<br /> General
<br /> The LCD-160 is a 640-character Liquid Crystal Display(LCD)
<br /> annunciator and remote control for the NOTIFIER NFS-3030/
<br /> NFS2-3030 Fire Alarm Control Panel (FACP) The LCD-160
<br /> will mimic the top portion (160 characters) of the NFS-3030/
<br /> NFS2-3030's 640-character display. This provides the event
<br /> and preprogrammed custom messages as displayed on the I
<br /> main panei. The full screen contains soft key functions, and ',i l;�i�,�`,,
<br /> can display other panei information.
<br /> ;�,p' �:��.
<br /> �- .. .��¢;�" ,..
<br /> LCD-160 Features �-rv� �.��"�
<br /> ° �:� .���� `
<br /> • 640-character Liquid Crystal Display with backlit control. ��r: ;�r°.K%
<br /> • On-board input, output, and status indicators to support C,:�&�r:-`:� ,�;,,,,,�,�.,��,.,,�;,�. �c„a�,c�;
<br /> diagnostics. a; ,_ �w; •v °
<br /> • Software upgrades and foreign-languages character sets � �a�;�;°�;� �.'�,.�'. �' ``' ° �;�
<br /> via serial port from a panel or other device using the rr�` ��{` ��'� �,
<br /> Remote Data Port(RDP)interface.Upgrades do not require ^� �'���'��� , `�', �
<br /> the replacement of any programmable devices.
<br /> • Rubberized keypad. . �
<br /> • Input for AKS-1 key switch.
<br /> • Fits in two ACS annunciator module locations.
<br /> • Display and Control Center(DCC)participation�ndication.
<br /> 6940cov.)P9
<br /> RDP Interface
<br /> Any communication between the control panel and any RDP RDP BUS WIR/NG SPECIFICATIONS
<br /> device,such as the LCD-160,occurs over an RDP interiace.
<br /> • RDP interface communication is supervised by the FACP W�ring distance: 4000 feet (1219.2 m) at 18 AWG (0.78
<br /> and the LCD-160 mrr�) between the panel and the last device on the RDP bus
<br /> RDP bus can drive up to 32 RDP devices.The FACP must �subject to system's power restrictions).
<br /> • be at one end of the bus;the last RDP device on the circuit W�ring size: 18 to 12 AWG (0.78 to 3.1 mmz) twisted-pair
<br /> must have an enabled end-of-line resistor.' cable,with characteristic impedance of 120 ohms t 20%.
<br /> • Each LCD-160 on the bus requires a non-resettable 24 Wire resistance: Limit total wire resistance to 100 ohms on
<br /> VDC power connection. The power circuit is inherently the RDP bus, and 10 ohms on the RDP device power circuit.
<br /> supervised and a loss of power registers as a communica- Unloaded resistance between RDP connectors must be
<br /> tion failure at the control panei. greater than 1 K ohm.A remote power supply is required if total
<br /> • The LCD-160 can be powered by a regulated remote power Power wiring resistance exceeds 10 ohms.
<br /> supply listed for fire-protective signaling use. If the 24 VDC NOTES:1)DO NOT RUN CABLE adjacent to,or in the same con-
<br /> power comes from a non-power-limited source, it must duit as: 120 VAC service;'nois�'e/ectrica/circuits that are power-
<br /> remain separate from the power-limited RDP bus. ing mechanica/bells or horns;audio circuits above 25 Vrms;motor
<br /> control circuits;SCR power circuits;or non-power-limited circuits.
<br /> 5 ecifications 2)Reler to LCD-160 Manual,document no.5T 850,if RDP devices
<br /> p are to be mounted in SEPARATE CAB/NETS or powered by
<br /> Input supply voltage(TB2): Regulated, filtered 24 VDC via REMOTE POWER SUPPLIES.
<br /> non-resettable power supply intertace listed for fire-protective �MPERATURFJHUM/DITY RANGE:
<br /> signaling use. Sources can be: panels with integrated power
<br /> supplies, main power supplies (AMPS-24, etc.), auxiliary This system meets NFPA requirements for operation at 0—
<br /> power suppties (APS-6R, etc.); or a compatible accessories 49°C/32—120°F and at a relative humidity 93%t 2%RH
<br /> output. If RDP devices are to be powered by separate power (noncondensing)at 32°C t 2°C(90°F t 3°F). However,the
<br /> supplies, a common reference connection must be estab- useful life of the system's standby batteries and the electronic
<br /> lished. components may be adversely affected by extreme tempera-
<br /> Data communications port(T61): Power-limited RDP inter- ture ranges and humidity. Therefore,ii is recommended that
<br /> face. this system and its peripherals be installed in an environment
<br /> Current draw: Standby current 0.300 A with backlight on, with a normal room temperature of 15--27°C/60—80°F
<br /> 0.075 A with backlight off.A/arm current:0.325 A with back-
<br /> �ight on,all LEDs active.
<br /> DN-6940:A•12/Ot/O6—Page 1 of 4