Laserfiche WebLink
WIRING REQUIREMENTS <br /> While shielded wire is not required, it is recommended that all SLC wiring be twisted -pair to minimize the effects of electrical inter- <br /> ference. Wire size should be no smaller than 18 AWG (0.78 mm and no larger than 12 AWG (3.1 mm The wire size depends <br /> bn the length of the SLC circuit. Use the table below to determine the specific wiring requirements for the SLC. <br /> SLC Wire Distance in Feet Wire Size Wire Type <br /> Requirements (m) <br /> Non- Plenum (FPLR): <br /> Genesis 4315, Belden 5020UL <br /> Twisted -pair, unshielded 10,000 feet (3,048 m) 12 AWG (3.31 mm2) plenum (FPLP): <br /> Genesis 4515, Belden 6020UL <br /> Non- Plenum (FPLR): <br /> Genesis 4313, Belden 5120UL <br /> Twisted -pair, unshielded 8,000 feet (2,438 m) 14 AWG (2.08 mm2) plenum (FPLP): <br /> Genesis 4513, Belden 6120UL <br /> Non - Plenum (FPLR): <br /> Genesis 4311, Belden 5220UL <br /> Twisted -pair, unshielded 4,875 feet (1,486 m) 16 AWG (1.31 mm2) plenum (FPLP): <br /> Genesis 4511, Belden 6220UL <br /> Non - Plenum (FPLR): <br /> Genesis 4306, Belden 5320UL <br /> Twisted -pair, unshielded 3,225 feet (983 m) 18 AWG (0.821 mm2) plenum (FPLP): <br /> Genesis 4506, Belden 6320UL <br /> FireWarden -100 -2 Wire Requirements <br /> DN -7101 • 06/02/06 — Page 3 of 4 <br />