• Maximum current charge. 1.5 A. $tandards and Codes <br /> • Maximum battery capacity' 18 AH. The FCP�-24S6 and FCPS-24S8 comply with the following <br /> standards: <br /> Appiications • NFPA 72 National Fire Alarm Code. <br /> Example 1: Expand notification appiiance power an additional . UL 864 Standard for Control Units for Fire Afarm Systems <br /> 6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four (NAC expander mode) <br /> Class B (Sryle Y) outputs or four Class A (Sryle Z) outputs . UL i481 Power Supplies for Fire Alarm Systems <br /> (using ZNAC-4) For example,the FACP notification appliance <br /> circuits will activate the FCPS when reverse-polarity activation <br /> occurs. Trouble conditions on the FCPS are sensed by the agency L'estings and Approvafs <br /> FACP through the notification appiiance circuit. These listings and approvals appiy to the modules specified in <br /> Example 2: Use the FCPS to expand auxiliary regulated 24- this document. In some cases,certain modules or applications <br /> volt system power up to 4 0 A (FCPS-24S6) or up to 6.0 A may not be listed by certain approval agencies, or fisting may <br /> (FCPS-24S8) Both resettable and non-resettabie power be in process. Consult factory for Iatest iisting status. <br /> options are avaifabie. Resettable outputs are created by con- . UL Listed: S635,S674 <br /> necting the resettable output from the FACP to one or both of ULC Listed:S635(FCPS-24S6C& FCPS-24S8C} <br /> the FCPS inputs. � <br /> Example 3: Use addressable control modules to activate the <br /> • CSFM Approved: 7315-0028:225 <br /> FCPS instead of activating it through the FACP notification ' MEA: 299-02-E <br /> appliance circuits.This typically allows for mounting the FCPS • FM Approved <br /> at greater distances` away from the FACP while expanding <br /> system architecture in various applications. Ordering Information <br /> For example, an addressable control module is used to acti- FCPS-24S6: 6.0 A, 120 VAC remote charger power supply. <br /> vate the FCPS,and an addressable monitor module is used to Inciudes main printed circuit board, transformers, enclosure <br /> sense FCPS troubie conditions. Locai au�uliary power output ��5"H x 14.5"W x 2.75"D[cm:38 1 H x 36.83W x 6.985D]),and <br /> from the FCPS provides power to the addressable control installation instructions. <br /> module. <br /> FCPS-24S6C: Same as above, ULC-listed. <br /> 'NOTE:Addressable FACPs are capable of locating control and <br /> monitor modules at distances of up to 12,500 feet(3,810 meters). FCPS-24S6R: Same as FCPS-24S6 with red enciosure. <br /> FCPS-24S6E: 6 0 A, 240 VAC remote charger power supply. <br /> Sync Foilower/Generator Note Includes main printed circuit board, transformers, enclosure <br /> In some installations, it is necessary to synchronize the flash ��5"H x 14.5"W x 2.75"D[cm:38.1 H x 36.83W x 6.985D]),and <br /> timing of all strobes in the system for ADA compliance. �nstallation instructions. <br /> Strobes accomplish this by monitoring very short timing pulses FCPS-24S8: 8.0 A, 120 VAC remote charger power supply. <br /> on the NAC power which are created by the FACP When Includes main printed circuit board, transformers, enclosure <br /> installed at the end of a NAC wire run, the FCPS-24S6/-24S8 (15"H x 14.5"W x 2.75"D[cm:38.1 H x 36.83W x 6.985D]),and <br /> can track (i.e. "follow") the strobe synchronization timing installation instructions. <br /> pulses on the existing NAC wire run.This maintains the overall FCPS-24S8C Same as above, ULC-listed. <br /> system flash timing of the additional strobes attaches to the <br /> FCPS. FCPS-24SSR: Same as FCPS-24S8 with red enclosure. <br /> When the FCPS-24S6/-24S8 is configured(via DIP switch set- FCPS-24S8E: 8.0 A, 240 VAC remote charger power suppiy. <br /> tings) as a"sync follower,"the FCPS's NAC outputs track the Incfudes main printed circuit board, transformers, enclosure <br /> strobe synchronization pulses present at the FCPS's sync (15"H x 14 5"W x 2.75"D[cm:38.1 H x 36.83W x 6.985Dj),and <br /> input terminal.The pulses originate from an upstream FACP or �nstallation instructions. <br /> other power supply. ZNAC-4: Class A(Style Y)NAC option module. <br /> When the FCPS-24S6/-24S8 are configured (via DIP switch EOLR-1: 12124 VDC end-of-line relay for monitoring four-wire <br /> settings) as a "sync generator," the FCPS's sync input termi- smoke detector power <br /> �als are not used. Rather, the FCPS is the originator of the gAT 1270: Battery, 12-volt, 7.0 AH (two required, see BAT <br /> strobe synchronization pulses on the FCPS's NAC outputs. In Series data sheet DN-6933) <br /> °sync generator"mode,the sync type(System Sensor, Whee- <br /> fock,or Gentex)is selectabie via DIP switch settings. PS-1270: Battery, 12-volt, 7.0 AH (two required, see PS <br /> Series data sheet DN-1109) <br /> System Sensor�and NOTIFIEFt�are registered trademarks of Honeyweli <br /> Intemational Inc. <br /> C�2009 by Honeywell Intemational Inc.All rights reserved.Unauthorized use <br /> of this document is strictly prohibited. <br /> 1S0 �oo� This document is not intended to be used for installation purposes. <br /> We try to keep our product information up-to-date and accurate. <br /> We cannot cover all specific applications or anticipate all requirements. <br /> ��6� All specifications are subjed to change without notice. <br /> QiALITT SrSTEMS MadeintheU.S.A. <br /> For more information,contact Nofrfier Phone:(203)484-7161,FAX.(203)484-7118. <br /> www.not'rfier.com <br /> Page 2 of 2—dn-6927:a•04/30/09 <br />