SYSTEM —SPECIFIC 6.5.3.7 Mechanical Required minimum outdoor air rate is the larger of <br />minimum outdoor air rate or minimum exhaust air <br />rate required by Standard 62.1, Standard 170, or <br />applicable codes or accreditation standards. <br />Outdoor air ventilation systems shall comply with <br />one of the following: a) design minimum system <br />outdoor air provided < 135% of the required <br />minimum outdoor air rate, b) dampers, ductwork, <br />and controls allow the system to supply — the <br />required minimum outdoor air rate with a single <br />set -point adjustment., or c) system includes <br />exhaust air energy recovery complying with <br />Section 6.5.6.1. <br />HVAC 6.8.1-15, 6.8.1-16 Mechanical Electrically operated DX-DOAS units meet ❑ lid ❑ <br />requirements per Tables 6.8.1-15 or 6.8.1-16. <br />2. To be checked by Plan Reviewer <br />Plan Review 4.2.2, 5.4.3.1.1, 5.7 <br />Envelope Plans and/or specifications provide all information ❑ 0 ❑ <br />with which compliance can be determined for the <br />building envelope and document where <br />exceptions to the standard are claimed. <br />Plan Review 4.2.2, 6.4.4.2.1, <br />Mechanical Plans, specifications, and/or calculations provide <br />❑ ❑ <br />6.7.2 <br />all information with which compliance can be <br />determined for the mechanical systems and <br />equipment and document where exceptions to the <br />standard are claimed. Load calculations per <br />acceptable engineering standards and <br />handbooks. <br />Plan Review 4.2.2, 7.7.1, 10.4.2 <br />Mechanical Plans, specifications, and/or calculations provide <br />❑ 11 ❑ <br />all information with which compliance can be <br />determined for the service water heating systems <br />and equipment and document where exceptions <br />to the standard are claimed. Hot water system <br />sized per manufacturer's sizing guide. <br />Plan Review 4.2.2, 8.4.1.1, <br />Project Plans, specifications, and/or calculations provide <br />0 El ❑ <br />8.4.1.2, 8.7 <br />all information with which compliance can be <br />determined for the electrical systems and <br />equipment and document where exceptions are <br />claimed. Feeder connectors sized in accordance <br />with approved plans and branch circuits sized for <br />maximum drop of 3%. <br />Plan Review 4.2.2, 9.4.3, 9.7 <br />Interior Lighting Plans, specifications, and/or calculations provide <br />11❑ <br />all information with which compliance can be <br />determined for the interior lighting and electrical <br />systems and equipment and document where <br />exceptions to the standard are claimed. <br />Information provided should include interior <br />lighting power calculations, wattage of bulbs and <br />ballasts, transformers and control devices. <br />Plan Review 9.7 <br />Exterior Lighting Plans, specifications, and/or calculations provide <br />❑ <br />all information with which compliance can be <br />determined for the exterior lighting and electrical <br />systems and equipment and document where <br />exceptions to the standard are claimed. <br />Information provided should include exterior <br />lighting power calculations, wattage of bulbs and <br />ballasts, transformers and control devices. <br />Insulation 5.8.1.7.3 <br />Envelope Insulation in contact with the ground has —0.3% <br />❑ 0 <br />water absorption rate per ASTM C272. <br />Air Leakage 5.4.3.4 <br />Envelope Vestibules are installed where building entrances <br />separate conditioned space from the exterior, and <br />meet exterior envelope requirements. Doors have <br />self -closing devices, and are > 7 ft apart (> 16 ft <br />apart for adjoinging floor area — 40000 sq.ft.). <br />Vestibule floor area < 7 50 sq.ft. or 2 percent of <br />the adjoining conditioned floor area. <br />EnergyGauge Summit© Fla/Com-2020. Effective Date: Dec 31, 2020 <br />Florida Building Code, Seventh Edition (2020) - Energy Conservation C402.1.1: ASHRAE Energy Cost Budget Option <br />5/19/2022 Page 10 of 24 <br />