Laserfiche WebLink
STROBE Operating Specifications <br /> The strobe shall be a System Sensor SpectrAlert Advance • Standard operating temperature: 32 °F to 120 °F (0 °C to 49 °C). <br /> Model listed to UL 1971 and shall be approved for fire • K Series operating temperature: —40°F to 151 °F (-40 °C to <br /> protective service. The strobe shall be wired as a primary-sig- 66 °C). <br /> naling notification appliance and comply with the Americans with <br /> Disabilities Act requirements for visible signaling appliances, Humidity range: 10% to 93% non condensing (indoor products). <br /> flashing at 1 Hz over the strobe's entire operating voltage range. • Strobe flash rate: 1 flash per second. <br /> The strobe light shall consist of a xenon flash tube and associ- • Nominal voltage: regulated 12 VDC /FWR or regulated 24 <br /> ated lens /reflector system. VDC /FWR. NOTE: Full Wave Rectified (FWR) voltage is a <br /> HORN /STROBE COMBINATION non- regulated, time - varying power source that is used on <br /> some power supply and panel outputs. <br /> The horn /strobe shall be a System Sensor SpectrAlert Advance • Operating voltage range: 8 V to 17.5 V (12 V nominal); or <br /> Model listed to UL 1971 and UL 464 and shall be 16 V to 33 V (24 V nominal). NOTE: P, S, PC, and SC rod - <br /> approved for fire protective service. The horn /strobe shall be ucts will operate at 12 V nominal only for 15 cd and 15/75 cd. <br /> wired as a primary- signaling notification appliance and comply Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821 mm'). <br /> • with the Americans with Disabilities Act requirements for visible <br /> signaling appliances, flashing at 1 Hz over the strobe's entire • Ceiling -mount dimensions (including lens): 6.8" diameter <br /> operating voltage range. The strobe light shall consist of a x 2.5" deep (17.3 cm diameter x 6.4 cm deep). <br /> xenon flash tube and associated lens /reflector system. The horn • Wall -mount dimensions (including lens): 5.6" H x 4.7" W x <br /> shall have three audibility options and an option to switch 2.5" D (14.2 cm H x 11.9 cm W x 6.4 cm D). <br /> between a Temporal 3 pattern and a Non - Temporal (continuous) • Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x <br /> pattern. These options are set by a multiple position switch. On 11.9 cm W x 3.3 cm D). <br /> four -wire products, the strobe shall be powered independently of <br /> the sounder. The horn on horn /strobe models shall operate on a Agency Listings and Approvals <br /> coded or non -coded power supply. <br /> OUTDOOR PRODUCTS The listings and approvals below apply to SpectrAlert Advance <br /> Selectable Output Notification Devices. In some cases, certain <br /> SpectrAlert Advance outdoor horns, strobes and horn /strobes modules may not be listed by certain approval agencies, or list - <br /> shall be listed for outdoor use by UL and shall operate between ing may be in process. Consult factory for latest listing status. <br /> —40 °F and 151 °F (-40 °C and 66 °C). The products shall be listed • UL Listed: file S4011 (HR_, HW , P2_, P4_, PC2, <br /> for use with a System Sensor outdoor /weatherproof backbox PC4 models); file S5512 (models SCR, SCRH, SCW, <br /> with half -inch and three - fourths -inch conduit entries. SCWH, SR, SRI-I, SW, SWH); file S3593 (SCRHK, SCRK, <br /> SYNCHRONIZATION MODULE SRHK, SRK). <br /> The module shall be a System Sensor Sync•Circuit • ULC Listed: file CS1099 (HRA, HRKA); file CS1089 (typi- <br /> listed to UL 464 and shall be approved for fire protective service. calla Canadia n data <br /> "A" , with exception n s specific strns See <br /> The module shall synchronize SpectrAlert strobes at 1 Hz and Canadian s sheet for listings and d specifications. <br /> horns at Temporal 3. Also, while operating the strobes, the mod- FM approved. <br /> • <br /> ule shall silence the horns on horn /strobe models over a single • MEA approved: file 452 -05 -E. <br /> pair of wires. The module shall mount to a 4.688" x 4.688" x • CSFM approved: file 7125 - 1653:186 (SCR, SCRH, SCW, <br /> 2.125" (11.906 x 11.906 x 5.398 cm) backbox. The module shall SCWH, SR, SRH, SW, SWH); file 7125- 1653:188 P2, <br /> also control two Style Y (class B) circuits or one Style Z (Class P4_, PC2_, PC4 models); file 7135 - 1653:189 (HR, HRK, <br /> A) circuit. The module shall synchronize multiple zones. Daisy- HWj; file 7300 - 1653:187 (SCRHK, SCRK, SRHK, SRK). <br /> chaining two or more synchronization modules together will syn- <br /> chronize all the zones they control. The module shall not oper- <br /> ate on a coded power supply. <br /> Strobe Current Draw, Horn Current Draw, <br /> UL Maximum (mA RMS) UL Maximum (mA RMS) <br /> 8 -17.5V 16 -33V 8 -17.5V 16 -33V <br /> Sound <br /> Candela DC FWR DC FWR Pattern dB DC FWR DC FWR <br /> 15 123 128 66 71 Temporal High 57 55 69 75 <br /> 15/75 142 148 77 81 Temporal Medium 44 49 58 69 <br /> Standard 30 NA N/A 94 96 Temporal Low 38 44 44 48 <br /> Candela 75 NA NA 158 153 Non - temporal High 57 56 69 75 <br /> Range 95 NA NA 181 176 Non - temporal Medium 42 50 60 69 <br /> 110 NA NA 202 195 Non - temporal Low 41 44 50 50 <br /> 115 NA NA 210 205 Coded High 57 55 69 75 <br /> 135 NA NA 228 207 Coded Medium 44 51 56 69 <br /> High 150 NA NA 246 220 Coded Low 40 46 52 50 <br /> Candela <br /> Range 177 NA NA 281 251 <br /> 185 NA NA 286 258 <br /> Page 2 of 4 — DN- 7087:A • 10/18/06 <br />