provide shut-off valves in access panels to allow shut down of area of fixtures <br />where indicated on Drawings. <br />3.5.13 Install shock absorbers with isolating valves as indicated on the Drawings, <br />3.5.14 The inside of all pipes shall be clean, reamed smooth with no burrs, fins or other <br />obstructions. <br />3.5.15 All drains, including trap under utility sinks, shall be copper with soldered joints <br />unless noted otherwise. <br />3.5.16 No pipe shall be run exposed, unless approved by Publix Representative. <br />3.6. Pipe Insulation <br />3.6.1 Sealed at all joints and seams with adhesive in accordance with insulation <br />manufacturer's recommendations. Pipe supports shall be on the outside of the <br />insulation with saddles of galvanized sheet metal. Saddle length shall be twice the <br />diameter of the pipe, or 6", whichever is greater. <br />3.6.2 Fiberglass seams shall be sealed with factory furnished self sealing lap and butt <br />joints in accordance with manufacturer's recommendation. <br />3.7. Fixture Installation <br />3.7.1 Stub out to the exact location of the fixtures. All stubs shall be set symmetrically <br />with fixture. <br />3.7.2 Install fixtures and trim supplied by Publix or others. Connect to plumbing as <br />required. Finish out and trim fixtures as needed for complete installation. <br />3.7.3 Caulkni& All plumbing fixtures shall be bedded and caulked along joint at walls, <br />and other intersecting surfaces with butyl caulking compound, counter tops and <br />brass shall be caulked with "plumbers putty". <br />17.4 Backing shall be of 2 x 6 pressure treated wood flush with stud face and extending <br />to next stud beyond fixture on each side. Secure as required. <br />3.& Inspection: <br />' <br />-3.8.1 The Work shall be installed under the inspection and with the approval of Flublix' <br />Authorized Representative. <br />3.8.2 Notify the Publix' Representative two days in advance of backfilling, enclosing, or <br />covering all plumbing lines so that he may inspect installation. <br />3.8.3 Do not cover or enclose plumbing until inspection is made and installation is <br />acceptable. Correct deficiencies in installation as directed by Publix' Representative. <br />3.8.4 Notify Inspector as required by local authority when all work is completely installed <br />and tested leak -tight. <br />3.8.5 Do not conceal piping or fixtures until approval has been obtained from inspector. <br />3.9. Tests and Adjustments <br />3.9.1 All soil, waste, and vent piping shall be filled with water to the highest point in each <br />system with all air removed. The lines shall be flushed by removing the test plug. <br />Piping may be tested in sections providing that all portions to be concealed shall be <br />subjected to not less than a 10 ft. head for 24 hours with no leaks. Standpipe <br />installed for head test shall be 2 in. minimum diameter. <br />3.9.2 Sewer piping shall be filled with water to it's highest point. <br />3.9.3 Water piping shall be flushed out, tested at 100 psi for 24 hours with no leaks, and <br />shall be left under pressure of supply main for the balance of the construction <br />period. <br />3.9.4 Plumbing fixtures shall be filled with water and checked for leaks or retarded flow. <br />3.9.5 All flush valves, loose key stops, valves and similar equipment shall be adjusted and <br />balanced to provide for the proper operation of the various systems. <br />3.9.6 Each piece of plumbing equipment and the entire plumbing system shall be adjusted <br />and readjusted as required to insure proper functioning and shall be left in first class <br />operating condition. <br />3.9.7 Gas piping shall be tested at 50 psi air pressure for 24 hours, with no leaks. <br />3.10. Disinfection: <br />3.10.1 Before being placed in service, all water distribution systems shall be flushed clean <br />and disinfected. <br />3.10.2 The method to be followed shall be that prescribed by the Health Authority or Water <br />Purveyor having jurisdiction or, in the absence of a prescribed method, use one of <br />the following procedures: <br />3.10.2.1 AWWA C651. <br />3.10.2.2 AWWA C652. <br />3.10.2.3 SBCCI 1997, Section 610 (paraphrased here): <br />a) The pipe system shall be flushed with clean, potable water until dirty <br />water does not appear at the outlets. <br />b) The system shall be filled with a water/chlorine solution containing at <br />least 50 parts per million of chlorine, valved off, and allowed to stand for <br />(24) hours. Alternately, a solution of 200 parts per million and a standing <br />time of (3) hours may be used. <br />c) Flush the system with clean potable water until the chlorine is purged <br />from the system. <br />d) Repeat the procedure where bacterial contamination remains present <br />in the system. <br />3.11. Cleaning Equipment and Premises: <br />3.1 1.1 Thoroughly clean all parts of fixtures and equipment. exposed parts which are to be <br />painted shall be thoroughly cleaned of foreign matter with grease, oil, soldering <br />flux, etc. removed. <br />3.1 1 .2 Exposed metal work shall be carefully brushed down with steel brushes to remove <br />rust and other spots and touched up with primer. <br />End of Section 15400 <br />Section 15500 <br />Heating, Ventilating, and Air Conditioning (HVAC) <br />1. General <br />1. 1. Summary <br />1.1.1 Provide all materials and equipment and perform all labor required to install HVAC <br />systems complete as indicated, as required by code, and as specified herein. All <br />sizes, etc., are Publix minimum and if local code requirements are higher, the work <br />shall be bid and installed accordingly. <br />1.1.1.1 Obtain and pay for all permits, bonds, inspection. <br />1.1.1.2 Provide roof top and split HVAC systems or install systems provided by <br />Publix as described below. <br />1.1.1.3 All A/C curbs set for drying -in by roofer. <br />I � 1. 1.4 All roof mounted fans will be furnished by Publix and installed by HVAC <br />Contractor. Curbs will be furnished by Publix for installation by roofer. <br />1.1.1.5 Provide hurricane brackets and other supports required to secure units to <br />structure for wind conditions - <br />Hurricane: FM 1-90, or higher if designated by authority having <br />jurisdiction. <br />1.1.1.6 Provide sheet metal duct systems as indicated on Drawings and described <br />in Specifications. <br />1.1.1.7 Provide exhaust ducts between the cooking hoods and the roof mounted <br />exhaust fans. <br />1.1.1.8 Provide double -wall metal gas vents. <br />1. 1. 1 �9 Coordinate HVAC work with all trades involved. <br />1. 1. I � 10 Provide all other materials and services required for a complete working <br />installation described in Contract Documents. <br />1.1.1.11 All removed equipment shall be turned over to the Owner at an area <br />designated by the Owner. All equipment not wanted by the Owner shall <br />be removed from the site and properly disposed of by the contractor. <br />1.1.2 HVAC Equipment: <br />1.1.2.1 All HVAC equipment shall be priced separately and submitted as an Add <br />Alternate. <br />1.1.2.2 If Alternate is not accepted, Publix will provide equipment delivered to <br />the site of Construction, Coordinate delivery schedule with construction <br />progress. Contractor shall be responsible for receiving, unloading, storing <br />and protecting equipment on site. Provide all labor, equipment, materials, <br />and services required for installation and satisfactory completion of <br />HVAC work. <br />1.1.2.3 If Alternate is accepted, in addition to above, provide equipment, delivery, <br />required staging and storage, and all other services required to complete <br />the Work. <br />1.2. Definitions: Explanation and precedence of Documents: <br />1.2.1 For purposes of clarity and legibility, HVAC drawings are essentially diagrammatic <br />and, although size and location of equipment are drawn to scale wherever possible, <br />Contractor shall make use of all Contract Documents. <br />1.2.2 The Drawings indicate size, connection points and routes of ducts and equipment. It <br />is not intended, however, that all offsets, rises and drops are shown. Install all items <br />as required to fit structure, avoid obstructions, and retain clearance, headroom, <br />openings and passageways. <br />1.2.3 Remodels: Carefully examine all existing conditions, existing work in place and <br />premises and compare the Drawings with the existing conditions. Submittal of bid <br />indicates that the Contractor has examined the Site and Drawings and has included <br />all required work in his bid. No allowances will be made for error resulting from <br />Contractor's failure to visit job sites and to review Drawings. <br />1.2.4 Conflicts, discrepancies, interferences and omissions in Documents shall be brought <br />to the attention of the Architect for clarification prior to commencement of work, <br />1.2.5 Information was taken from various archive drawings and limited field observation. <br />Field verification of existing conditions and points of connection are required. <br />Provide all demolition, cutting and patching, and excavation required for the project, <br />whether or not shown on the drawings. <br />1.2.6 The term "provide" shall be defined as furnished and installed complete in every <br />way by the contractor. <br />1.3. Submittals: <br />1.3.1 Within 30 days of Contract Commencement (Authorization to Proceed), submit for <br />publix Architect's approval: <br />Cooling Equipment <br />Air Handling Equipment <br />Heating Equipment <br />Air Distribution <br />Valves, Gauges, Specialties, Thermometers, Misc. <br />Insulation <br />Round and Oval Insulated Duct <br />All submittal data shall have rough -in dimensions, connection sizes, any <br />special installation requirements, certified performance data and <br />horsepower, voltage and phase for all equipment. <br />Equipment, fixtures and trim with cuts including rough -in dimensions, <br />Other items required to complete the work <br />L3.2 Submit six identical bound copies of all items. Arrange categories in order listed <br />above, <br />1.3.3 All cuts for the above shall have rough -in dimensions, connection sizes, and special <br />installation requirements. <br />1.3.4 Project Record Drawings� Comply with Section 01 720. <br />1.3.5 Do not order materials or proceed with the work without approved submittals. <br />1.3.6 Confirm electrical requirements and voltage with Div. 16 Contractor prior to <br />ordering equipment. <br />1.4. Quality: <br />1.4.1 Subcontractor: <br />1.4.1.1 The HVAC Subcontractor shall be a reputable firm regularly engaged in <br />this type of work employing skilled workmen, and with proper equipment. <br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two similar <br />jobs, of comparable size and character, installed and operating within the <br />previous two years prior to Bid Opening. <br />1.4.1.3 Flublix reserves the right to refuse any Subcontractor with or without <br />cause. <br />1.4.2 Personnel: <br />1.4.2.1 Employ an experienced Superintendent to oversee all operation. <br />1.4.2.2 Work shall not proceed without adequate supervision present at all times. <br />1.4.2.3 Work shall be accomplished by workers certified in their trade as masters, <br />journeymen, and apprentices in accordance with regulations of the <br />governing authority or customary practice. Utilize workers with skills in <br />proportion to complexity of tasks required. <br />1.4.2.4 Publix reserves the right to reject personnel with or without cause. <br />1.4.3 Quality standards: Work will be judged in comparison to work of similar types. <br />Substandard construction as judged by Publix Representative will not be accepted- <br />1.4.4 Codes and Standards: <br />1 A.4.1 The entire system and all components specified herein shall meet all <br />applicable national, state, county and local codes, standards and <br />ordinances in every respect. <br />1.4.4.2 The contractor shall meet with the authority having jurisdiction (AHJ) and <br />review the proposed work, prior to commencing the work. Comply with <br />and provide all additional and supplementary requirements of the AHJ. <br />1.4.4.3 Comply with all OSHA requirements for construction safety. All <br />ductwork, piping and equipment lower than 6 ft. - I 0 in. AFF shall be <br />padded and striped per OSHA requirements. <br />1.4.4.4 The following are the codes and standards which the engineer knows to <br />govern the work, <br />a) Standard Mechanical Code, 1997. <br />b) Standard Gas Code, 1997. <br />c) Florida Energy Efficiency Code for Building Construction, 1997. <br />d) NFPA 30, 1996, Flammable and Combustible Liquids Code. <br />e) NFPA 37, Stationary Combustion Engines and Gas Turbines, 1994. <br />f) NFPA 54, National Fuel Gas Code, 1996. <br />g) NFPA 70, National Electric Code, 1996. <br />h) NFPA 90A, Standard for the Installation of Air Conditioning and <br />Ventilating Systems, 1996. <br />i) NFPA 92A, Smoke Control Systems, 1993. <br />j) NFPA 96, Ventilation Control and Fire Protection of Commercial <br />Cooking Operations, 1994. <br />k) NFPA I 0 1, Life Safety Code, 1997. <br />1) NFPA 21 1, Chimneys, Fireplaces, Vents and Solid Fuel -Burning <br />Appliances, 1992. <br />in) ASME/ANSI B31.9, 1992, Building Services Piping. <br />n) SMACNA HVAC Duct Construction Standards, 1985. <br />o) ASHRAE Standard 3, 1996, Reducing Emission of Fully Halogenated <br />CFC Refrigerants in Refrigeration and Air Conditioning Equipment and <br />Applications. <br />p) ASHRA-E Standard 15, 1994, Safety Code for Mechanical <br />Reffigeration. <br />q) ASHRAE Standard 62, 1989, Ventilation for Acceptable Indoor Air <br />Quality. <br />1.4.5 Participate in the pre -construction conference. <br />1.5. Sequencing: <br />1.5.1 Notify General Contractor, or any others, of all chases, sleeves and openings <br />required so that the work can be accomplished without delay. Provide necessary <br />sleeves, etc., to be installed. Other -wise, this Contractor shall pay for appropriate <br />trades to perform cutting and patching. <br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut. <br />1.5.3 Where construction necessitates the routing of ducts or piping through structural <br />members, or framing, permission to make such installation shall first be obtained <br />from the Publix Field Representative <br />1.6. Temporary Operation: The Owner may require operation of part or all of the installation <br />pri or to Final Acceptance. This operation shall not constitute acceptance of the Contractor's <br />work. <br />1.7. The Owner reserves the fight to make emergency repairs as required to keep equipment in <br />operation without voiding the Contractor's guarantee nor relieving the Contractor of his <br />responsibilities during the guarantee period. <br />1.8. Operating Instructions and Service Manual � <br />1.8.1 Provide two (2) neatly bound copies of maintenance and instructions book, pans <br />lists pertaining to all equipment furnished. <br />1.8.2 Each section shall be indexed and include parts lists, instruction books, suppliers' <br />phone numbers and addresses, and individual equipment guarantees all in separate <br />sections. <br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to complete <br />care and operation of the HVAC system. Inform the Architect in writing as to the <br />persons who received the instructions and the date that this was done, <br />1.9. Warranty: <br />1.9.1 All now work, equipment, materials, and systems shall be warranted against all <br />defects for a period of one year after final acceptance by the Owner. <br />1.9.2 Provide five-year compressor replacement warranty. <br />2. Products <br />2.1. Materials <br />2.1.1 All Materials shall be new, full weight, of the best quality with the same brand or <br />manufacturer used for each class of materials or equipment. All similar materials <br />shall be of the same type and manufacturer unless otherwise designated. <br />2.2. Nameplates <br />2.2.1 Nameplates shall not be painted. <br />2.2.2 All switches, starters, and major pieces of equipment shall be identified with black <br />plastic nameplates with engraved white letters. <br />2.3. Controls: <br />2.3.1 An Environmental Control Panel will be furnished by Publix and installed by <br />electrical contractor to control all AC units. Conduit, line voltage circuits, <br />interlocks, etc., shall be furnished and installed by the electrical contractor, as <br />shown on drawings. <br />2.4. Equipment Starl-Up� All rooftop AC units shall be started and adjusted for proper operation <br />by the manufacturer or his representative. No equipment shall be run prior to this start-up. <br />All units shall be made ready for start-up at the same time. Contractor shall have qualified <br />personnel in attendance to coordinate ductwork and electrical aspects of the start-up <br />2.5. Filter Media� Two inch thick pleated non -woven throw -away filters equivalent to FARR <br />30-30 unless noted otherwise on drawings. <br />2.6. Air Distribution <br />2.6.1 General: <br />2.6.1.1 All air distribution shall be supplied by manufacturers maintaining ADC <br />certified laboratories. <br />2.6.1.2 Furnish and install, unless otherwise noted, all grilles, registers, and <br />outlets at the location and of the type and size shown on the Drawings. <br />Install foam rubber gaskets behind flanges of all grilles and registers to <br />prevent leakage and streaking. Insulate backs of diffusers with R-8 <br />fiberglass insulation, cement and mastic vapor barrier. Adjust air volumes <br />and set deflection in accordance with Drawings. <br />2.6.1.3 Prior to requesting a Final Inspection, submit a typed schedule or a <br />marked up set of Drawings indicating the observed velocity of each grille, <br />register or out] et. These test data shall be final readings after balancing the <br />system, <br />2.6.1.4 All dampers shall be in wide open or neutral position prior to test and <br />balance of the system. <br />2.&2 Return Air Grilles and Registers: <br />2.6.2.1 Acceptable Manufacturers: Airguide, Anemostat, Barber Coleman, Metal <br />Industries Inc, Titus, or other prior approved manufacturer. <br />2.6.2.2 Where indicated, provide opposed blade dampers. <br />2.6.2.3 Where required, grilles shall be suitable for smooth surface mounting, <br />holes cut in wood doors by General Contractor and grille installed by <br />HVAC Contractor. <br />2.6.3 Outlets: <br />2.6.3.1 Acceptable Manufacturers: Air guide, Anemostat, Barber Coleman Metal <br />Industries Inc, Titus, or other prior approved manufacturer. <br />2.6.3.2 All supply outlets shall be aluminum or aluminized steel where required <br />when part of rated roof -ceiling assembly. Return air grilles, outlets, <br />registers and door grilles shall be ofetched aluminum with acrylic finish <br />and as indicated. <br />2.6.3.3 Provide steel grilles, fire dampers and radiation dampers as indicated on <br />the Drawings and in accordance with UL. roof -ceiling assembly design <br />where indicated. <br />2.6.3.4 Provide UL listed lay -in ceiling outlets equal to those manufactured by <br />Titus, or prior approved equal, complete with radiation damper and <br />thermal blanket where indicated. <br />2.6.3.5 Variable volume type shall be Titus or prior approved equal, factory <br />insulated, complete with controls, damper, change over thermostat as <br />indicated on the Drawings. <br />2.6.4 Louvers: Aluminum, drainable with bird screen, AMCA certified. <br />Ruskin #ELF-375D <br />Louvers and Dampers Inc. IEL-4-104, ALL Series <br />2.6.5 Steel Diffusers and Grilles: <br />2.6.5.1 Acceptable Manufacturers: Airguide, Anemostat, Barber Coleman, Metal <br />Industries Inc, Titus, or other prior approved manufacturer. <br />2.6.5.2 The finish shall be an Anodic Acrylic and shall conform to the following� <br />Property Test Method Value <br />Bake N/A 20 minutes at 300 deg F <br />Color N/A As specified on drawings (white as <br />default) <br />Salt Spray ASTM B 1 17-90 48 hr. minimum <br />2.7. Sheet Metal Duct Work: All duct and fittings shall be manufactured from galvanized steel <br />of lock forming quality per ASTM A-527. The zinc coating shall be minimum G90 (.90 oz. <br />per sq. ft.) per ASTM A-525. Seams on fittings shall be welded or tacked & sealed. <br />Individual fittings are required, manifolding is not permitted. Comply with SMACNA <br />requirements for duct construction for ventilation and air conditioning systems. <br />2.7.1 Rectangular Duct Work: <br />2.7.1.1 Panels shall be cross broken. (Beaded duct not acceptable.) <br />2.7.1.2 Longitudinal standing seams may be used. <br />2.7.1.3 Comer closures are not required, <br />2.7. 1 A Hangers shall be band iron. <br />2.7.1.5 Elbows shall be as drawn and be double vaned. <br />2.7.1.6 Rectangular branch connections shall be angular type with volume <br />damper, no volume extractor. Round branch connections shall be radiused <br />bell -mouth type with volume damper. <br />2.7.1.7 Inspection plates and test holes are not required. <br />2.7.1.8 Fresh air intake shall be square or rectangular standard. <br />2.7.1.9 Access doors shall be insulated and removable. <br />2.7.L10 Sealer on all joints and all seams. <br />Hardcast Iron Grip Water -Based Duct Sea] ant 601. <br />United McGill, United Duct Sealer. <br />Precision Adhesives PA-2084 Duct Sealant. <br />Fosters 32-50 <br />2.7.1.11 There shall be no sheet metal ducts with gage less than 24, even where <br />permitted by SMACNA. <br />2.7.2 Round and Flat Oval Duct: <br />2.7.2.1 All round and flat -oval duct shall be spiral lockseam, triple fib <br />construction. Longitudinal scam duct is prohibited. <br />2.7.2.2 Substitution of sizes by cross section area or equivalent round formula <br />must have written prior approval, <br />2.7.2.3 Where ductwork is exposed to view, provide mill phosphatized sheet <br />metal for painting. <br />2.7.2.4 Field Joints in Exposed Ductwork: Ductmate industries "Spiralmate <br />Round Duct Connector" and "Ovalmate Flat Oval Duct Connector" or <br />approved equals. Slip -type joints are not permitted in exposed duct. <br />2.7.2.5 Approved Duct Manufacturers: <br />R. V. Money, Inc. - St. Petersburg, Florida <br />United McGill Corp. <br />2.7.3 Ductwork Pressure Classification: <br />2.7.3.1 Unless noted other -wise, construct ductwork according to the following: <br />Constant Volume Systems <br />Supply 2 in. w.c. <br />Return 2 in. w.c. <br />Exhaust 2 in. w.c. <br />Variable Volume Systems <br />Supply 4 in. w.c. <br />Return 2 in. w.c. <br />Exhaust 2 in. w.c. <br />2.8. Flexible Duct and Fittings: <br />2.8.1 Factory insulated on aluminum liner, UL listed Class I Air Duct, STD. 181 and <br />NFPA Bulletin 90A. Insulation shall be nominal 2" blanket fiberglass with <br />reinforced polyester rip -stop vapor barrierjacket. <br />18.2 Maximum length - 8 feet. <br />2.8.3 Approved products: <br />Flexmaster TL-M <br />Insulated Metalflex V-250-UL <br />Thermo -Fin Type A-300 <br />2.8.4 Supports shall be spaced maximum 3 feet, support band min. 2 in. wi& Use <br />Wiremold duct collars and galvanized strap clamps or equal as approved by <br />Architect. <br />2.8.5 Spin in fittings shall be Metal Masters Model NIS 1-6G or equal as approved by <br />Architect. <br />2.9. Duct Leakage Loss: <br />2.9.1 A maximum cfm loss of 2% of the rated capacity of each system is allowed. This <br />leakage will be determined by the test and balance consultant. <br />2.9.2 Loss exceeding 2% shall be corrected by the HVAC Contractor prior to acceptance <br />by Publix. <br />2.10. Grease Hood: Furnished by Publix: <br />2.10.1 Install UL classified range hoods as indicated on the Drawings and in accordance <br />with local code and/or NFPA 96- <br />2.10.2 Chemical Fire Suppression <br />2,10-2.1 This Contractor shal I be responsible to provide a complete NFPA 96 <br />compliant surface stack and hood fire suppression system. <br />2.10.2.2 System shall be a pre-engineered system, by ANSUL or prior approved <br />equivalent <br />2.10.2.3 System shall include automatic ,gas shutoff valve, line size. Furnish valve <br />loose for installation by plumbing contractor. <br />2.10.2.4 Submit detailed shop drawings for the system including list of materials, <br />and dimensioned lay -out drawings certified by the manufacturer. <br />2.10.2.5 This Contractor shall provide field installation of the system including all <br />piping, nozzles, cables, accessories and appurtenances. <br />2.10.2.6 Final field hook-up, start-up, testing and operational certification shall be <br />performed by factory representatives. <br />2. 1 O� 2.7 Upon activation of fire suppression system, the supply fan shall stop, the <br />exhaust fan shall continue to run, the gas valve shall close and the fire <br />alarm system shall receive indication that a fire has occurred in the hood. <br />2.10.2.8 The above sequence shall be verified by testing, in the presence of the <br />Owner's representative. <br />2.1 1. Provide welded 16 ga. galvanized exhaust duct between grease hoods and exhaust fans as <br />indicated on Drawings. <br />2.12. Devices and other miscellaneous items: <br />2.12.1 Dampers: Opposed blade, butterfly type, or splitter, all factory made as indicated. <br />Each shall have a locking quadrant accessible for adjustment, with extension sleeve <br />for duct wrap insulation. Provide balancing dampers at each branch duct <br />connection. <br />2,12.2 Fire dampers shall be rated where indicated and shall be UL listed. <br />2.12.3 Radiation Dampers: UL 555C listed and installed where indicated <br />2.12-4 Piping System for Condensate� Schedule 40 PVC outdoors, ASTM B88 Type M <br />copper DWV indoors. <br />2,13. Insulation: <br />2.13.1 Concealed ITVAC Ductwork: <br />2.13.1.1 Insulate externally with 2" fiberglass duct wrap with all -service jacket <br />vapor barrier. <br />2.13.1.2 Neatly cut and fit insulation to the duct surface with all ductjoints <br />overlapped 2" minimum, secured with outward -clinch staples 4" on center <br />each way. <br />2.13.1.3 On ducts 24" or greater in width the insulation on the underside of the <br />duct shall be secured to the sheet metal surface with Foster's #85-20, or <br />and secured mechanically with sheet metal screws and <br />caps, mechanical fasteners adhered to the duct on not more than <br />18"centers each way- <br />2.13.1.4 All transverse and longitudinal seams, and penetrations of the vapor <br />barrier facing shall be covered with SMACNA rated foil backed tape <br />applied in and sealed with Foster's 430-35, or equal, vapor barrier mastic. <br />2.13.2 Indoor A/C Condensate Piping: <br />' <br />2.13.2.1 Insulate with 3/4" expanded rubber, "Armaflex" or equivalent, selected to <br />fit snugly on the pipe with no voids, glued joints, <br />2.13.2.2 Provide PVC jacketing and fitting covers to exposed segments lower than <br />5 feet above finished floor. <br />2.13.3 Exposed HVAC Ductwork (Mechanical Rooms) <br />2.13.3.1 Insulate externally with 2" fiberglass insulation board with all service <br />jacket vapor barrier <br />2.13.3.2 On ducts 24" or greater in width the insulation on the underside of the <br />duct shall be secured to the sheet metal surface with Foster's #85-20, or <br />equal, adhesive, and secured mechanically with sheet metal screws and <br />caps, mechanical fasteners adhered to the duct on not more than <br />I 8"centers each way. <br />2.13.3.3 All transverse and longitudinal seams, and penetrations of the vapor <br />barrier facing shall be covered with SMACNA rated foil backed tape <br />applied in and sealed with Foster's #30-35, or equal, vapor barrier mastic. <br />2.14� Exhaust Fans <br />2.14.1 Roof Mounted Exhaust Fans <br />2.14.1.1 <br />Fans shall be belt or direct drive, as scheduled, with aluminum centrifugal <br />backward inclined fan wheels. Wheels shall be statically and dynamically <br />balanced. <br />2.14.1.2 <br />Motors shall be thermally protected, heavy duty ball bearing type and be <br />readily accessible for maintenance. Motors and drives shall be mounted <br />on vibration isolators out of the airstream. Fan shafts shall be mounted in <br />permanently sealed, lubricated pillow block ball hearings. <br />2.14.1.3 <br />Provide aluminum birdscreen. For fans not serving grease hoods, provide <br />gravity -operated, parallel -blade backdraft damper. <br />2.14.1.4 <br />Provide roof curb complete with fiber cant strip and wood nailer. Roof <br />curb shall match roof slope in order to mount unit level. For fans serving <br />grease hoods, provide vented curb extension to comply with NFPA 96 <br />exhaust discharge height. <br />2.14.1.5 <br />Provide speed control for direct drive fans except kitchen hood fans. <br />2.14.1.6 <br />Disconnect by Division 16 Contractor. <br />2.14.2 Wall Mounted <br />Exhaust Fans <br />2.14.2.1 <br />Fans shall be direct -drive with aluminum centrifugal backward curved fan <br />wheels. Wheels shall be statically and dynamically balanced. <br />2.14.2.2 <br />Motors shall be thermally protected, isolated from the airstream and be <br />readily accessible for maintenance, Motors and fan wheels shall be <br />mounted on vibration isolators- <br />2.14.2.3 <br />Provide aluminum birdscreen and gravity -operated, parallel -blade <br />backdraft damper. <br />2.14.2.4 <br />Fans shall be furnished with a flanged aluminum grille suitable for <br />mounting on interior of the wall opening where indicated. <br />2.14.2.5 <br />Provide speed control for direct drive fans, <br />2.14.2.6 <br />Disconnect by Division 16 Contractor. <br />2.14.3 Sidewall <br />Propeller Fans � <br />2.14.3.1 <br />Fans shall be direct drive with fabricated aluminum, statically and <br />dynamically balanced propellers, <br />2.14.3.2 <br />Motors shall be thermally protected, permanently lubricated, heavy duty <br />type, and easily accessible for maintenance. - <br />2.14.3.3 <br />Provide gravity -operated backdraft damper, wall housing with guard and <br />weatherhood. <br />2.14.3.4 <br />Provide speed control for direct drive fans. <br />2.14.3.5 <br />Disconnect by Division 16 Contractor. <br />2.14.4 Inline Cabinet <br />Fans <br />2.14.4.1 <br />Fans shall be direct drive with aluminum centrifugal forward curved fan <br />wheels. Wheels shall be statically and dynamically balanced. <br />2.14.4.2 <br />Motors shall be thermally protected, permanently lubricated, heavy duty <br />type, and easily accessible for maintenance. Motors and drives shall be <br />mounted on vibration isolators. <br />2.14.4.3 <br />Provide Round Duct Connector. Provide hooded wall cap as shown on <br />plans. <br />2.14.4.4 <br />Provide speed control for direct drive fans. <br />2.14.4.5 <br />Disconnect by Division 16 Contractor. <br />2.15, Flues and Vents <br />2.15.1 General <br />2.15 � 1. I <br />Flues and vents exposed to the weather shall be appropriately supported <br />and guyed to withstand 100 m.p.h. wind, manufacturer's standard <br />components, <br />2.15.2 Type B Double Wall Gas Vents <br />2.15�2.1 <br />For use on atmospheric gas burners only, <br />2.15.2.2 <br />LTL listed and labeled. <br />2.15.2.3 <br />Fabricationi Double wall with air space, aluminum inner pipe, galvanized <br />steel outer pipe, <br />2.15.2.4 <br />Basis of Design� Selkirk Metalbestos Model RV. <br />2.15.3 Double Wall Metal Flues (Model PS) <br />2.15.3.1 <br />For use with atmospheric or forced draft gas appliances. <br />2.15.3.2 <br />UL listed and labeled. <br />2.15.3.3 <br />Fabrication: Double Wall with I inch minimum air space between walls. <br />Construct innerjacket of 20 gage Type 316 stainless steel. Construct outer <br />jacket of 24 gage aluminized steel, liquid -tight construction. <br />2.153.4 <br />Basis of Design: Selkirk Metalbestos Model PS. <br />2.15.4 Double Wall Oven Vent <br />2.15.4.1 <br />For use on oven heat and steam vent only. <br />2.15.4.2 <br />UL Listed and labeled. <br />2.15.4.3 <br />Fabrication: Double wall with air space, 400 series stainless steel inner <br />pipe, galvanized or aluminized steel outer pipe. <br />2.15.4.4 <br />Basis of Design: Selkirk Metalbestos Model DF. <br />2.15.5 Accessories, <br />UL labeled� <br />2.15.5.1 <br />Ventilated Roof Thimble: Consists of roof penetration, vent flashing with <br />spacers and storm collars. <br />2.155.2 <br />Exit Cone: Consists of inner cone, and outerjacket, to increase stack exit <br />velocity 1. 5 times. <br />2.15.5.3 <br />Stack Cap: Consists of conical rain shield inverted cone for partial rain <br />protection with low flow resistance. <br />2.15.5.4 <br />Vent Dampers: Same size as draft hood collar, constructed of stainless <br />steel or galvanized steel, with corrosion resistant components. <br />2.16. Grease Duct <br />2.16.1 Field Fabricated Ductwork <br />2.16.1.1 <br />Fabricate in accordance with SMACNA HVAC Duct Construction <br />Standards - Metal and Flexible, 1985,and NFPA 96. <br />2.16.1.2 <br />Construct of 16 gage carbon steel or 18 gage stainless steel, using <br />continuous external welded joints. <br />2.16.1.3 <br />Use stainless steel for ductwork exposed to view and stainless steel or <br />carbon steel for ducts where concealed. <br />2.16.1.4 <br />Provide all necessary clean -out provisions whether or not shown on the <br />drawings. Where grease duct is run horizontally, provide full size <br />approved clean -out access doors at each elbow to permit cleaning <br />operations upstream or downstream of each elbow. <br />2.16.2 Factory Built Grease Duct <br />2.16.2.1 <br />Factory -built grease duct shall be laboratory tested and listed by <br />Underwriters Laboratories, Inc., for use with commercial cooking <br />equipment as described in NFPA 96. <br />2.16.2.2 Double wall ducting shall have an outer jacket of aluminum steel .025" <br />thick in 6 inches through 24" diameters and .034" thick for larger <br />diameters. The inner liner shall be type 304 stainless steel with a nominal <br />thickness of.035" for all sizes. <br />2.16.2.2.1 Fiber insulated exhaust system (Model IPS) shall have a fiber <br />insulation between the walls of I inch thick. Provide I inch <br />minimum air space between duct and surrounding <br />noncombustibles. <br />2.16.2.3 Each system shall be designed to provide access to inspection and <br />cleaning at each change of duct direction, permit drainage of grease <br />residue through a duct section, enable the system to allow for the thermal <br />expansion and allow various types of fire suppression equipment to be <br />integrated into the grease ductwork. <br />2.16.2.4 Joints of the inner liner will be sealed using V-Bands and Selkirk <br />Metalbestos High Temperature Ceramic Joint Cement, supplied by the <br />manufacturer. <br />2.16.2.5 Ducts extending above roof surfaces must terminate with fan adaptor and <br />as outlined in local building codes or as required by NFPA 96. <br />2.16.2.6 The system shall be installed as designed by the manufacturer in <br />accordance with NFPA 96 and in accordance with the terms of the <br />manufacturer's 10-year warranty. <br />2.16.2.7 All parts exposed to the outer atmosphere should be protected by a <br />minimum of one base coat and one finish coat of paint, such as series <br />4300 Heat Resistant paint as manufactured by Rustoleum, or equal. Paint <br />shall be supplied and applied by Contractor, <br />3. Execution: <br />3.1. General <br />3.1.1 Make all joints, connections, unions, etc., with proper care to insure that tight <br />connections are made without excess material, well secured to supports. <br />3.1.2 Install duct with runs straight, shop formed radiuses at bends, and adequate <br />supports. <br />3.1.3 Verify all field dimensions and locations of equipment and fixtures within the layout <br />to ensure close, neat fit, with other trades work. <br />3.2. Installation: <br />3.2.1 Installation of rooftop A.C. units: <br />3.2.1.1 Rooftop units shall be provided with factory furnished galvanized steel <br />roof curbs complete with wood nailer strips. Curbs are shipped knocked <br />down for field assembly. Provide materials and coordination with other <br />trades required to ensure that curbs are installed properly. Roof curbs <br />shall match roof slope in order to mount unit level. <br />3.2.1.2 Lift all A/C units with spreader bars to prevent cable damage to cabinets <br />and components. <br />3.2. 1 3 Publix will accept only those units which are in new condition without <br />dents or other damage- Scratches or paint damage are to be re -painted with <br />manufacturer's paint. <br />3.2.1.4 In the event that field repair involves the refrigeration circuit of any unit, <br />such repair is to be made by the unit manufacturer or his representative. <br />3.2.1.5 Provide each unit with a condensate drain trap in accordance with <br />Drawings and unit manufacturer's recommendation. <br />3.2.1.6 Piping of unit mounted heat reclaim coil(s) will be by Publix. <br />3.2.1.7 Provide flexible duct connector at supply and return connection to each <br />ITVAC unit. <br />3.2.2 Although the locations of the equipment and ductwork may be shown on the <br />Drawings in certain positions, the Contractor shall be guided by the architectural <br />details and conditions existing at the job, correlating this work with that of others. <br />3.2.3 'Outside air intakes shall be min. 36" above the finished roof, minimum 10'-O" from <br />any exhaust outlet or vent, and minimum 20'-O" from any flue out] et. <br />3.3. Flues and Vents <br />3.3.1 Install with minimum ofjoints. Align accurately at connections, with internal <br />surfaces smooth. <br />3.3.2 Support in strict accordance with manufacturer's recommendations, industry <br />standard, and SMACNA HVAC Duct Construction Standards - Metal and Flexible, <br />1985. <br />3.3.3 Pitch with positive slope up. <br />3.3.4 Maintain UL listed minimum clearances from combustibles. <br />3.3.5 Assemble pipe and accessories as required for complete installation. <br />3.3.6 Install vent dampers, locating close to draft hood collar. <br />3.3.7 Assemble and install flue and vent sections in accordance with manufacturer's <br />recommendations, industry practices, and in compliance with UL listing. <br />3.3.8 Level and plumb vertical sections. <br />33.9 Clean flues and vents during installation, removing dust and debris. <br />3.3.10 At appliances, provide joints permitting removal of appliances without removal or <br />dismantling of flues or vents. <br />3.4. Grease Ducts <br />3.4.1 Field fabricated ductwork - install in accordance with NFPA 96. Support in <br />accordance with SMACNA HVAC Duct Construction Standards. <br />3.4.2 Factory built grease duct - install and support in accordance with NFPA 96 and <br />manufacturer's instructions. Provide factory built fan adaptor between the roof curb <br />and fan base. <br />3.5. Substantial Completion Inspection <br />3.5.1 All of the following items must be completed prior to Substantial Completion <br />Inspections. No exceptions will be made and no payment will be made until all <br />items are completed. <br />3.5.2 Cleaning Equipment and Premises: <br />3.5.2.1 Thoroughly clean all parts of the apparatus and equipment. Exposed parts <br />which are to be painted shall be thoroughly cleaned of cement, plaster, <br />and other material and all oil and grease spots shall be removed. Repaint <br />or touch up as required to make look like new. Surfaces shall be carefully <br />wiped and all cracks and comers scraped out. <br />3,5.2,2 Exposed metal work shall be carefully brushed down with steel brushes to <br />remove rust and other spots and touched up with primer. <br />3.5.3 Testing and Balancing Systems <br />3.5.3.1 Publix will provide a test and balance contractor. This service will be done <br />in the presence of the HVAC Sub- Contractor, so that deficiencies can be <br />noted. <br />3.5.3.2 Comply with "Standards for Field Measurement and Instrumentations" <br />Form No. 8 1266 Volume One. as published by the Associated Air Balance <br />Council. <br />3.5.3.3 Perform duct leakage testing in accordance with SMACNA HVAC Air <br />Duct Leakage Test Manual, I st Ed., 1985. Complete duct leakage test <br />prior to performing air system balancing procedures. <br />3.5.3.4 Submit three (3) copies of the complete test reports to the Publix <br />Refrigeration Department prior to Final Acceptance of the Project. <br />3.5.3.5 Provide sufficient time before the completion date so that testing and <br />balancing can be accomplished, and remediation made. <br />3.5.3.6 Put all HVAC Equipment into full operation and continue operation <br />during each working day of testing and balancing. <br />3.5.3.7 Implement changes recommended by the testing and balancing contractor, <br />including pulley changes, balancing dampers and other items as required <br />to obtain proper system balance as judged by the testing and balancing <br />contractor and the Publix Architect. <br />3.5.3.8 Maintain operation of the system for a minimum of 24 hours after balance <br />has been obtained. Notify Publix Architect so that he may inspect the <br />system under operating conditions. <br />3.6. Dust streaking on exposed duct systems: After 6 months, examine all exposed ductwork for <br />dust streaking. Where streaking has occurred, the causes of the streaking shall be <br />determined and repaired. Streaked surfaces shall be cleaned and touched up to match the <br />original finish. <br />End of Section 15500 <br />Section 16400 <br />Electrical <br />1. General <br />1. 1. Summary <br />1.1.1 Provide <br />all materials and equipment and perform all labor required to install <br />electrical systems complete as indicated, as required by code, and as specified <br />herein. <br />All sizes, etc., are Publix minimum and if local code requirements are <br />higher, the <br />work shall be provided accordingly. <br />1.1.1.1 <br />Obtain and pay for all permits, bonds, inspection. Coordinate inspections <br />with work as it progresses. <br />LI.L2 <br />Provide services necessary to coordinate work with work of others. <br />Notify concerned parties before proceeding with work that will affect <br />them. <br />1.1.1.3 <br />Provide electric service, as shown on the Drawings, to connect with site <br />utilities at a point outside the building. <br />1.1.1.4 <br />Install all panelboards, and contactors at the locations shown on the <br />Drawings and specified herein. <br />1.1,15 <br />' <br />Furnish and install all conduit and conductors between the load side of the <br />feeder breakers to the breaker panels. <br />1.1.1.6 <br />Furnish and install all secondary circuits between the panelboards and the <br />final terminal as shown on the Drawings and specified herein. <br />1.1.1.7 <br />Receive, store, install and make final electrical connections to all lighting <br />fixtures as shown on the Drawings and specified herein. <br />1.1.1.8 <br />Furnish and install conduit and boxes for the telephone outlets. <br />1.1.1.9 <br />Make electrical connections to the electric door operators as shown on the <br />Drawings and specified herein. <br />1.1.1.10 <br />Make all electrical connections to equipment supplied by Publix. <br />1.1.1.11 Make all electrical connections to refrigerated display cases and walk-in <br />boxes as shown on the Drawings and specified herein. <br />1.1.1.12 Make all electrical connections between the switchboard and the <br />refrigeration compressors and condensing equipment as shown on the <br />Drawings and specified herein. <br />1.1.1.13 Furnish and install all motor starters, disconnect devices, conduit and <br />conductors for control and power wiring. <br />1.1.1.14 Make all electrical connections between the switchboard and the air <br />conditioning compressors, air handling units, package units and strip <br />heaters as shown on the Drawings and specified herein. <br />1.1.1.15 Make all electrical connections between the machine rooms mounted <br />refrigeration equipment and the refrigerated display cases, walk-in <br />freezers and coolers as shown on the Drawings and specified herein. <br />1.1.1.16 Furnish and install all conduit and conductors to totally electrically <br />connect all controls as shown on the Drawings and specified herein. <br />1.1.1.17 Furnish and install all electrical wiring required for the dry chemical fire <br />extinguisher system in the grease exhaust hoods in compliance with <br />NFPA Bulletins # 1 7, #96, and with local codes. <br />1.1.1.18 Furnish and install all electrical wiring devices as shown on the Drawings <br />and specified herein. <br />1. 1. L 19 Furnish and install all conduit, conductors, disconnect devices and flexible <br />metal conduit to completely wire all supply and exhaust fans as shown on <br />the Drawings and specified herein. <br />1.1.1.20 The Electrical Contractor shall properly store and secure all materials <br />firmi shed by Publix and will be held fully responsible and liable for <br />damage and loss. It shall be required that he sign for the materials <br />supplied by Publix. <br />1.1.1.21 Panels for A/C and refrigeration mechanical systems, as furnished <br />internally pre -wired by others, shall be mounted and connected by the <br />Electrical Contractor. Refer to Drawings and Specifications for air <br />conditioning. <br />I � 1. 1.22 Furnish and install all controls for fans installed by others. <br />1.1.1.23 Furnish and install power wiring to each HVAC unit including the safety <br />disconnect switch and other required electrical devices to make the unit <br />operational as shown on the Drawings and specified herein. <br />1.1.1.24 Install and connect air conditioning control panel, energy management <br />system, and transducer panel supplied by Publix, as shown on the <br />Drawings and specified herein. <br />1.1.1.25 Install conduit, conductors and make connections to "Publix" sign, and all <br />other facade signs and under -canopy signs (signs supplied and installed by <br />Publix), as shown on the Drawings and specified herein. <br />1.1.1.26 Burglar and fire alarm systems or combined system, as shown on the <br />Drawings and specified herein� The Contractor shall supply and install <br />conduit, boxes, pull strings as shown on Drawings for devices and control <br />wiring as shown on the Drawings. Specific equipment and complete final <br />hook-up by Publix as noted on Drawings. <br />1.1.2 Related Work by Other Contractors: <br />1.1,2,1 Setting and sealing of all curbs and pitch pockets shall be by Roofing <br />Contractor. (Setting of A/C curb only shall be by A/C Contractor.) <br />1.1.2.2 Setting of water heaters, ovens, kitchen equipment, gondolas, cash <br />registers, air conditioners, exhaust fans, refrigerated cases, meat room <br />equipment, facade signs and other miscellaneous equipment by others. <br />Final electrical connection shall be provided by Electrical Contractor. <br />1.1.2.3 Kitchen Hood Fire Protection System shall be by Others. <br />1.1.3 Publix reserves the right to furnish some items of electrical equipment to the <br />Electrical Contractor. If this is done the Electrical Contractor shall install the <br />equipment and deduct the cost of the equipment from his contract. Cost adjustment <br />will be made by Change Order. <br />1.1.4 All apparatus shall be installed at exact height and locations as shown on the <br />Architectural Drawings, or if not shown, at heights and locations shown on other <br />Drawings or as required by applicable codes and laws. <br />1.1.5 Perform all excavation and backfill required for services, and for all conduit and <br />work inside and outside the building. Cutting of curbs, walks, concrete and paving <br />required for excavation shall be done by appropriate trade. <br />1.1.6 All store cases, coolers, and freezers will be furnished and set in place by Publix. <br />Check Equipment Plan A801 and R- I to verify exact locations. <br />1.2. Definitions: Explanation and Precedence of Documents: <br />1.2.1 For purposes of clarity and legibility, Electrical Drawings are essentially <br />diagrammatic and, although size and location of equipment are drawn to scale <br />wherever possible, Contractor shall make use of all Contract Documents. <br />1.2.2 The Drawings indicate size, connection points and routes of conduit and equipment. <br />It is not intended, however, that all offsets, rises and drops are shown. Install all <br />items as required to fit structure, avoid obstructions, and retain clearance, headroom, <br />openings and passageways. <br />1.2.3 Remodels� Carefully examine all existing conditions, existing work in place and <br />premises and compare the drawings with the existing conditions. Submittalofbid <br />indicates that the Contractor has examined the Site and Drawings and has included <br />all required work in his bid. No allowances will be made for any error resulting <br />from Contractor's failure to visit Job Sites and to review Drawings. <br />1.2.4 Conflicts, discrepancies, interferences and omissions in Documents shall be brought <br />to the attention of the Architect for clanfication prior to commencement of Work. <br />1.3. Submittals <br />1.3.1 Within 30 days of Contract Commencement (Authorization to Proceed), submit for <br />Publix Architect's approval- <br />1.3.1.1 List of materials intended for use in the Project. <br />1.1 1.2 Manufacturer's catalogue cuts of materials intended for use in the Project. <br />1.3.1.3 Copies of licenses of key personnel if requested by Publix. <br />1.3.1.4 Samples of materials if requested by Publix, <br />1.3.1.5 Other items required to complete the Work. <br />1.3.2 Submit six identical bound copies of all items. Arrange categories in order listed <br />above. <br />1.3.3 All cuts for the above shall have rough -in dimensions, connection sizes, and any <br />special installation requirements. In addition, furnish motor horsepower voltage and <br />phase for all equipment. <br />1.3.4 Close Out Documents: <br />1.3.4� 1 Comply with applicable provisions of Section 0 1 720 - Proj ect Record <br />Documents. <br />1.3.4.2 Provide a complete set of manufacturer's warranties and warranty <br />certificates, <br />1.3.4.3 A copy of the final approval from the local building department. <br />1 A. Quality: <br />IAA Subcontractor: <br />1.4.1.1 The Electrical Subcontractor shall be a reputable firm regularly engaged <br />in this type of work, employing skilled workmen, and with proper <br />equipment. <br />1.4. 1 2 Upon request, Subcontractor shall show evidence of at least two similar <br />jobs, of comparable size and character, installed and operating within the <br />previous two years pri or to bid opening. <br />1.4.13 Publix reserves the right to refuse any Subcontractor with or without <br />cause. <br />1.4.2 Personnel <br />1.4.2.1 Employ an experienced superintendent to oversee all operation. <br />1.4.2.2 Work shall not proceed without adequate super -vision present at all times. <br />1.4.2.3 Work shall be accomplished by workers certified in their trade as masters, <br />journeymen, and apprentices in accordance with regulations of the <br />governing authority or customary practice. Utilize workers with skills in <br />proportion to complexity of tasks required. <br />1.4.2.4 Publix reserves the right to reject personnel with or without cause. <br />1.4.3 Quality Standards <br />1.4.3.1 Work shall be accomplished to ensure safety to all personnel during <br />installation and after occupancy. <br />1.4.3.2 Work will be judged by Publix in comparison to work of similar types. <br />Substandard construction as judged by Publix Representative will not be <br />accepted. <br />1.4.3.3 Neatness counts. Make all joints, connections, unions, etc., with proper <br />care to insure that tight connections are made without excess material, <br />well secured to supports. <br />1.433.4 Install conduit with runs straight, accurately formed radiuses at bends, and <br />adequate supports. <br />1.4.4 Regulations: Conform to governing codes, ordinances and regulations of city, <br />county and state having jurisdiction. Where local codes are not applicable, conform <br />to State Electric Code where Project is located. Comply with applicable provisions <br />of the following codes and standards (latest version published unless earlier verions <br />is adopted by governing agencies): <br />All National Fire Protection Association (NFPA) Codes and Standards <br />including the National Electrical Code <br />Local Utility Code <br />Local Building Code <br />Safety Code for Mechanical Refrigeration <br />OSHA - for construction <br />1.4.5 Test the entire system. The solid neutral wire shall be tested for thorough grounding <br />at the service entrance and/or separately derived source through the grounding <br />electrode conductor and grounding electrobe. All hot wiring shall be tested for <br />shorts and grounding. <br />1.4.6 Participate in the Pre -Construction Conference. <br />1.4.7 Substitutions� Comply with Section 01630 - Product Options and Substitutions. In <br />general, substitutions are not allowed. <br />I.S. Sequencing: <br />1.5.1 Notify General Contractor, or any others, of all required chases, sleeves and <br />openings required so that the work can be accomplished without delay, Provide <br />necessary sleeves, etc., to be installed. Otherwise, Electrical Sub -Contractor shall <br />pay for appropriate trades to perform cutting and patching. <br />reverdrup <br />S VERDR UP FACILITIES, INC <br />FLORIDA CORPORATE LICENSE #AA C001291 <br />5750 Major Boulevard, Suite 500, Orlando, FL 32819 <br />(407)903-5001 Fax (407)903-5150 <br />ARCHITECT OF RECORD <br />NAME: FLOYD WILSON MCCOLLUM, JR, AIA <br />REGISTRATION: FLORIDA REG, #AR0016162 <br />DA TE: 02128101 <br />1� <br />/ <br />,)� ' V-4`y-�, <br />I <br />. <br />3 ,3 ) 14 I V071 <br />- ", i L 1" <br />Revision: <br />Date: By- Description: <br />0 <br />V .?� <br />_D <br />I <br />Z) <br />C 0- <br />0 � E <br />ob- <br />Lf ) <br />MAMOO <br />a) <br />%� <br />0 <br />E <br />%� <br />a) <br />=0 <br />I*- <br />M <br />0= <br />IT <br />Ir- <br />Ile <br />D <br />LO <br />W <br />014 <br />CD <br />co <br />co <br />M <br />M <br />- <br />[___ CO CO <br />a_ co <br />a <br />W <br />< <br />a <br />- <br />--Jlv,- <br />_W I_ <br />. <br />W <br />W <br />< <br />> <br />W <br />XCOOLL <br />LU _C0 <br />02:000 <br />< <br />LU <br />0 <br />- <br />=C-O <br />LL (D < ;::- <br />LL - <br />=:) <br />at <br />_J <br />=:) <br />_J <br />LL <br />- <br />� <br />D <br />C,0 J ,:1- <br />0 LLJ LL1 dr) <br />LLJO� <br />4= <br />Cl) <br />�: <br />0 <br />M <br />U) <br />_J <br />i <br />< LU <br />�___ _J = <br /><C/) <br />CF) <br />CV) <br />U <br />LU <br />- <br />_J <br />_J <br />- <br />M: <br />0� LLJ r�:o <br />> <br />< <br />W <br />:) <br />0�--C::)= <br />a_::3,1-a_ <br />Z <br />0 <br />>- <br />X: <br />a <br />Of 3 x LU <br />I <br />O<OLU <br />o <br />�- <br />3: <br />0 <br />C) <br />04 <br />M <br />0- <br />LU <br />0 LL M [--- <br />U) <br />�- <br />F-_ <br />N <br />Key Plan: <br />Scales: <br />Sverdrup Project No.., 22196390 <br />Drawing Title: <br />SPECIFICATIONS <br />Date: 03/12/99 <br />Designed By: RBJ Drawing No.: <br />Drawn BT RM PM9 <br />Checked BY: FWM <br />