Laserfiche WebLink
A <br />Z <br />1.5.2 Joists, girders, beams, columns or reinforcing steel shall not be cut. <br />1.5.3 Where construction necessitates the routing of conduit through structural members, <br />framing or under footings, permission to make such installation shall first be <br />obtained from the Publix Field Representative. <br />1.6. Temporary Operation: <br />1.6.1 The Owner may require operation of parts or all of the installation prior to Final <br />Acceptance. <br />1.6.2 Cost of utilities for such operation shall be paid by the Contractor. This operation <br />does not constitute acceptance of the Contractor's Work. <br />1.6.3 All electricity used for construction shall be paid for by the General Contractor. <br />Furnish and install temporary electrical connection and meter for construction <br />purposes. Remove temporary service when use is no longer required. Clean up and <br />landscape as required. <br />1.7. Emergency Repairs: The Owner reserves the right to make emergency repairs as required <br />to keep equipment in operation without voiding the Contractor's guarantee nor relieving the <br />Contractor of his responsibilities during the guarantee period. <br />1.8. Operating Instructions and Service Manual: <br />1.8.1 Provide two (2) neatly bound copies of maintenance and instructions book, parts <br />lists pertaining to all equipment furnished. <br />1.8.2 Each section shall be indexed and include parts lists, instruction books, suppliers' <br />phone numbers and addresses, and individual equipment guarantees all in separate <br />sections. <br />1.8.3 Representatives of the Owner shall be instructed by the Contractor as to complete <br />care and operation of the electrical system. Inform the Architect in writing as to the <br />persons who received the instructions and the date that this was done. <br />2. Products: <br />2.1. Materials: <br />2.1.1 All materials shall be new, of the best quality. <br />2.1.2 All similar materials such as switches, panelboards, fuses, circuit breakers, junction <br />boxes, contactors and other classes of equipment shall be of the same type and <br />manufacturer. <br />2.1.3 All equipment and materials shall be furnished in strict accordance with the <br />equipment schedule and Specification requirements. <br />2.2. Panelboards <br />2.2.1 The panelboards shall be dead -front, totally enclosed, with locking doors, with bolt - <br />in type circuit breakers in one, two or three pole common trip units as noted on the <br />Drawings, UL approved. The panelboards shall be 3 phase, 4 wire, solid neutral, <br />ground bus, 120/208 volts, with number of poles, ampacity, and short circuit <br />interrupting rating as noted on the Drawings. Panelboards shall have copper <br />bussing. The circuits shall be connected to individual poles of the panel exactly as <br />shown on the Drawings, and the panel shall be provided with a typewritten <br />s directory. <br />2.2.2 All panels shall be factory assembled. <br />2.2.3 Ground fault circuit interrupters shall be provided on each circuit as required by the <br />NEC or where specified on the Drawings. <br />2.2.4 Circuit breakers installed in panels AB, BC and CD shall be equipped with HID <br />rated breakers as applicable for the load. <br />2.2.5 Isolated ground busses shall be provided where indicated. <br />2.2.6 Acceptable Manufacturers: <br />G.E <br />Square - D <br />Westinghouse <br />ITE Div. of Siemens -Allis <br />2.3. Electrical Service Entrance <br />2.3.1 The service entrance shall be as indicated on the Drawings. <br />2.3.2 Coordinate with the utility company. Verify method of service with local utility <br />company and obtain written approval from Publix Representative before <br />commencement of work. <br />2.3.3 The system shall be grounded in conformance with NEC and as shown on <br />Drawings. <br />2.4. Main Switchboard/Main Distribution Panel (MDP) <br />2.4.1 Acceptable Manufacturers: <br />G.E. <br />Square - D <br />Westinghouse <br />ITE Div. of Siemens -Allis <br />2.4.2 General: Furnish and install the main switchboard as herein specified and shown on <br />the Drawings. <br />2.4.3 The switchboard shall meet Underwriters' Laboratories enclosure requirements and <br />be furnished with an Underwriters' Laboratories label. <br />2.4.4 Enclosure Construction <br />2.4.4.1 The switchboard framework shall consist of steel channels welded or <br />bolted to the frame to rigidly support the entire shipping section for <br />moving on rollers and floor mounting. The framework is to be formed, <br />code gauge steel, rigidly welded and bolted together to support all cover <br />plates, bussing and component devices during shipment and installation. <br />2.4.4.2 Each switchboard section shall have an open bottom and individual <br />removable top plate for installation and termination of conduit. Top and <br />bottom conduit areas are to be clearly shown and dimensioned on the <br />Shop Drawings. The end plates of the switch boxes shall be removable <br />for installation purposes. The wireway front covers are to be hinged to <br />permit access to the branch switch load side terminals without removing <br />the covers. All closure plates shall be screw removable and small enough <br />for easy handling by one man. The paint finish shall be gray enamel over <br />a rust -inhibiting phosphate primer. <br />2.4.5 Bussing: <br />2.4.5.1 The switchboard bussing shall be of sufficient cross -sectional area to <br />continuously conduct amperage as indicated on Drawings with a <br />maximum average temperature rise of 50 degrees c. above an ambient <br />temperature of 25 degrees c. <br />2.4.5.2 The buss shall be aluminum with 50% neutral with an integrated <br />equipment short circuit rating of 150,000 amps (sym). <br />2.4.5.3 The buss shall extend the full length of the available feeder area of each <br />enclosure section. <br />2.4.6 Withstand Rating. <br />2.4.6.1 The switchboard, as a complete unit, shall be given a single withstand <br />short circuit current rating by the manufacturer. The withstand short <br />circuit current rating shall certify that all equipment is capable of <br />withstanding the stress of a fault equal to the interrupting rating of the <br />least overcurrent protective device contained therein. Such rating shall be <br />established by actual tests by the manufacturer on equipment constructed <br />similarly to the subject switchboard. This test data shall be available and <br />shall be furnished to the Architect, if requested, with or before the <br />submittal of Approval Drawings. <br />2.4.6.2 The complete unit shall have interrupting rating of not less than the <br />available or interrupting fault current shown on the drawings. <br />2.4.7 Main Switch (where shown on the Drawings): <br />2.4.7.1 The main switch shall be fusible and of the bolted contact type, equipped <br />with a 120 volt electric trip device for remote shunt trip operation. <br />2.4.7.2 The switches shall be dead -front type with a fuse -door interlock and <br />provisions for padlocking in the open position with at least three padlocks. <br />The bolted contacts are to firmly bolt the movable blades to both the top <br />and bottom stationary contacts. The switch shall have a quick -make, <br />quick -break mechanism. Easily replaceable stationary are tips and arch <br />chambers shall be used. The switch shall be capable of opening and <br />closing into a fault of twelve times its continuous current rating in <br />accordance with UL requirements to insure safety on emergency <br />operation. <br />2.4.7.3 The main switch shall be equipped with NEMA Class 'L' fuses and be <br />Bussman KTU type. <br />2.4.7.4 The main switch shall be as manufactured by Pringle or Square "D" bolted <br />lock and rated at ampacity shown on the Drawings - no substitutions. <br />2.4.8 Main Breaker (where shown on the Drawings): The main breaker shall be equipped <br />with a 120 volt electric trip device for remote shunt trip operation. <br />2.4.9 Fusible Switches (where shown on the Drawings): <br />2.4.9.1 The fusible switches shall be quick -make, quick -break with the size <br />shown on the associated Drawings. The units shall be listed and approved <br />by Underwriters' Laboratories for general use and where applicable, shall <br />be dual horsepower rated for both standard one-time or dual -element <br />fuses. The fusible switches shall be group mounted in panel -type <br />construction. Each switch shall be equipped with class 'R' rejection type <br />fuse clips. <br />2.4.9.2 Each switch is to be enclosed in a separate steel enclosure. The enclosure <br />shall employ a hinged cover for access to the fuses which shall be <br />interlocked with the operating handle to prevent opening the cover when <br />the switch is in the on position. This interlock shall be constructed so that <br />it can be released with a standard electrician's tool for testing fuses <br />without interrupting service. The units shall have padlocking provisions <br />in the off position and the operating handle position shall give positive <br />switch position indication. Switches shall pass industry standard I2t <br />withstandability tests and fuse race tests as described elsewhere in the <br />Specifications. <br />2.4.9.3 All fusing as manufactured by Bussman, type KTN-R, dual -element and <br />current limiting as shown on the Drawings. <br />2.4.10 Circuit Breakers (where shown on the Drawings). The circuit breakers shall be <br />group of individually mounted, as required for the sizes shown on the Drawings. <br />2.5. Bus Duct (where shown on the Drawings): <br />2.5.1 Service entrance bus duct shall be rated as shown on Drawings, 3 phase, full neutral, <br />suitable for 120/208 volts service, inside -outside location. <br />2.5.2 The bus duct shall be complete with all necessary elbows, transformer taps, fire <br />stops, wall flange for fittings and supports to provide a satisfactory installation as <br />indicated on the Drawings. <br />2.5.3 The bus duct shall be of the same manufacturer as the main switchboard. <br />2.5.4 The bus duct shall have the same or greater withstand rating as the main <br />switchboard's interrupting rating. <br />2.5.5 Support for the bus duct shall be by the General Contractor. <br />2.6. Overcurrent Protective Devices <br />2.6.1 Enclosed, Molded -Case Circuit Breaker: NEMA AB 1, handle lockable. <br />2.6.1.1 Characteristics: Frame size, trip rating, number of poles and auxiliary <br />devices as indicated and interrupting capacity rating to meet available <br />fault current. <br />2.6.1.2 Application Listing: Appropriate for application, including switching <br />fluorescent lighting loads or heating, air-conditioning and refrigerating <br />equipment. <br />2.6.1.3 Circuit Breakers, 200 A and Larger: Trip units interchangeable within <br />frame size. <br />2.6.1.4 Circuit Breakers, 400 A and Larger: Field -adjustable short -time and <br />continuous current settings. <br />2.6.1.5 Current -Limiting Trips: Where indicated, let -through ratings less than <br />NEMA FU 1, Class RK-5. <br />2.6.1.6 Current Limiters: Where indicated, integral fuse listed for circuit breaker <br />2.6.1.7 Lugs: Mechanical lugs and power -distribution connectors for number, <br />size and material of conductors indicated. <br />2.6.1.8 Shunt Trip: Where indicated. <br />2.6.2 Future Devices: Where indicated, equip compartments with mounting brackets, <br />supports, bus connections and appurtenances designed for overcurrent protective <br />device types and ampere ratings indicated. <br />2.7. Contactors <br />2.7.1 Contactors shall be manufactured by Square'D', Siemens, or General Electric; or <br />others as approved by Publix in writing specifically for this project. Contactor to be <br />of the same manufacturer as it's respective panel serving the contactor. <br />2.7.2 Contactors shall be designed to carry the full rated current on a continuous basis. <br />2.7.3 Contactors shall be electrically operated, mechanically held, and suitable for remote <br />operation. The mechanically held contactors shall be supplied with coil clearing <br />contacts which disconnect the magnet coil when operated to eliminate any AC <br />magnetic hum. <br />2.7.4 Contactors shall be as sized as shown on the Drawings and be installed in a NEMA <br />1 enclosure. <br />2.8. Wire and Cable <br />2.8.1 All wires shall be THHN/THWN-2 copper unless otherwise noted. No aluminum <br />wire will be permitted. <br />2.8.2 No wire shall be smaller than #12 AWG except control wire. No smaller than #10 <br />AWG shall be used on runs of over 100 ft. <br />2.8.3 In no case shall the number of conductors installed in conduits exceed the maximum <br />fill allowed by the NEC. Should this occur on the Drawings, the Electrical <br />Contractor shall inform the Architect before installation. Conductors shall not be <br />installed beneath the heating equipment foundations. <br />2.8.4 Wire must be in one unspliced run to all secondary panel feeders, and in one <br />unspliced run to all air conditioning and refrigeration units. <br />2.8.5 Install all phase conductors, neutral conductor, and ground conductor from <br />panelboard to the equipment connection junction box. If the neutral conductor is <br />not needed it shall be taped and identified in the J.B. for future use. <br />2.9. Conduits and Raceways <br />2.9.1 PVC Schedule 40 conduit may be used under floor slab. Risers and raceways <br />embedded into concrete shall be heavy wall hot dipped galvanized steel. All <br />conduit between transformer and main switch shall be heavy wall, hot dipped, <br />galvanized steel W/MFG couplings and fittings, unless noted otherwise on the <br />Drawings. <br />2.9.2 No PVC shall be installed above floor slab. <br />2.9.3 Raceways concealed in wall or ceiling spaces shall be standard weight galvanized <br />EMT with compression couplings or as specified below. <br />2.9.4 Underfloor Duct (where shown on the Drawings): <br />2.9.4.1 Shall be "Walkerduct" (no substitutes) as manufactured by Walker/ <br />Textron Company, Parkersburg, West Virginia. Install complete service <br />fittings, blanking plates, junction boxes, covers, etc., with threaded <br />fittings. Use standard No. 2 and No. 4 duct with 42-24 x 2 x 2 or #2-12 x <br />2 x 2 inserts as shown on Drawings, adaptors 41126a-3/4", for cable. <br />Install Walker Duct junction boxes with brass tops recessed to receive <br />terrazzo. Verify locations of duct with Drawings. <br />2.9.4.2 Top of cut insert shall be 3/4" below finish floor line. <br />2.10. Time Switches <br />2.10.1 Provide time switches as manufactured by Intermatic (no substitutes). <br />2.10.2 Time switches shall be DPST, 40 amperes, 120 volt, AC motor and astronomic dial, <br />spring -wound carry-over. <br />2.10.3 Time clocks shall be labeled. <br />2.11, Outlet Boxes, Fittings, and Connectors <br />2.1 1.1 Unless hereinafter specifically noted or shown on the Drawings, the minimum size <br />of branch circuit outlet boxes for concealed work shall be 4"x4"xI 1/2" for square <br />boxes and 4"xl 1/2" for octagon boxes. <br />2.11.2 Boxes shall be provided with plaster covers of sufficient depth to bring the face of <br />the outlet substantially flush with the finished wall or ceiling. The box shall not <br />project beyond the finished wall or ceiling line. <br />2.11.3 Outlets in concrete block, or other hollow masonry walls: <br />2.11.3.1 Openings in concrete block walls for outlets shall be cut to exact size with <br />a masonry saw. <br />2.11.3.2 Switch and receptacle mounting heights, as specified or noted may be <br />adjusted so that the bottom of the outlet box may rest on the top of the <br />wall block at the nearest mortar joint <br />2.11.3.3 All unused outlets shall be provided with blank covers. <br />2.11.4 Where conduits 1" or larger enter outlet boxes, the boxes shall be 4 l l/] 6"x4 - I I/ <br />16"x2 1/4" minimum. Boxes shall be of ample size to provide conductor spaces as <br />required by the National Electric Code. <br />2.11.5 "Handy", utility or sectional boxes will not be permitted in masonry walls. <br />2.11.6 When more than one switch or device is shown ganged at any location, a one-piece <br />box of suitable size shall be installed. <br />2.11.7 Outlet boxes intended for the installation of lighting fixtures shall be equipped with <br />3/8" "No -Bolt" or equal fixture studs. <br />2.11.8 Unless otherwise noted, all switches, receptacles and devices shown on the exterior <br />of building walls shall be installed in flush mounted boxes provided with <br />weatherproof gaskets. <br />2.11.9 All conduit fittings (condulets) shall be of the cast metal threaded hub type, Crouse - <br />Hinds, or Appleton. <br />2.11.10A11 rigid conduits entering panels, cabinets, outlet boxes, etc., shall be provided with <br />locknuts on both sides of such devices driven tight so as to maintain positive <br />electrical and mechanical continuity throughout the conduit system. Insulated <br />bushings shall be installed on the inside of the termination <br />2.11.11 Threadless couplings shall not be used for rigid conduit. <br />2.1 1.12A11 EMT couplings and box connectors shall be of the set screw steel concrete tight <br />or steel compression type. Compression type shall be used in all coolers or freezers. <br />No cast connectors or couplings will be allowed. <br />2.11.13A11 flex conduit shall be steel w/steel fittings, and shall extend a maximum of 10 ft, <br />unless approved by Publix. <br />2.12. Junction Boxes: Wiring shall be neatly arranged, bundled and laced in proper groups. <br />2.13. Pull Boxes <br />2.13.1 Pull boxes shall be installed in conduit system where needed whether or not they are <br />shown on the Drawings. <br />2.13.2 Boxes shall be constructed of code gauge galvanized steel with screw covers. <br />2.14. Safety Switches <br />2.14.1 The basis of design and quality standards is Square - D. <br />2.14.2 All units shall be of the same manufacturer. <br />2.14.3 Safety switches shall be fusible, solid neutral, 250 volt, quick -make and quick -break <br />with visible blades, single throw, general duty, of size and fusing as shown on the <br />Drawings, or required for application. Switches mounted out of doors shall be with <br />protective barrier over hot lugs. <br />2.14.4 Exterior units shall be in rain tight enclosure. (NEMA 3R) <br />2.15. Wall Switches <br />2.15.1 Switches shall be flush mounted, quiet tumbler type, 120/277 volts, 20 amp rated. <br />2.15.2 Wall plates shall be smooth, 302 stainless steel, one piece as indicated on the <br />Drawings. <br />2.15.3 Switches shall be installed on the "strike" side of the door swing. <br />2.15.4 Switches shown near doors shall be not less than two inches and not more than <br />twelve (12) inches from the trim. <br />2.16. Receptacles <br />2.16.1 All units shall be totally enclosed composition with side and rear connections. All <br />units shall be equipped with ears and have a rating as listed below. All devices shall <br />be Hubbell or Leviton. See symbol schedule on the Drawings. <br />2.16.2 Duplex convenience outlets with ground shall be 20 amp, 125 volt parallel slot, "U"- <br />shaped ground, heavy duty "T" rated. <br />2.16.3 120/208 volt, 3 wire receptacles with ground shall be single 3 wire polarized <br />receptacles with grounding terminal. <br />2.16.4 Weatherproof receptacles shall be duplex, 20 amp, 125 volt parallel slot receptacle <br />with "U" shaped grounding slot in flush, weatherproof box with gasketed cover and <br />self closing, spring door. <br />2.16.5 Floor outlets shall be 20 amp, 125 volts single or duplex parallel slot receptacles <br />with "U" shaped grounding slot as called for, located as shown on the Drawings. <br />Provide slotted brass flush cap for sealing when not in use. <br />2.16.6 All device cover plates shall be smooth 302 stainless steel, one piece. <br />2.17. Lighting Fixtures <br />2.17.1 All lighting fixtures shall be furnished by Publix and installed by this Subcontractor. <br />In -line fuses are included with all fluorescent and metal halide fixtures. <br />2.1.7.2 In areas of suspended ceilings two safety wires per fixture will be supplied and hung <br />by the suspended ceiling Subcontractor, the Electrical Subcontractor shall tie <br />fixtures in areas of suspended ceilings with two (2) #10 wire up to the roof joists per <br />fixture. <br />2.18. Electric Door Openers: Electric door openers shall be furnished and installed by others, but <br />where shown on the Drawings, shall be wired by the Electrical Contractor with two (2) 115 <br />volt, 20 amp, 3 wire circuits to control box at the top of the door. <br />2.19. Telephone Outlets: <br />2.19.1 Provide outlets as located on Drawings. <br />2.19.2 See Drawings for location and size of conduit runs. <br />2.19.3 Provide outlet boxes and stainless steel cover plates. <br />2.20. Standby Electric -Emergency Generator and Transfer Switch (where shown as new on the <br />Drawings). <br />2.20.1 Emergency generator and automatic load transfer switch will be fumished by Publix <br />and shall be set in place and connected by the contractor. <br />2.20.2 Emergency Generator: The system shall be installed according to the <br />manufacturer's instructions. <br />2.20.3 Automatic Load Transfer Switch: The automatic load transfer switch shall be <br />designed for the capabilities of this unit to transfer the load from normal to <br />emergency when any phase of the normal source drops below 70 percent of rated <br />voltage and to automatically restore the load to the normal source when all phases <br />are 90 percent or more of rated voltage and frequency. Unit is to be provided with a <br />contact to actuate the engine starting circuit. <br />2.20.4 The electrical contractor shall provide wiring and conduit to connect the battery <br />charger, generator start circuit and any block heater wiring required. <br />2.21. Grounding <br />2.21.1 All wiring systems shall be grounded in accordance with article 250 of the NEC. <br />All items of electrical equipment not connected directly and mechanically to the <br />conduit system shall be connected thereto with a jumper of suitable size. All breaks <br />in the continuity of the conduit system shall be bridged with a jumper of the proper <br />size between the next adjacent outlet or junction boxes. <br />2.21.2 Due care must be taken as not to interchange circuit neutrals. <br />2.21.3 A green THHN/THWN-2 insulated stranded 12 AWG or larger conductor shall run <br />unbroken from the system ground through the conduit system to the ground <br />connections at all receptacles, switches and lights. Appliance outlets shall be in <br />accordance with NEC Table 250-95. <br />2,22. Tests <br />2.22.1 The Electrical Contractor shall test all wiring and equipment for grounds, continuity <br />and proper operation. <br />2.22.2 When directed he shall demonstrate by use of a 500 volt megger, the insulation <br />resistance of any circuit or group of circuits. <br />2.22.3 Where such tests indicate the possibility of faulty insulation, the Electrical <br />Contractor shall locate the point or points of such faulty insulation and shall pull out <br />the faulty conductor or conductors, replace same with new and demonstrate the <br />elimination of faults. <br />2.22.4 The provisions of article 110 of the NEC shall be used as a guide for this test. <br />3. Execution <br />3.1. General: <br />3.1.1 Temporary Electric Service: Install and maintain 120/240 volt, 1 phase, 3 wire, 200 <br />amp temporary service for construction purposes. Power consumption cost shall be <br />paid by Contractor. Installation shall comply with OSHA, NEC and all local <br />requirements. <br />3.1.2 The locations of the outlets, switches and convenience outlets shall be <br />approximately as shown on the drawings and as specified, but exact locations shall <br />be as directed by Publix Field Representative. The running of all circuits, switch <br />legs and conduits is purely diagrammatic. Do not scale from Drawings. <br />3.13 Rigging and hoisting that is incidental to the electrical portion of the Work shall be <br />performed by the Electrical Contractor. This shall include the hoisting of equipment <br />supplied by both the Electrical Contractor and Publix that are installed by the <br />Electrical Contractor. <br />3.1.4 Coordinate this work with other trades so that interference between the trades can be <br />avoided. <br />3.1.5 All channels, angles and other members for the installation and support of the <br />electrical equipment shall be furnished and installed by the Electrical Contractor. <br />3A.6 The attachment of boxes, conduit, hangers, etc. shall be by machine screws or <br />through bolts on steel, expansion bolts in concrete and masonry, and wood screws in <br />wood. Wood composition plugs shall not be used. <br />3.2. Excavation and Backfilling: <br />3.2.1 Do all excavating required to install any underground conduit and after the same are <br />in place and tested and approved. Thoroughly tamp earth around conduits and <br />remove excess or spoil earth from premises as directed. <br />3.2.2 Underground conduit must be covered by a minimum of three (3) inches of <br />underslab fill. <br />3.3. Conduit, Raceways, Etc. <br />3.3.1 All metallic non -current carrying components and enclosures of the electrical wiring <br />system are to be bonded and grounded. <br />3.3.2 Furnish all necessary fittings and supports to make the raceways or busways fit the <br />building structure and equipment. Raceway size shown or called for are minimum. <br />The Electrical Contractor shall verify all raceway sizes with the dimensions of the <br />particular cable to be installed. <br />3.3.3 All exposed raceways and conduit shall be neatly installed perpendicular or parallel <br />to walls and floors. Concealed conduit may run diagonally in the horizontal <br />direction. No exposed conduit is allowed in sales area or work rooms (except where <br />required in exposed structure areas of stores without ceilings.) <br />3.3.4 All raceways shall be supported by approved types of galvanized wall brackets, <br />ceiling trapeze hangers, pipe hangers or pipe straps. Perforated metal strap or tie <br />wire shall not be used for any conduit or raceway. <br />3.3.5 All conduit located in the attic may be EMT, and must be installed within the area <br />provided for on Drawings. <br />3.3.6 Areas for work of various trades: Conform to locations as defined in Section 01010. <br />3.3.7 All conduit located underground may be PVC Schedule 40, except as noted on the <br />Drawings or specified herein. <br />3.3.8 All job cut threads shall be given a coat of rust -inhibitive paint. <br />3.3.9 Caulk where conduit passes through walls, providing approved fire -stopping system <br />where required. Caulk where conduit passes through walk-in freezers and coolers. <br />All cutting in block work must be done with carborundum saw; no chisel or hammer <br />work will be accepted. <br />3.4. Circuit Identification: Label all panels by approved means to identify circuits. Install <br />equipment in cans, as per Drawings. Mark all panels, time clocks, starters, contactors, <br />disconnect devices and main panels on the outside with riveted or approved attached plastic <br />laminated labels V minimum high w/ 3/4" minimum letters of contrasting colors. All <br />circuits shall be identified by typed lettering of contrasting color to tags & covered w/ <br />approved plastic cover. <br />3.5. Installation of Items Supplied by Others: <br />3.5.1 All store fixtures and equipment, including shelf gondolas and check out stands, will <br />be furnished and set in place by Publix, or others, and this Contractor shall make all <br />required electrical connections. Verify items and their locations with Publix's <br />Representative. <br />3.5.2 Meat and Deli Department equipment will all be with plug-in connectors except as <br />indicated on the Drawings. Do not wire direct unless shown on the Drawings or <br />directed by Publix's Representative. <br />3.5.3 All wiring and mounting shall be in cooperation with and under the direction of the <br />Publix's Representative. <br />3.6. Control of Outlets: <br />3.6.1 Branch lighting circuits shall be controlled as shown on the Drawings. <br />3.6.2 Convenience outlets shall have no intermediate control between panels and outlets, <br />unless indicated otherwise. <br />3.7. Connection of Conductors: All joints between conductors shall be connected with <br />approved pressure type, connectors and insulated with scotch 33 tape and friction tape, if <br />insulation is not provided in pressure type connector used. <br />3.8. Sleeves at Fire Retardant Lumber: If fire treated lumber is required by local codes and <br />ordinances, the Electrical Contractor shall provide PVC fitting boxes and piping that <br />penetrate the fire resistant lumber. If the PVC components are not approved by local code, <br />other approved methods must be used to protect against the salt in the fire resistant lumber. <br />3.9. Final Inspection: All of the following items must be completed prior to final inspection. <br />No exceptions will be made and no final payment will be made until all items are <br />completed. <br />3.9.1 Thoroughly clean all parts of the apparatus and equipment. Exposed parts which are <br />to be painted shall be thoroughly cleaned of cement, plaster, and other material and <br />all oil and grease spots shall be removed repaint or touch up as required to make <br />look like new. Such surfaces shall be carefully wiped and all cracks and corners <br />scraped out. <br />3.9.2 Exposed metal work shall be carefully brushed down with steel brushes to remove <br />rust and other spots and touched up with primer. <br />End of Section 16400 <br />Sverdrup <br />SVERDRUF FACILITIES, INC. <br />FLORIDA CORPORATE LICENSE #AA C001291 <br />5750 Major Boulevard, Suite 500, Orlando, FL 32819 <br />(407)903-5001 Fax (407)903-5150 <br />ARCHITECT OF RECORD <br />NAME., FLOYD WILSON McCOLLUM, JR., AIA <br />REGISTRATION: FLORIDA REG. #AR0016162 <br />DATE: 02128101 <br />'tea <br />Revision: <br />Date: By: Description: <br />x <br />C2 <br />N <br />W <br />L <br />O <br />QL <br />ti <br />M <br />r <br />L0 <br />C�4O <br />Liz <br />M <br />I—M00 <br />00 <br />J <br />Q <br />0 <br />U 000 <br />QW_J <br />LL <br />_ <br />Owwrn <br />cn <br />O <br />m <br />J <br />fUJ —0QW <br />Q� z <br />M <br />W <br />_ <br />_! <br />_ <br />D0��� <br />W <br />Z <br />(29 <br />>_ <br />QM0:�Ux� <br />OQOW <br />O <br />F— <br />5 <br />O <br />N <br />m <br />a <br />W <br />U LL m I— <br />cn <br />1-- <br />r_. <br />N <br />Key Plan: <br />Scales: <br />Sverdrup Project No.: 22196390 <br />Drawing Title: <br />SPECIFICATIONS <br />Date: 03/12/99 <br />Designed By: RBJ <br />Drawn By: RM <br />Checked By: FW M <br />awing No.: l <br />PM10 <br />