Laserfiche WebLink
USER INTERFACE COMPATIBLE ADDRESSABLE DEVICES <br /> LED INDICATORS All feature a polling LED and rotary switches for addressing. <br /> NI -100: Addressable low- profile ionization smoke detector. <br /> • AC POWER (green) NP -100: Addressable low- profile photoelectric smoke detec- <br /> • FIRE ALARM (red) tor. <br /> • SUPERVISORY (yellow) NP-100T: Addressable low- profile photoelectric smoke detec- <br /> • ALARM SILENCED (yellow) tor with thermal sensor. <br /> • SYSTEM TROUBLE (yellow) NH -100: Fast - response, low- profile heat detector. <br /> • MAINTENANCE/PRESIGNAL (yellow) NH -100R: Fast - response, low- profile heat detector with rate- <br /> • DISABLED (yellow) of -rise option. <br /> • BATTERY FAULT (yellow) ND -100: Photoelectric low -flow duct smoke detector. <br /> • GROUND FAULT (yellow) ND -100R: Photoelectric low -flow duct smoke detector with <br /> relay option. <br /> KEYPAD CONTROLS NMM -100: Addressable Monitor Module for one zone of nor- <br /> • ACKNOWLEDGEJSTEP malty -open dry- contact initiating devices. Mounts in standard <br /> • ALARM SILENCE 4.0" (10.16 cm.) box. Includes plastic cover plate and end -of- <br /> • DRILL line resistor. Module may be configured for either a Style B <br /> • SYSTEM RESET (lamp test) (Class B) or Style D (Class A) IDC. <br /> NDM -100: Dual Monitor Module. Same as NMM -100 except it <br /> • 16 -key alpha- numeric pad (similar to telephone keypad) provides two Style B (Class B) only IDCs. <br /> • 4 cursor keys NMM -100P: Miniature version of NMM -100. Excludes LED <br /> • ENTER and Style D option. Connects with wire pigtails. May mount in <br /> device backbox. <br /> ORDERING OPTIONS NZM -100: Similar to NMM -100, but may monitor up to 20 con - <br /> NFW2- 100(E) 198 -point addressable Fire Alarm Control ventional two -wire detectors. Requires resettable 24 VDC <br /> Panel, one SLC loop. Includes 80- character LCD display, sin- <br /> power. Consult factory for compatible smoke detectors. <br /> gle printed circuit board mounted on chassis, and cabinet. NC -100: Addressable Control Module for one Style Y/Z <br /> 4XTM Reverse Polarity Transmitter Module: Provides (Class B /A) zone of supervised polarized Notification Appli <br /> supervised output for local energy municipal box transmitter, ances. Mounts directly to a 4.0" (10.16 cm.) electrical box. <br /> alarm, and trouble. Notification Appliance Circuit option requires external 24 VDC <br /> DP- 9692B: Optional dress panel for FireWarden - 100 to power notification appliances. <br /> NC -100R: Addressable relay module containing two isolated <br /> TR -CEB: Trim Ring for semi -flush mounting. sets of Form -C contacts, which operate as a DPDT switch. <br /> BB -26: Battery backbox, holds up to two 26 AH batteries and Mounts directly to a 4.0" (10.16 cm.) box, surface mount using <br /> CHG -75. the SMB500. <br /> NFS -LBB: Battery box, houses two 55 AH batteries. NOT BG12LX: Addressable manual pull station with interface <br /> CHG -75: Battery charger for lead -acid batteries with a rating module mounted inside. <br /> of 25 to 75 AH. N100 -ISO: Fault Isolator Module. <br /> CHG -120: Remote battery charging system for lead -acid bat- SMB500: Used to mount all modules except the NMM -100P. <br /> teries with a rating of 55 to 120 AH. Requires additional NFS- NOTE: For more information on Compatible Addressable Devices <br /> LBB for mounting. for use with the FireWarden - 100-2, see the following data sheets <br /> NOTE: CHG -120 or CHG -75 required for batteries larger than (document numbers): N100 -S0 (DN- 6994), NP- 100 /NP -100T <br /> 18AH. (DN- 6995), NI -100 (DN- 6996), NH- 100/NH -100R (DN- 6997), ND- <br /> BAT Series: Batteries, see data sheet DN 6933. 100/ND -100R (DN- 7006), NMM-100/NMM-100P/NDM- 100 /NZM- <br /> 100 (DN- 6999), NC- 100/NC -100R (DN- 7000), and NOT- BG12LX <br /> XRM- 24(E): Optional transformer. Increases system power to (DN- 7001). <br /> 6.6 amps. Use XRM -24E with FireWarden - 100 -2E. <br /> PRT /PK- CABLE: Cable printer /personal computer interface <br /> cable. <br /> PRN -6: UL listed compatible event printer. Uses tractor -fed <br /> paper. <br /> COMPATIBLE ANNUNCIATORS <br /> ACM -8R: Relay module provides 8 Form -C 5.0 amp relays. <br /> ACM Annunciator Series: LED -type fire annunciators capa- <br /> ble of providing up to 99 software zones of annunciation. Avail- <br /> able in increments of 16 or 32 points to meet a variety of <br /> applications. <br /> LDM Graphic Series: Lamp Driver Module series for use <br /> with custom graphic annunciators. <br /> FDU -80 (Liquid Crystal Display) point annunciator: <br /> 80- character, backlit LCD -type fire annunciators capable of <br /> displaying English- language text. <br /> NOTE: For more information on Compatible Annunciators for use <br /> with the FireWarden - 100-2, see the following data sheets (docu- <br /> ment numbers) ACM -8R (DN- 3558), ACS/ACM Series (DN- 0524), <br /> LDM Series (DN- 0551), FDU -80 (DN- 6820). <br /> Page 2 of 4 — DN -7101 • 06/02/06 <br />