0
<br />n
<br />labeled with identification of project, type of tile, etc.
<br />1.1.2 Amount: Five percent of amount installed, but no less than one box of tile.
<br />1.2. Warranties:
<br />1.2. 1 Carpet Type 11: Manufacturer's standard wear/col orfastness I 0 year warranty.
<br />1.2.2 Carpet Type III: Manufacturer's standard 3 year pro -rated warranty,
<br />1.2.3 Installation: I year labor and material against all defects.
<br />2. Products
<br />2.1. Carpet Type I - Not Used.
<br />2.2. Carpet Type 11 for use in areas not subject to wheeled traffic:
<br />2.2.1 Carpet - Roll Goods:
<br />Manufacturer/Distributor: Patcraft Division of Queen, Inc.
<br />Series� 669 Einstein IL
<br />Color- 19420-098 Genius.
<br />Back: Woven polypropylene with anti -microbial agent, lifetime
<br />application
<br />2.2.2 Adhesive: Carpet manufacturer approved non -staining low VOC water base organic
<br />adhesive to provide adhesion without forming a vapor barrier.
<br />2.3. Carpet Type III
<br />Manufacturer/Distributor: The Matworks.
<br />Series: Dreadnaught.
<br />Color: Anthracite.
<br />BacL Moisture dissipating secondary back, with anti -microbial agent:
<br />lifetime application
<br />2.4. Transition Strips (use over existing vinyl tile, terrazzo, or concrete, and where carpet is used
<br />over new terrazzo) �
<br />2.4.1 Aluminum Base Extrusion designed to be fastened to floor with a channel to
<br />receive transition strip.
<br />2.4.2 Transition Strip: 3 1/2" (nom) width tapered to provide gradual change in thickness.
<br />Manufacturer: Gradus
<br />Series: RT84 with A-FT45 base
<br />3. Execution
<br />3.1. General: All applicators and field personnel shall be fully trained and familiar with
<br />manufacturers' application procedures.
<br />3.2. Tile Installation
<br />3.2.1 Design layout of tiles so that the edges abutting walls, equipment, etc, are formed
<br />with pieces large enough to prevent them being easily dislodged. At transition strips,
<br />provide first course of whole tiles abutting strip.
<br />3.2.2 Install tile with embossed arrows running in one direction only.
<br />3.23 Fit around all cases and other permanently installed fixtures. Trim tiles for tight
<br />installation,
<br />3.3. Roll Goods
<br />3
<br />3.3.1 Design layout to minimize seams, where spaces are less than the width of the roll,
<br />provide seamless installation.
<br />3.3.2 Glue down directly to slab, following carpet manufacturer's recommendations.
<br />End of Section 09680 1
<br />Section 09725
<br />Seamless Methyl Methacrylate Flooring
<br />1. General
<br />1. 1. Scope:
<br />1.1.1 Provide Seam I ess/Quartz[Fl ake Flooring System at locations indicated.
<br />1.1.2 Provide system in compliance with requirements of United States Department of
<br />Agriculture (USDA), Food and Drug Administration (FDA), and local Health
<br />Department.
<br />1.2. Job Conditions:
<br />1.2.1 Do not begin application until roofing operations have been completed.
<br />1.2.2 Set floor drains at concrete grade rather than finished grade of flooring system.
<br />1.2.3 Substrate� Applicator shall verify slab meets flooring system manufacturer's
<br />standards of slab quality. Notify Publix Architect if deficiencies exist before work is
<br />started.
<br />1.2.4 Preparation of substrate for application of Seamless Quartz Flooring shall constitute
<br />evidence of acceptance of slab.
<br />1.2.5 Conform to flooring system manufacturer's requirements for environmental
<br />conditions
<br />1.2.6 Protection of installed work shall begin immediately upon completion of each part.
<br />Do not allow materials which can mar or stain to come into contact with floor.
<br />Protect floor from wheeled traffic and other activities which might cause permanent
<br />damage.
<br />1.2.7 Clean floor daily. .
<br />1.3. Tests: Perform flooring manufacturer's standard bond test.
<br />1.4. Qualityi
<br />1.4.1 Applicator:
<br />1.4.1.1 Applicator shall be approved by Publix Architect, and the flooring system
<br />manufacturer.
<br />1.4. 1 2 Applicator shall have been trained by the flooring system manufacturer in
<br />all phases of surface preparation and application of the product specified.
<br />1.4.1.3 Applicator shall have five years experience in use of required equipment
<br />and application of specified flooring system. Submit proof of experience
<br />in work of similar scope before the bid. .
<br />1.4.1.4 Publix reserves the right to refuse any applicator with or without cause.
<br />1.4.1.5 Approved applicators�
<br />Nightengale Resurfacing, Palm Beach Gardens, Florida
<br />Federal Technical Services, Marietta, Georgia.
<br />Surface Systems, Greer, South Carolina.
<br />Dura Bond Company, Miami, Florida.
<br />PremUS, Winter Garden, Florida.
<br />1.4.2 Personnel:
<br />1.4.2.1 Employ an experienced superintendent trained by the system
<br />manufacturer to oversee all operation.
<br />1.4.2.2 Work shall not proceed without adequate supervision present at all times.
<br />1.4.2.3 Utilize workers with skills in proportion to complexity of tasks required.
<br />1.4.2.4 Publix reserves the right to reject personnel with or without cause.
<br />1.4.3 Quality Standards
<br />1.4.3.1 Work will be judged by Publix in comparison to work of similar types.
<br />1.4.3.2 Substandard construction as judged by Publix Representative or Flooring
<br />System Manufacturer's Representative will not be accepted.
<br />1.4.3.3 Neatness counts. Make all joints with proper care to insure that tight
<br />connections are made without excess material, well bonded to substrate.
<br />1.4.4 Sample � Prepare system mock-up composed of F-0" square floor sample with wall
<br />base sample applied to indicate system characteristics as follows:
<br />Color
<br />Application thickness
<br />Exposure of abrasive aggregate
<br />Typical cove base treatment
<br />1.5. Warranty: All seamless quartz flooring and wall base work against defects in material and
<br />workmanship for a period of two years. Work found to be defective during that time shall
<br />be replaced at no cost to the Owner. A written warranty shall be provided.
<br />2. Products
<br />2.1. Approved Manufacturer: Silikat Resin Systems, Waterbury, CT. Products of other
<br />manufacturers shall not be used in this system.
<br />2.2. Materials: Methyl Methacrylate (MMA) Acrylic Resin System components:
<br />2.2.1 Penetrating saturating primer/sealer coat - R-41 Primer.
<br />2.2.2 Flake broadcast system (SQ-2):
<br />Self -leveling topping - R61 SL, color P7.
<br />Colorless resin topcoat - R71 sealer,
<br />18% No. I Eggshell White
<br />3.5% No. 6 Silver Grey
<br />54% No. 63 Khaki
<br />3.5% No. 66 Grey
<br />3.5% No. 65 Light Grey
<br />3.5% No. 67 Winter Grey
<br />14% No. 16 Battleship Grey
<br />2.2.3 Colorless resin topcoat - R712 sealer.
<br />2.3. Mixes Follow manufacturer's prescribed procedures exactly.
<br />3. Execution
<br />3A. Preparation
<br />3. 1. I Protect all work in place by draping or masking as required, Provide protection for
<br />all adjacent surfaces.
<br />3.1.2 Mechanical surface preparation-
<br />3.1.2.1
<br />Shot blast all surfaces to receive flooring system with a mobile steelshot,
<br />dust recycling machine (Blastrac or equal).
<br />3.1.2.2
<br />Where surfaces are inaccessible to shot blast machines, utilize other
<br />equipment to achieve equivalent surface.
<br />3.1.2.3
<br />All surface and embedded accumulations of paint, toppings, hardened
<br />concrete layers, laitance, power trowel finishes, and other similar surface
<br />characteristics shall be completely removed leaving a bare concrete
<br />surface having a profile similar to 40 grit sandpaper and exposing the
<br />upper fascia of concrete aggregate.
<br />3.1.2.4
<br />Floor areas inaccessible to the mobile blast cleaning machines shall be
<br />mechanically abraded to the same degree of cleanliness, soundness, and
<br />profile using vertical disc scarifiers, needle guns, or other suitable
<br />equipment.
<br />31.1.15
<br />Remove all spent abrasive, laitance, and other debris with vacuum.
<br />3.1.2.6
<br />As surface preparation proceeds, perform flooring system manufacturer's
<br />specified bond test.
<br />3.2. Application:
<br />3.2.1 Follow manufacturer's instructions for each step.
<br />3.2.2 Apply primer/scaler.
<br />3.2.3 Apply topping and broadcast colored flakes on the surface of fresh material.
<br />3.2.4 Apply topcoat.
<br />3. 2.5 Sand surface with 20 mesh open grit sandpaper if required.
<br />3.2.6 Apply another topcoat.
<br />3.2.7 Cure 45-60 minutes between coats.
<br />3.3. Thickness: Total system thickness shall equal approximately 3/16".
<br />3.4. Cleaning and Protection: Take necessary steps to keep work in place clean and free from
<br />damage by ongoing construction activity. Repair defects as required, using flooring system
<br />manufacturer's recommended procedures.
<br />End of Section 09725
<br />Section 09900
<br />Paint and Wall Finishes
<br />1. General
<br />1. 1. Factory and shop applied painting: Apply as specified in sections governing the item
<br />required.
<br />1.2. Field Painting�
<br />1.2.1 Generally, paint all visible surfaces of all items both interior and exterior, and where
<br />needed for protection of materials from moisture damage.
<br />1-2.2 Apply single coat of primer or wall paint on surfaces subject to accumulation of dust
<br />and dirt; that is, door tops and other places where appearance is not critical.
<br />1.23 Interiors: Unless otherwise indicated back room areas shall receive a gloss finish.
<br />All other areas are to receive a flat finish.
<br />1.2.4 Exposed structure in back rooms shall be painted in 51.x Prototypes only.
<br />1.2.5 Where there is no indication for specific selections, match color and gloss of
<br />adjacent finishes, using coatings of the type recommended by the coating
<br />manufacturer.
<br />1.2.6 Interior and exterior materials:
<br />Concrete
<br />Portland cement plaster
<br />Masonry
<br />Woodwork (includes back -priming all wood siding, and interiors of
<br />millwork).
<br />Gypsum wallboard
<br />Steel and other ferrous metals including galvanized.
<br />1.2.7 Specifically excluded from field painting�
<br />Where concealed by ceiling: Structural steel, steel joist girders andjoists,
<br />metal roof deck, and interior electrical and mechanical work
<br />Concrete walks ' if remodeling work requires reconditioning of previously
<br />painted walks notify Architect.
<br />1.2.8 Materials and equipment not to be painted.
<br />Items of equipment furnished with complete factory finish, except for
<br />items specified to be given a finish coat under this Section.
<br />Non-ferrous metals, except for items specified and/or indicated to be
<br />painted.
<br />Prefinished sheet metal.
<br />Finished hardware, excepting hardware that is factory primed,
<br />Electrical panels.
<br />1.2.9 Surfaces not to be painted shall be left completely free of droppings, overspray and
<br />other accidentally applied materials resulting from painting work.
<br />1.3. Paint Materials:
<br />1.3.1 Deliver all paint, varnishes, enamels, lacquers, stains and similar materials in the
<br />original containers with the seals unbroken and labels intact and with the
<br />manufacturer's instructions printed thereon.
<br />1.3.2 Paint shall arrive on the job color -mixed except for tinting of undercoats and
<br />thinning. All thinning and tinting materials shall be as recommended by the
<br />manufacturer for the Particular material to be thinned or tinted.
<br />1.3.3 All mixed colors shall match the color selection made by the Architect. Verify prior
<br />to application of the coating.
<br />1.4. Storage of Materials:
<br />1.4.1 Store all materials used on thejob in a single place designated by the General
<br />Superintendent or Architect.
<br />1.4.2 Keep storage areas clean and free of debris. Take special care to remove all items
<br />which present danger of fire daily.
<br />1.4.3 Do not store materials in walk-in coolers and freezers.
<br />1.5. Inspection of Surfaces:
<br />1.5.1 Examine surfaces carefully before starting. Note defects which are not reparable by
<br />ordinary means. Work shall not proceed until such damages are corrected.
<br />1.5.2 Commencement of work in a specific area will be construed as acceptance of the
<br />substrate,
<br />1.6. Job Conditions
<br />1.6.1 Before painting is started in any area, broom clean and remove dust.
<br />1.6.2 Until paint is fully dry, broom cleaning will not be allowed; use commercial vacuum
<br />cleaning equipment.
<br />1.6.3 Provide adequate illumination forjudging colors and finish quality in areas where
<br />painting operations are proceeding.
<br />1.7. Cooperation with other trades: Schedule painting work with other trades. Do not proceed
<br />until all affected work is in place, and, where required, protected from painting operations.
<br />2. Products
<br />2.1. Manufacturer: Only Sher -win Williams products will be acceptable. If a product is needed
<br />which is not produced by Sherwin Williams, notify Publix Architect.
<br />3. Execution
<br />3.1. Workmanship, General:
<br />3.1.1 Only skilled mechanics shall be employed. Apply by brush and roller. Spray
<br />painting will be allowed for steel joist girders,joists, steel deck, and electrical and �
<br />mechanical work which is 13 or more feet above the floor.
<br />3.1.2 Protect work in place at all times, and protect all adjacent work and materials by
<br />suitable means.
<br />3.1.3 In remodeling operations, where electrical panels were previously painted, paint to
<br />match surrounding wall.
<br />3.1.4 All materials shall be applied under adequate illumination. Evenly spread and
<br />smoothly flow on to avoid runs, sags, holidays, brush marks, air bubbles and
<br />excessive roller stipple.
<br />3.1.5 Provide complete coverage and hide. Where color, stain, dirt, or undercoats show
<br />through final coat of paint, the surface shall be covered by additional coats until the
<br />paint film is of uniform finish, color, appearance and coverage.
<br />3.1.6 All coats shall be dry to manufacturers recommendations before applying
<br />succeeding coats.
<br />3.1.7 Wood surfaces to be stained shall appear uniform in shading with color variations
<br />caused only by the natural wood grain.
<br />12. Preparation of Surfaces:
<br />3.2.1 Surfaces shall be clean, dry and adequately protected from dampness.
<br />1
<br />3.2.2 Surface shall be free of foreign materials which will adversely affect adhesion or
<br />appearance of applied coating.
<br />3.2.3 Mildew shall be removed and the surface treated in accordance with the coating
<br />manufacturers recommendations.
<br />3.2.4 Wood-
<br />3.2.4.1 Sand to smooth and even surface, then dust off.
<br />3.2.4.2 Apply pigmented shellac to all knots, pitch and resinous sapwood prior to
<br />application of specified primer coats.
<br />3.2.4 � 3 After priming coat has dried, putty or spackle all nail holes, cracks, open
<br />joints and other defects. Putty shall be colored to match primer, if putty is
<br />not compatible with finish, spot prime puttied areas.
<br />3.2.5 Drywall: Fill all minor irregularities with spackling paste and sand to a smooth level
<br />surface. Exercise care to avoid raising nap of paper.
<br />3.2.6 Concrete, Masonry and Stucco
<br />3.16.1 Patch large openings and holes and finish flush with adjacent surface.
<br />After priming, fill remaining small holes with prepared patching material,
<br />3.2.6.2 Remove form oil from poured -in -place concrete with form oil solvent, or
<br />other operations as required for complete removal.
<br />3.2.6.3 Do not paint until surfaces have cured for 28 days and are dry.
<br />3.2.7 Ferrous metal surfaces
<br />3.2.7.1 Remove dirt and grease with mineral spirits and wipe dry with clean
<br />cloths.
<br />3.2.T2 Remove rust, mill scale and defective paint down to sound surfaces or
<br />bare metal using scraper, sandpaper or wire brush as necessary.
<br />3 � 2.7.3 Touch up all bare metal and damaged shop coats with specified shop coat
<br />primer.
<br />3.2.8 Galvanized metal surfaces: Remove dirt and grease with mineral spirits and wipe
<br />dry with clean cloths.
<br />3.2.9 Existing surfaces to be repainted (when and where applicable)
<br />3.2.9.1 Where existing work is cut, patched, or added to, all new surfaces shall be
<br />painted or touched up to match existing work as closely as possible.
<br />3.2.9.2 Existing work, where scheduled for repainting or where damaged by work
<br />of this Contract, shall be repaired and scraped or sanded to provide good
<br />adhesion for paint. Paint to match similar new work or existing work as
<br />appropriate.
<br />3.3. Workmanship for Exterior Painting
<br />3.3.1 Follow manufacturer's recommendations forjob conditions and surface preparation.
<br />3.3.2 Do not proceed with painting work when the surface temperature is below 50
<br />degrees F., while the surface is damp, or during rainy or frosty weather. Avoid
<br />painting surfaces while they are exposed to hot sun.
<br />3.3.3 Exterior doors shall have tops, bottoms, and side edges finished the same as the
<br />exterior faces of these doors.
<br />3.4. Workmanship for Interior Painting
<br />3.4.1 Enamel or varnish finish applied to wood or metal shall be sanded with fine
<br />sandpaper and then cleaned between coats to produce an even surface.
<br />3.4.2 Interior doors shall be sealed on the tops and bottoms with the prime coat only. Side
<br />edges of interior doors shall be finished as faces of these doors.
<br />3.4.3 All closet interiors shall be finished the same as adjoining rooms, unless other -wise
<br />specified.
<br />3.5. Caulking
<br />3.5.1 Caulk between exposed masonry and steel frames. Caulk as required to close all
<br />mortarjoints.
<br />3.5.2 Joints and spaces to be caulked shall be clean and dry. Leave surfaces neat and
<br />clean. Caulk before final painting.
<br />3.6. Clean -Up:
<br />3.6.1 Upon completion of the work, remove all paint and varnish spots from floors, glass
<br />and other surfaces.
<br />3.6.2 Remove from the premises all rubbish and accumulated debris.
<br />3.6.3 Leave work in clean, orderly and acceptable condition.
<br />4. Schedules
<br />4.1. Exterior Paint Schedule
<br />4.1.1 Where Exterior Wallis not to receive portland cement plaster:
<br />Ist Coat - Sherwin Williams Heavy Duty Block Filler - B42W46
<br />2nd and 3rd Coats - Sherwin Williams A-100 Satin Latex House and
<br />Trim.
<br />Color� Outside color as selected by Shopping Center Architect and
<br />approved by Publix' Architect.
<br />4.1.2 Where store receives rear or side exterior portland cement plaster: See Section
<br />09220 - Lath and Portland Cement Plaster, color as selected by Shopping Center
<br />Architect and approved by Publix' Architect.
<br />4.1.3 Exterior Ferrous Metal (not aluminum or shop painted)�
<br />I st Coat on Non -Galvanized -Sherwin Williams Extend Metal Primer -
<br />E41
<br />Ist Coat on Galvanized - Sherwin-Williams DTM Bonding Primer.
<br />2nd Coat - Sherwin Williams DTM Semi -gloss Enamel.
<br />Color as indicated, or if not indicated, as selected by Publix Architect.
<br />4.1.4 Exterior Doors and Jamb s �
<br />I st Coat - Sherwin Williams DIM Bonding Primer.
<br />2nd and 3rd Coat - Sherwin Williams DTNI Semi -gloss Enamel B66
<br />Series.
<br />Outside color as selected by Shopping Center Architect and approved by
<br />Publix' Architect-, inside color as specified in interior paint paragraphs.
<br />4.2, Interior Paint Schedule
<br />4.2.1 Concrete Masonry (Back Rooms)
<br />I st Coat - Sherwin Williams ProMar Block Filler B25W25.
<br />2nd and 3rd Coats - Sherwin Williams Healthspec Semi -Gloss.
<br />Color: SW #1234 "Evening Shadow" (Gray) unless indicated otherwise.
<br />4.2.2 Concrete Masonry with Epoxy where indicated
<br />I st Coat - Sherwin Williams AB25W25 Block Filler.
<br />2nd and 3rd Coats - Sherwin Williams Tile -Clad HS Epoxy B62WZ
<br />Series.
<br />Color: White.
<br />4.2.3 Gypsum Wallboard (General):
<br />I st Coat: Sherwin Williams Promar 400 Flat.
<br />2nd and 3rd Coats: Sher -win Williams HealthSpec Semi -Gloss.
<br />Color: SW 1004 "Pure White" unless indicated otherwise.
<br />4.2.4 Gypsum Wallboard in Backrooms, Customer Service, Front Offices, Cash Room,
<br />General Office and Managers Offices, Restroorn Ceilings (where indicated as
<br />painted)�
<br />I st Coat: Sherwin Williams Promar 400 Flat.
<br />2nd and 3rd Coats: Sherwin Williams HealthSpec Semi -Gloss.
<br />Color� SW #1234 "Evening Shadow" (Gray) unless indicated otherwise.
<br />4.2.5 Gypsum Wallboard behind Refrigerated Cases
<br />One Coat - Sherwin Williams Healthspec Interior Semi -Gloss Enamel.
<br />4.2.6 Plywood, Wood Shelving, Wood Base:
<br />I st Coat - Sherwin Williams DTM Bonding Primer B66,
<br />2nd and 3rd Coats - Sherwin Williams Healthspec Semi -Gloss Enamel.
<br />Color: SW 41234 "Evening Shadow" (Gray) unless indicated otherwise.
<br />4.2.7 Plenum Areas (In Bakery, around hoods, oven & supply or exhaust curtain walls
<br />where other finish is not indicated.)
<br />I st Coat - Sherwin Williams Promar 400 Flat.
<br />2nd and 3rd Coats - Sherwin Williams Healthspec Semi -Gloss Enamel.
<br />Color: SW 41004 "Ultra White" unless indicated otherwise.
<br />4.2.8 Interior Exposed Metal (brush application -all metals except as allowed in spray
<br />applications listed below):
<br />I st Coat (Bare Steel) - Permatex Extend Waterborne Primer 475448.
<br />I st Coat (Factory Primed) - Sherwin Williams DTM Bonding Primer.
<br />2nd and 3rd Coats - Sherwin Williams DTM Semi -Gloss Enamel.
<br />Color: To match adjacent wall.
<br />4.2.9 Structural steel in place, steel joist girders and joists, steel deck, electrical and
<br />mechanical work (spray application - allowed over 13 ft. AFF only). Paint structure
<br />in back rooms of prototypes where visible from sales area only.
<br />I st and 2nd Coat - Sherwin Williams Super Save Lite Dry Fall Semi -
<br />Gloss, #B47W62; Color: Brilliant White
<br />4.2.10 Filters
<br />Paintable Caulk And Sealants - Sherwin Williams 4C-950 Acrylic
<br />Caulking.
<br />Spackling Compounds - Sher -win Williams #C-50.
<br />All spackling shall be done after prime coat is applied.
<br />End of Section 09900
<br />Section 10170
<br />Plastic Toilet Compartments
<br />1. General
<br />1. 1. Submittals: Submit Shop Drawings showing plans, elevations, and attachment and
<br />hardware details.
<br />2. Products
<br />2.1. Partitions: Toilet Partitions shall be I" thick solid polymer resin, of the manufacturer's
<br />standard white color,
<br />2.2. Manufacturers
<br />Santana Products Co., Scranton, PA, (Poly -Mar HD Solid)
<br />Capital Partitions, Inc., Columbia, MD, (Poly -Pro Polymer)
<br />Comtec Industries, Scranton, PA
<br />2.3. Constr-uction: Partitions shall be I" thick ' all edges shall be machined to a radius of 0,250"
<br />and all sharp corners removed. All dividing panels and doors shall be 55" high mounted 14"
<br />A.F.F., or 58" high mounted 12" A.F.F.
<br />2.4. Hardware:
<br />2.4.1 Wall Brackets: Continuous full -panel-I ength extruded aluminum, brite anodized.
<br />2.4.2 Head Rails: Extruded aluminum, brite anodized.
<br />2.4.3 Pilaster Shoes: 20 ga stainless steel,
<br />2.4.4 Hinges: Integral w/nylon & stainless pins, or 8-inch aluminum, brite anodized.
<br />2.4.5 Latches: Aluminum, brite anodized.
<br />2.4.6 Strikes: Aluminum, brite anodized.
<br />2.4.7 Bumper/Hooks: Heavy chrome plated zamac.
<br />2.4.8 Pull (accessible stall only): Heavy duty chrome plated zamac.
<br />3. Execution
<br />3.1. Installation: Installation shall be in accordance with approved drawings and manufacturer's
<br />standard recommendations.
<br />End of Section 10170
<br />Section 10522
<br />Fire Extinguishers, Cabinets, and Accessories
<br />1. General
<br />1. 1. Related Documents
<br />1.1.1 Drawings and general provisions of the Contract,including General and
<br />Supplementary Conditions and Division I Specification Sections, apply to this
<br />Section.
<br />1.2. Summary
<br />1.2.1 This Section includes the followin&
<br />1.2. 1 � I Fire extinguishers.
<br />1.2.1.2 Fire extinguisher mounting brackets.
<br />1.2.2 Related Sections: The following Sections contain requirements that relate to this
<br />Section:
<br />1.2.2.1 Division 15 Section "Standpipe and Sprinkler Systems" for fire protection
<br />standpipe and hose systems.
<br />1.2.2.2 Division 16 Section "Interior Lialuina" for fire exting . uisher location
<br />lights.
<br />1 3. Submittals
<br />1.3.1 General� Submit the following according to the Conditions of the Contract and
<br />Division I Specification Sections.
<br />1.3.2 Product data for mounting brackets, details showing mounting methods,
<br />relationships of brackets to surrounding construction.
<br />1.3.3 Samples for initial selection purposes in the form of manufacturer's color charts
<br />consisting of actual units or sections of units showing full range of colors, textures,
<br />and patterns available for each type of bracket finish indicated or exposed to view.
<br />1.3.4 Samples for verification purposes in full-size units of each type of bracket finish
<br />indicated, and in sets for each color, texture, and pattern specified, showing the full
<br />range of variations.
<br />1.4. Quality Assurance
<br />1.4.1 Single -Source Responsibility: Obtain extinguishers and brackets from one source
<br />from a single manufacturer.
<br />1.4,2 Coordination Verify that brackets are sized to accommodate type and capacity of
<br />extinguishers indicated and provided by Owner under separate Contract.
<br />1.4.3 UL-Listed Products� Fire extinguishers shall be UL listed with UL listing mark for
<br />type, rating, and classification of extinguisher.
<br />1.4.4 FM -Listed Products: Fire extinguishers approved by Factory Mutual Research
<br />Corporation for type, rating, and classification of extinguisher with FM marking.
<br />1
<br />2. Products
<br />2.1. Manufacturers
<br />2.1.1 Manufacturers: Subject to compliance with requirements, provide products by one
<br />of the following:
<br />Ansul Fire Protection,
<br />BadgeF-Powhatan.
<br />American Specialties Inc.
<br />Bobfick Washroom Equipment, Inc.
<br />Croker Div., Fire -End and Croker Corp.
<br />Filtrine Manufacturing.
<br />Lyon Metal Products.
<br />J.L. Industries.
<br />Larsen's Manufacturing Co.
<br />Modern Metal Products by Muckle.
<br />Potter -Roemer, Inc.
<br />Samson Metal Products, Inc.
<br />2.2. Fire Extinguishers
<br />2.2.1 General: Provide fire extinguishers for each cabinet and other locations indicated,
<br />in colors and finishes selected by Architect from manufacturer's standard, that
<br />comply with authorities having jurisdiction.
<br />2.2.2 Provide A, B, C, Type 2A-IOB:C, 5 lb nominal capacity in a polyester and epoxy
<br />paint container with pressure guage.
<br />2.2.3 Provide 10 lb, Class 60-B:C fire extinguisher, DC series, Dy chemical for use in
<br />electrical and grease fires, provided in a polyester and epoxy container with pressure
<br />guage.
<br />2.3. Mounting Brackets
<br />2.3.1 Brackets: Designed to prevent accidentally dislodging extinguisher, of sizes
<br />required for type and capacity of extinguisher indicated, in plated finish.
<br />2.3.1.1 Provide brackets for extinguishers not located in cabinets.
<br />3. Execution
<br />3.1. Examination
<br />3.1.1 Examine walls and partitions for thickness and support framing for bracket to verify
<br />cabinet depth and mounting prior to cabinet installation.
<br />3.1.2 Do not proceed until unsatisfactory conditions have been corrected.
<br />3.2. Installation
<br />3.2.1 Follow manufacturer's printed instructions for installation.
<br />3.2.2 Install in locations and at mounting heights indicated or, if not indicated, at heights
<br />to comply with applicable regulations of governing authorities.
<br />3.2.2.1 Fasten mounting brackets and cabinets to structure, square and plumb.
<br />End of Section 10522
<br />Section 10800
<br />Toilet Accessories
<br />1. General
<br />(Not Used)
<br />2. Products
<br />2.1- Toilet Accessories.
<br />2. 1.1 Mirror with stainless steel shelf Over each lavatory 18" x 30" x 1/4" polished
<br />plate glass mirror with galvanized steel back, stainless steel frame and shelf and
<br />with theft proof mounting, equal to the following:
<br />Accessible toilet stalls (tilt mirror): Bradley 7405, 18" x 30"
<br />All other lavatories: Bradley 7815, 18" x 30"
<br />Equivalent models manufactured by McKinney are also acceptable.
<br />2.1.2 Coat & Hat Hooks: Furnish 48 each, Stanley 97082� mount on 3/4" x 5" boards in
<br />employee restrooms as directed by Publix Representative.
<br />2.1.3 Grab Rails: 1 1/2" diameter satin finish stainless steel� one 36 inch at the rear and
<br />one 42 inch to the side of each accessible toilet.
<br />2.1.4 Mirror (mount on back of all restroom doors): 5 mm float glass, edges polished,
<br />quality Q3, 18" x 60".
<br />2.2. Towel, soap, toilet paper, cup dispensers and baby changing station furnished & installed
<br />by Publix.
<br />3. Execution
<br />3.1. Installation: Install all toilet accessories securely to walls indicated, grab rails shall be
<br />mounted to reinforced walls to withstand a point load of 350 pounds at any point.
<br />End of Section 10800
<br />Section 13900
<br />Fire Sprinkler System
<br />I . General
<br />1. 1. System Description:
<br />1.1.1 Construction Documents indicate the Design of a Fire Sprinkler System that
<br />complies with the intent of Publix. Information contained in these Documents shall
<br />be the only basis for Bid.
<br />1-1.2 Factory Mutual Engineering is the approver of all systems that are acceptable to
<br />Publix. However, Factory Mutual approval is a minimum requirement. Publix's
<br />requirements exceed those of Factory Mutual in many particulars.
<br />1.1.3 Design Changes:
<br />1.1.3.1 It is recognized that there are several ways to obtain the protection
<br />intended by Publix, and approvable by Factory Mutual Engineering. If
<br />changes can be made to the Design to achieve cost or time savings, these
<br />shall be submitted to Publix before requesting approval by Factory Mutual
<br />or the Authority Having Jurisdiction.
<br />1.1.3.2 Work shall not begin on the assumption of approvability of changes to the
<br />Design.
<br />1.1.3.3 If Publix approves design changes, submit Change Order request for
<br />inclusion in Contract.
<br />1.2. Scope of WorL
<br />1.1 1 Renovate complete overhead sprinkler system as shown on the Drawings and
<br />described herein. This specification applies only to Publix remodels where no
<br />additonal tenant spaces are involved.
<br />1.2.2 Provide other systems and apparatus as needed for security of components, ease of
<br />access by Fire Fighters and Officials, and as required for a complete, integrated
<br />system.
<br />1.3. Design Requirements
<br />1.3.1 Conform to the requirements of the local building code and the Authority Having
<br />Jurisdiction. If conflicts occur between the requirements of the above mentioned
<br />codes and authorities, the most stringent shall govern.
<br />1. 3. 2 Spacing of sprinklers shall not exceed 130 sq. ft. per sprinkler, without written
<br />permission from Publix.
<br />1.3.3 Sprinkler location: All sprinklers shall be located as shown on Architect's
<br />Drawings, and as required by codes, including vestibules and canopy attic areas (if
<br />combustible).
<br />1.4. Quality:
<br />1.4.1 Subcontractor-
<br />1.4.1.1 The Fire Sprinkler Subcontractor shall be a reputable firm regularly
<br />engaged in this type of work, employing skilled workmen, and with
<br />proper equipment. Work within the State of Florida shall be performed by
<br />a firm licensed as a Class I or 11 Fire Sprinkler Contractor.
<br />1.4.1.2 Upon request, Subcontractor shall show evidence of at least two similar
<br />jobs, of comparable size and character, installed and operating within the
<br />two years prior to bid opening.
<br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without
<br />disclosing cause.
<br />1.4.2 Personnel:
<br />1.4.2.1 Employ an experienced Superintendent to oversee all operation.
<br />1.4.2.2 Work shall not proceed without adequate super -vision present at all times.
<br />Within the State of Florida, Foreman shall be a Journeyman Sprinkler
<br />Fitter.
<br />1.4.2.3 Work shall be performed by workers certified in their trade as
<br />journeymen, and apprentices in accordance with regulations of the
<br />It,
<br />governing authority or customary practice. Utilize workers with skills in
<br />proportion to complexity of tasks required.
<br />1.4.2.4 Publix reserves the right to refuse assignment of workers to Publix work
<br />with or without disclosing cause.
<br />1,4.3 Quality Standards
<br />1.4.3.1 Work shall be accomplished to ensure leak -proof installation.
<br />1.4.3.2 Work will bejudged by Publix in comparison to work of similar types.
<br />Substandard construction as judged by Publix Representative wil I not be
<br />accepted.
<br />1.4.3.3 Neatness counts. Make all joints, connections, unions, etc. with proper
<br />care to insure that tight connections are made without excess material,
<br />well secured to supports.
<br />1.4.3.4 Install piping with runs straight, accurately formed radiuses at bends, and
<br />adequate supports.
<br />1.5. Pressure Test:
<br />1.5.1 Perform testing as required by Factory Mutual and authorities having jurisdiction.
<br />Test results shall be certified by these agencies.
<br />1.5.2 As a minimum, test all piping and equipment under hydrostatic pressure of 200
<br />pounds per square inch for a 2 hour continuous period.
<br />1.5.3 Correct all defects revealed by test.
<br />1.5.4 Retest as required until system is leak free under test conditions.
<br />2. Products
<br />2.1. Heads
<br />2.1.1 Areas with suspended ceilings� Use chrome recessed type sprinklers rated at 165
<br />degrees F., "Reliable" Ft glass bulb with "Reliable" GFI escutcheon ormatch
<br />existing sprinklers.
<br />1 1.2 In areas with exposed structure:
<br />2.1.2.1 Sales/Customer Areas: Use brass upright type sprinklers rated at 1,65
<br />degrees F.
<br />Z�
<br />2.1.2.2 Storage, and other areas not used by customers: Use brass upright type,
<br />rated at 286 degrees F or match existing sprinklers.
<br />2.1.3 Cooler/Freezer Areas: Provide 165 degrees F. dry pendant sprinklers. Seal pipe
<br />penetration and insulate pipe to I'-O" above top of cooler/freezer insulation panel.
<br />2.2. Dry Systems: Where required by local authorities, the system shall be controlled by a
<br />separate wall or post indicator valve and dry pipe valve. Valves are to be equipped with an
<br />air compressor, low air trouble alarm, and supervisory switches. Control valves for either
<br />shall be located 4'-6" above finished floor.
<br />2.3. Provide spare sprinkler heads and wrenches. Provide number of cabinets, spare sprinkler
<br />heads in locations required by NFPA 13 and Factory Mutual.
<br />2.4. Provide pipe sleeves for all pipes passing through concrete floors and for all pipes passing
<br />through conerete and masonry walls.
<br />2.5. Provide escutcheons for all exposed pipes passing through floors and walls, Escutcheons
<br />shall be brass chrome plate, two-piece hinged, fastened with set screw, size to suit.
<br />2.6. All fittings shall be Factory Mutual approved and stamped and shall conform to the
<br />requirements of NFPA. #13 and the Factory Mutual Approval Guide, except that no "slip"
<br />type fittings are to be used.
<br />2.7. Piping:
<br />2.7.1 Piping shall conform to the requirements of NFPA. # 1 3 and the Factory Mutual
<br />Approval Guide. Piping may be grooved, threaded and/or welded if all components
<br />and methods are Factory Mutual approved.
<br />2.7.2 Interior Sprinkler Piping: Schedule 40 black steel screwed pipe with standard
<br />weight cast iron fittings, or schedule 40 black steel grooved pipe with couplings.
<br />2.8. Sprinkler heads shall be approved by Underwriters' Laboratories and Factory Mutual.
<br />3. Execution
<br />3.1. General
<br />3,1.1 Architectural and Structural Drawings shall be used for building construction,
<br />dimensions and specific locations.
<br />3.1.2 Perform all cutting and fitting required for work of this Section in rough
<br />construction of the building, and in areas of existing buildings and structures as
<br />required by alterations and connections to existing.
<br />'
<br />.3.1.3 All patching of finished construction of new and existing buildings shall be by the
<br />General Contractor under the Sections of Specifications covering those materials.
<br />3.1.4 Verify all field dimensions and locations of equipment and fixtures within the layout
<br />as established by the General Contractor to insure close, neat fit, with other trades
<br />work.
<br />3.1.5 Where the work is dependent upon work of other trades or work already in place for
<br />its proper installation, examine such other work and see that is in the proper
<br />condition and state of completion before continuing the installation.
<br />3.1.6 Include the services of an experienced Superintendent, who shall be constantly in
<br />charge of the work, together with qualified journeymen required to properly unload,
<br />install, connect, adjust, start and operate and test the work involved, including
<br />equipment and materials furnished by others and by Owner. All work shall be
<br />executed in a first class workmanlike manner. Workmanship that, in the opinion of
<br />Publix, is substandard or shoddy, shall be removed and replaced with acceptable
<br />work at no cost to Publix.
<br />3.1.7 Follow Drawings in laying out work and check Drawings of other trades to verify
<br />spaces in which work will be installed. Coordinate work with other trades. Maintain
<br />maximum headroom and space conditions at all points. Where headroom or space
<br />conditions appear inadequate, notify Architect before proceeding with installation.
<br />3.2. Area of horizontal runs by trades: See Section 0 1 0 1 0.
<br />I I
<br />3.-). Conceal all piping above suspended ceiling where practical.
<br />3.4. If directed by Architect, the Subcontractor shall, without extra charge, make reasonable
<br />modifications in the layout as needed to prevent conflict with work of other trades or for
<br />proper execution of the work.
<br />3.5. Provide qualified installers. Install materials, apparatus and equipment in neat, workmanlike
<br />manner.
<br />3.6. Cooperate with the work of other trades to prevent conflict or interference and to aid rapid
<br />completion of the overall project.
<br />3.7. Protect materials, apparatus and equipment from damage, moisture, dirt, debris and work of
<br />other trades. Do not install damaged materials and equipment, remove them from the site.
<br />3.8. Install drops for sprinkler heads in areas with finished ceiling. Coordinate the exact location
<br />of the ceiling grid with the ceiling contractor.
<br />3.9. Examine all work of others. If any conditions exist which will prevent satisfactory
<br />installation of materials or equipment the Architect shall be notified in writing. Starting of
<br />work without notification indicates acceptance, and any or all changes required will be at
<br />Contractor's expense.
<br />3.10. Keep thejob site free from accumulations of waste materials and rubbish. Leave thejob site
<br />and work in clean, orderly and acceptable condition. Clean all materials and equipment of
<br />dirt, dust, paint, spots and stains, soil marks arid other foreign matter.
<br />3.11. The inside sprinkler piping shall be installed in such a manner that there will be no leakage.
<br />3.12. There shall be no on site welding of sprinkler piping.
<br />3.13. Requirements for Final Acceptance and Payment:
<br />3.13.1 Furnish Publix' Representative with a complete set of a]I manufacturer's warranties
<br />and instructions, and with two sets of as -built drawings.
<br />3.13.2 Obtain Final Inspection and test required by the authorities having jurisdiction for
<br />their acceptance of the system; provide adequate advance notice to Publix'
<br />representative of such inspection and test furnish Publix' Representative with
<br />evidence of acceptance of the system by the local authority having jurisdiction.
<br />3.14. Guarantee
<br />3.14.1 All equipment shall be tested, adjusted and placed in proper operating condition by
<br />the subcontractor. Contractor shall advise the Architect in writing that the systems
<br />are installed according to the Specifications and Drawings and are operating
<br />satisfactorily. The Owner shall receive written warranty covering all defects in
<br />workmanship and material for a period of one (1) year from the date of Final
<br />Acceptance.
<br />3.14.2 All defects within this period shall be repaired without cost to the Owner. This shall
<br />include adjustments, and all regular and preventative maintenance.
<br />3.14.3 The Owner reserves the tight to make emergency repairs as required to keep
<br />equipment in operation without voiding the Contractor's warranty.
<br />3.15, Final Inspection
<br />3.15.1 All of the following items shall be completed prior to final inspections. No
<br />exceptions will be made and no final payment will be made until all items are
<br />completed.
<br />3.16. Cleaning Equipment and Premises:
<br />3,16.1 Thoroughly clean all exposed parts of the apparatus and equipment. Exposed parts
<br />which are to be painted shall be thoroughly cleaned of cement, plaster, and other
<br />material and all oil and grease spots shall be removed. Repaint or touch up as
<br />required to make look like new. Such surfaces shall be carefully wiped and all
<br />cracks and corners scraped out.
<br />3.16.2 Exposed metal work shall be carefully brushed down with steel brushes to remove
<br />rust and other spots and touched up with primer.
<br />End of Section 13900
<br />Section 13955
<br />Automatic Extinguishing Systems
<br />1. General
<br />1. 1. Automatic Extinguishing Systems, in their entirety, will be provided as an integral part of
<br />the Grease Hood systems furnished by Publix and installed under the Contract. Owner
<br />furnished services includes all set-up of the extinguishing systems.
<br />2. Products
<br />(Not Used)
<br />3. Execution:
<br />(Not Used)
<br />End of Section 13955
<br />Section 15400
<br />Plumbing
<br />1. General
<br />1. 1. Summary
<br />1.1.1 Provide all materials and equipment and perform all labor required to install
<br />plumbing complete as indicated, as required by code, and as specified herein. All
<br />sizes, etc., are Publix minimum and if local code requirements are higher, the work
<br />shall be bid and installed accordingly.
<br />1.1.1.1 Obtain and pay for all permits, bonds, inspection.
<br />1.1.1.2 Provide hot and cold water mains and distribution piping, all overhead and
<br />concealed except main water supply into building and where indicated on
<br />the Drawings. No PVC pipe allowed above floor slab, (except plumbing
<br />waste piping, unless not code approved).
<br />1.1.1.3 Provide a system of soil and waste drains, vents, and connections to alI
<br />sewer, and water mains and all fixtures.
<br />1.1.1.4 Plumbing Fixtures: Provide and adjust, except as herein specified.
<br />1.1�15 Provide all piping hanging and hangers.
<br />1.1.1.6 Provide gas piping and all indirect drains required for equipment
<br />furnished in other sections, and by Owner.
<br />1.1.1.7 Provide rough -in plumbing for fixtures indicated as furnished by Publix or
<br />others, and make required connections. Include uncrating equipment,
<br />moving into place, and installing complete.
<br />1.1.1.8 Coordinate plumbing work with all trades involved, including the
<br />Refrigeration Contractor's work.
<br />1 1.1.1.9 Provide all other materials and services required for a complete working
<br />installation described in Contract Documents.
<br />1.1.1.10 Provide Watts #909 backflow preventer on main water service line.
<br />Coordinate location with Publix representative.
<br />1.1.2 All apparatus shall be installed at exact height and locations as shown on the
<br />Architectural Drawings, or if not shown, at heights and locations determined by
<br />applicable codes and laws.
<br />1.1.3 PerforTn all excavation and backfill required for services, and for all plumbing and
<br />work inside and outside the building. Cutting of curbs, walks, concrete and paving
<br />required for excavation shall be done by appropriate trade.
<br />1.1.4 All store cases, coolers, and freezers will be furnished and set in place by Publix.
<br />The Refrigeration Contractor shall make all condensate waste connections required
<br />to Plumbing Contractors stub ups. Check equipment drawings against Drawings in
<br />order to verify exact locations. Provide gas piping as indicated.
<br />1.2. Definitions: Explanation and -Precedence of Documents:
<br />1.2.1 For purposes of clarity and legibility, Plumbing Drawings are essentially
<br />diagrammatic and, although size and location of equipment are drawn to scale
<br />wherever possible, Contractor shall make use of all Contract Documents-
<br />1.2.2 The Drawings indicate size, connection points and routes of pipe. It is not intended,
<br />however, that all offsets, rises and drops are shown. Install piping as required to fit
<br />structure, avoid obstructions, and retain clearance, headroom, openings and
<br />passageways.
<br />1.2.3 Carefully examine all existing conditions, existing piping and premises and compare
<br />the Drawings with the existing conditions. Submittal of bid indicates that the
<br />Contractor has examined the site and Drawings and has included all required work
<br />in his bid. No allowances will be made for any error resulting from Contractor's
<br />failure to visit Job Sites and to review Drawings.
<br />1.2.4 Conflicts, discrepancies, interferences and omissions in documents shall be brought
<br />to the aftention of the Architect for clarification prior to commencement of work.
<br />1.2.5 Information was taken from various archive drawings and limited field observation.
<br />Field verification of existing conditions and points of connection are required.
<br />Provide all demolition, cutting and patching, and excavation required for the
<br />project, whether or not shown on the drawings.
<br />1.2.6 The term "provide" shall be defined as furnished and installed complete in every
<br />way by this contractor.
<br />1.33. Submittals:
<br />1.3.1 Within 30 days of Contract Commencement (Authorization to Proceed), submit for
<br />Publix' Architect's approval
<br />Fixtures and trim with cuts including rough -in dimensions.
<br />Equipment
<br />Drains and cleanouts (floor and wall)
<br />Valves, stops, hose bibbs
<br />Miscellaneous
<br />Roof flashing
<br />Piping diagrams
<br />Other items required to complete the Work
<br />1.3.2 Submit six identical bound copies of all items. Arrange categories in order listed
<br />above.
<br />1.3.3 All cuts for the above shall have rough -in dimensions, connection sizes, and any
<br />special installation requirements. In addition, furnish motor horsepower voltage and
<br />phase for all equipment.
<br />1.3.4 Project Record Drawings� Comply with Section 01720.
<br />1.3.5 Do not order materials or proceed with the work without approved submittals.
<br />1.3.6 Confirm electrical requirements and voltage with Div. 16 contractor prior to
<br />ordering equipment.
<br />1.4. Quality:
<br />1.4.1 Subcontractor:
<br />1.4.1.1 The Plumbing Subcontractor shall be a reputable firm regularly engaged
<br />in this type of work, employing skilled workmen, and with proper
<br />equipment.
<br />1.4.1.2 Upon request Subcontractor shall show evidence of at least two similar
<br />jobs, of comparable size and character, installed and operating within the
<br />previous two years prior to bid opening.
<br />1.4.1.3 Publix reserves the right to refuse any Subcontractor with or without
<br />disclosing cause.
<br />1.4.2 Personnel:
<br />1.4.2.1 Employ an experienced Superintendent to oversee all operation.
<br />1.4.2.2 Work shall not proceed without adequate supervision present at all times.
<br />1.4.2.3 Work shall be accomplished by workers certified in their trade as masters,
<br />journeymen, and apprentices in accordance with regulations of the
<br />governing authority or customary practice. Utilize workers with skills in
<br />proportion to complexity of tasks required.
<br />1.4.2.4 All welding shall be performed by certified welders. For each welder,
<br />provide certification of welding quality test, current within 6 months of
<br />project.
<br />1.4.2.5 Publix reserves the right to refuse assignment of workers to Publix work
<br />with or without disclosing cause.
<br />1.4.3 Quality Standards
<br />�
<br />1.4.3.1 Work shall be accomplished to ensure leak -proof installation.
<br />1.4.3.2 Workwill bejudgedby Publix in comparisonto work of similartypes.
<br />Substandard construction as judged by Publix Representative will not be
<br />accepted.
<br />1.4.3.3 Make all joints, connections, unions, etc. with proper care to insure that
<br />tight connections are made without excess material, well secured to
<br />supports.
<br />1.4.3.4 Install piping with runs straight, accurately formed radiuses at bends, and
<br />adequate supports.
<br />1.4.4 Codes and Standards:
<br />1.4.4.1 The entire system and all components specified herein shall meet all
<br />applicable national, state, county and local codes, standards and
<br />ordinances in every respect,
<br />1.4.4.2 The contractor shall meet with the authority having jurisdiction (AHJ) and
<br />review the proposed work, prior to commencing the work. Comply with
<br />and provide all additional and supplementary requirements of the AHJ.
<br />1.4.4.3 Comply with all OSHA requirements for construction safety. All piping
<br />and equipment lower than 6 ft. - I 0 in. AFF shall be padded and striped
<br />per OSHA requirements.
<br />1.4.4.4 The following are the codes and standards which the engineer knows to
<br />govem the work.
<br />a) Standard Plumbing Code, 1997.
<br />b) Standard Gas Code, 1997.
<br />C) Florida Accessibility Code for Building Construction,
<br />1994.
<br />d) Florida Energy Efficiency Code for Building
<br />Construction, 1997,
<br />e) NFPA 30,1996, Flammable and Combustible Liquids
<br />Code.
<br />f) NFPA 37, Stationary Combustion Engines and Gas
<br />Turbines, 1994.
<br />g) NFPA 54, National Fuel Gas Code, 1996.
<br />h) NFPA 58, Liquefied Petroleum Gas Code, 1998.
<br />h) NFPA 70, National Electric Code, 1996.
<br />i) NFPA 101, Life Safety Code, 1997,
<br />j) ANSFASME 31.9, Building Services Piping.
<br />1.4.5 Participate in the Pre -Construction Conference.
<br />1.5. Sequencing�
<br />1.5.1 Notify General Contractor, or any others, of all required chases, sleeves and
<br />openings required so that the work can be accomplished without delay. Provide
<br />necessary sleeves, etc., to be installed. Otherwise, this contractor shall pay for
<br />appropriate trades to perform cutting and patching.
<br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut.
<br />1.5.3 Where construction necessitates the routing of piping through structural members,
<br />framing or under footings, permission to make such installation shall first be
<br />obtained from the Publix Field Representative
<br />1.6. Temporary Operation: The Owner may require operation of parts or all of the installation
<br />prior to Final Acceptance. This operation shall not constitute acceptance of the Contractor's
<br />work.
<br />1.6.1 All gas and water used for construction shall be paid for by the General Contractor.
<br />Furnish and install all temporary water piping required for construction purposes
<br />and remove piping when use is no longer required. Restore site and piping to
<br />original conditions.
<br />1.7. The Owner reserves the right to make emergency repairs as required to keep equipment in
<br />operation without voiding the Contractor's guarantee nor relieving the Contractor of his
<br />responsibilities during the guarantee period.
<br />1.8. Operating Instructions and Service Manual:
<br />I.S.1 Provide two (2) neatly bound copies of maintenance and instructions book, parts
<br />lists pertaining to all equipment furnished.
<br />1.8.2 Each section shall be indexed and include parts lists, instruction books, suppliers'
<br />phone numbers and addresses, and individual equipment guarantees all in separate
<br />sections.
<br />I.S.3 Representatives of the Owner shall be instructed by the Contractor as to complete
<br />care and operation of the plumbing system. Inform the Architect in writing as to the
<br />persons who received the instructions and the date that this was done,
<br />1.9. Warranty
<br />1.9.1 All new work, equipment, materials and systems shall be warranted against all
<br />defects for a period of one year after final acceptance by the Owner.
<br />2. Products:
<br />2.1. Materials:
<br />2.1.1 All materials shall be new, full weight, of the best quality with the same brand or
<br />manufacturer used for each class of materials or equipment. All similar materials
<br />shall be of the same type and manufacturer unless other -wise designated.
<br />2.1.2 All plumbing fixtures shall be "first quality" as defined and set forth in Commercial
<br />Standard CS 20-36 as promulgated by the U.S. Department of Commerce.
<br />2.2. Fixtures
<br />2.2.1 Provide vitreous china fixtures unless otherwise noted.
<br />2.2.2 American Standard product designations have been used for consistency. Equivalent
<br />fixtures by Crane, Kohler, or E1jer may be accepted.
<br />2.2.3 Provide floor mounted carrier for all wall -hung fixtures, suitable for safely
<br />supporting a 250 lb. load at the fixture outside edge.
<br />2.2.4 Handicap Fixtures
<br />2.2.4.1 Provide ADA approved padded seamless white safety covers for waste
<br />and supply piping of handicap fixtures.
<br />2.2,4.2 Provide offset tailpiece for lavatories.
<br />2.2.4.3 Provide anti -scald pressure balanced tempering valve for lavatories and
<br />other hand washing fixtures, unless the fixture is served with tempered
<br />(mixed) supply water.
<br />2.2.5 Instantaneous Water Heater
<br />2.2.5.1 Thermostatically controlled, UL Listed, suitable for use in handicap hand
<br />washing facilities.
<br />2.3. Equipment
<br />2.3.1 Drains, Cleanouts: As scheduled. Approved manufacturers:
<br />Smith
<br />Zurn
<br />Wade
<br />2.4. Pipe and Fittings�
<br />2.4.1 Hot and cold water piping: ASTM B88 Seamless Type "L" copper tubing with
<br />wrought copper solder fittings. Main service type "K". Underground copper piping
<br />shall be protected from the elements with a bitumastic material (Pittsburg Corn'
<br />Pittwrap) or AWWA C 105 polyethylene color codedjacket. ing
<br />2.4.2 L.P. Gas Piping
<br />2.4.2.1 Indoors: ASTM A53B steel pipe, Schedule 40, black, forged steel socket
<br />weld fittings.
<br />2.4 � 2.2 Outdoors: ASTM A53B steel pipe, Schedule 40, mill galvanized. Stencil
<br />paint "LP -Gas" in bright yellow every 5 feet, at each bend, and at each
<br />valve.
<br />2.4.23 Indoors - Liquid: Not permitted.
<br />2.4.2.4 Outdoors - Liquid: ASTM A53 steel pipe, Schedule 80, mill galvanized.
<br />Stencil paint "LP -Liquid" in bright yellow every 5 feet, at each bend, and
<br />at each valve.
<br />2.4.2.5 Flexible Connectors: Designed and listed for LP gas service, stainless
<br />steel wire braid reinforced, min. 350 psi working pressure.
<br />2.4.2.6 Regulator: Designed and listed for LP gas service, two -stage design with
<br />integral pressure relief or over -pressure shut-off device, and a means to
<br />measure the outlet pressure.
<br />2.4.2.7 Vaporizers: Designed and listed for LP gas service, min. 250 psi working
<br />pressure.
<br />2.4.2.8 Hydrostatic Relief Device� Designed and listed for LP gas service, for
<br />positive pressure relieving protection, in each section of piping (including
<br />flexible connectors) in which LP gas can be isolated between shut-off
<br />valves. Relief device shall actuate between 400 and 500 psig. Extend
<br />relief to a point at least I 0 feet above grade.
<br />2.4.3 Gas Piping:
<br />2.4.3.1 Indoors ASTM A53B steel pipe, Schedule 40, black, forged steel socket
<br />weld fittings.
<br />2.4.3.2 Outdoors: ASTM A53B steel pipe, Schedule 40, mill galvanized,
<br />'�
<br />malleable iron screwed fittings, galvanized. Stencil paint "GAS" in bright
<br />yellow every 5 feet, at each bend and at each valve.
<br />2.4.4 Soil, Waste, Vent Pipe:
<br />2.4.4.1 PVC pipe (where allowed by codes): Unplasticized, ASTM D 1 785, Type
<br />11, solvent cement joints, DWV fittings. schedule 40 unless indicated
<br />otherwise on the Drawings, all elbows shall be long sweep type (above
<br />and below the floor).
<br />2.4.4.2 Cast Iron Pipe: Coated service weight cast iron soil pipe using coated
<br />S VERDR UP FACILITIES, INC
<br />FLORIDA CORPORATE LICENSE #AA COO 1 291
<br />(407)903-5001 Fax (407)903-5150
<br />5750 Major Boulevard, Suite 500, Orlando, FL 32819
<br />ARCHITECT OF RECORD
<br />NAME FLOYD WILSON MCCOLLUM, JR., AIA
<br />REGISTRATION: FLORIDA REG. #AR0016162
<br />DA TE: 02128101
<br />Revision:
<br />Date:
<br />By: Description:
<br />1. ., il
<br />� 11 � /
<br />11A.�_J 1� 4,+n �(
<br />, , I -
<br />I
<br />17
<br />1 1. I ri',,�_
<br />I A ,
<br />� - �, I,, 19 .1
<br />/ ,- 11_�
<br />71 4- , I , �,
<br />2 ,,
<br />Is
<br />V 25
<br />-0
<br />Z)
<br />I
<br />-
<br />0-
<br />C
<br />0 � 2i
<br />&
<br />0
<br />(D
<br />%�
<br />a
<br />E
<br />%�
<br />0
<br />4=
<br />(I
<br />[*--
<br />M
<br />qi
<br />T_
<br />14T
<br />D
<br />L0
<br />Ln
<br />(N
<br />C�o
<br />00
<br />CV)
<br />01
<br />- 00 00
<br />[___ M 00
<br />0- Ir-
<br />a
<br />W
<br /><
<br />0
<br />X
<br />__J
<br />LU `�_
<br />C0 C) LL. ,
<br />LU -00
<br />LU
<br />W
<br /><
<br />>
<br />W
<br />0
<br />0�
<br />(_5 000
<br />- = 2: Q0
<br />LL (D < �
<br /><
<br />=)
<br />UJ
<br />_J
<br />_J
<br />LL
<br />�
<br />N_
<br />LL -
<br />C0 _J 1:T
<br />OLULUO-)
<br />Cy
<br />Ch
<br />=)
<br />0
<br />-
<br />U)
<br />C) ��
<br />4=
<br />3::
<br />Co
<br />_J
<br />M0LU
<br />[-- < LL1
<br />< W -1 2:
<br />M
<br />M
<br />U
<br />LU
<br />-
<br />_J
<br />_J
<br />Zi
<br />Z:
<br />ftt, LJJ r'_�o
<br />>
<br /><
<br />W
<br />D
<br />0 [--- (D =
<br />0- :::i ,�'- 0-
<br />LU
<br />W
<br />Z
<br />CD
<br />>-
<br />X:
<br />01:� E)- >< LU
<br />_J
<br />d
<br />3::
<br />4=
<br />C-4
<br />a-
<br />a
<br />0<0 LU
<br />�_
<br />0
<br />m
<br />LU
<br />0 LL Co [---
<br />C/)
<br />�-
<br />[-�
<br />N
<br />Key Plan:
<br />Scales:
<br />Sverdrup Project No.: 22196390
<br />Drawing Title:
<br />SPECIFICATIONS
<br />Date: I
<br />03/12/99
<br />Designed By: RBJ Drawing No.:
<br />Drawn BT RM PM8
<br />Checked By: FWM
<br />
|