STROBE Operating Specifications
<br /> The strobe shall be a System Sensor SpectrAlert Advance . Standard operating temperature: 32°F to 120°F (0°C to
<br /> Model listed to Ul 1971 and shali be approved tor fire 490��
<br /> protective service.The strobe shali be wired as a primary-sig- K Series operating temperature: -40°F to 151°F (-40°C
<br /> naling notification appliance and comply with the Americans � to 66°C).
<br /> with Oisabilities Act requirements for visible signaling appli-
<br /> ances, flashing at 1 Hz over the strobe's entire operating volt- • Humidity renge: 10% to 93% non-condensing (indoor
<br /> age range.The strobe light shall consist of a xenon flash tube products).
<br /> and associated lens/reflector system. • Strobe tlash rate: 1 flash per second.
<br /> HORN/STROBECOM8INATlON � Nominal voltage: regulated 12 VDC/FWR or regulated 24
<br /> VDC/FWR. NOTE: Full Wave Rectified(FWR) voltage is a
<br /> The horn/strobe shall be a System Sensor SpectrAlert non-regulated, tirne•varying power source that is used on
<br /> Advance Model listed to UL 1971 and UL 464 and some power supply and panel outputs.
<br /> shall be approved for fire protective service. The horn/strobe Operating voltage range:8 V to 17.5 V(12 V nominal);or
<br /> shall be wired as a primary-signaling notification appliance � �6 V to 33 V(24 V nominal).IVOTE:P,S,PC,and SC prod-
<br /> and comply with the Americans with Disabilities Act require- ucts wil!operate at i2 V nomina!only for f5 cd and 15/75
<br /> ments for visible signaling appliances,flashing at 1 Hz over the cd,
<br /> strobe's entire ope�ating voltage range. The strobe fight shall
<br /> consist of a xenon flash tube and associated lens/reflector sys- • Input terminal wire gauge: 12 to 18 AWG (3.31 to 0 821
<br /> tem.The horn shall have three audibiliry options and an option mm2).
<br /> to switch between a Temporal 3 pattern and a Non-Temporal • Celling-mount dimensions (including lens): 6.8" diame-
<br /> (continuous)pattern.These options are set by a multiple posi- ter x 2.5"deep(17 3 cm diameter x 6 4 cm deep)
<br /> tion switch.On four-wire products,the strobe shall be powered . yyall•mount dimensions(including lens):5.6"H x 4 7"W
<br /> independently of the sounder The horn on horn/strobe models x 2.5"D(14.2 cm H x t 1.9 cm W x 6.4 cm D).
<br /> shali operate on a coded or non-coded power supply. Horn dlmensions: 5.6" H x 4 7"W x 1.3" D(14.2 cm H x
<br /> OtJTDOOR PRODUCTS • 11.9 cm W x 3.3 cm D)
<br /> SpectrAlert Advance outdoor horns,strobes and horn/strobes
<br /> shall be iisced ror oucdoor use by UL and snan operate Agency Listings and Approvals
<br /> between -40°F and 151°F (-40°C and 66°C). The products The listings and approvals below appiy to SpectrAlert Advance
<br /> shall be listed for use with a System Sensor outdoor/weather- Selectable Output Notification Devices. In some cases,certain
<br /> proof backbox with half-inch and three-fourths-inch conduit modules may not be listed by certain approval agencies, or
<br /> entries. listing may be in process. Consult factory for latest listing sta-
<br /> SYNCHRONlZATION MODULE tus.
<br /> The module shall be a System Sensor Sync�Circuit MDL3R or ' UL Listed: S4011 (HR_, HW_, P2__, P4_, PC2_,
<br /> MDL3W listed to UL 464 and shall be approved for fire protec- PC4_ models); 55512 (models SCR, SCRH, SCW,
<br /> tive service.The module shall synchronize SpectrAlert strobes SCWH, SR, SRH, SW, SWH); S3593 (SCRHK, SCRK,
<br /> at 1 Hz and horns at Temporal 3. Also, while operating the SRHK,SRK).
<br /> strobes, the module shall silence the horns on horn/strobe � ULC Listed: S4011 (HRA, HRKA); S5512 (typically "A"
<br /> models over a single pair of wires.The module shall mount to models, with exception of outdoor strobes). See Canadian
<br /> a 4.688"x 4.688"x 2.125"(11.906 x 11.906 x 5.398 cm)back- data sheet la listings and specilications.
<br /> box. The module shall a{so control iwo Style Y (class B)cir- . FM approved
<br /> cuits or one Style Z (Class A) circuit. The module shall . MEA.452-05-E
<br /> synchronize multiple zones. Oaisy-chaining two or more syn-
<br /> chronization modules together will synchronize all the zones • CSFM: 7125-1653:0166 (SCR, SCRH, SCW, SCWH, SF,
<br /> they control. The module shall not operate on a coded power SRH,SW,SWH); 7300-1653:0188(P2_,P4_, PC2_, PC4_
<br /> supply. modules); 7135-1653:0189 (HR, HRK, HW); 7300-
<br /> 1653:d187(SCRHK,SCRK,SRHK,SRK).
<br /> Strobe Current Draw, Florn Current Draw,
<br /> UL Maximum (mA RMS) UL Maximum (mA RMS)
<br /> 8-17.5V 16-33V Sound 8-17.5V 16-33V
<br /> Candela Pattern dB
<br /> DC FWR DC FWR DC FWR DC FWR
<br /> 15 123 1 66 71 Temporal High 57 55 69 75
<br /> 15/75 142 148 77 81 Temporal Medium 44 49 58 69
<br /> Standard 30 NA NlA 94 96 Tempora� Low 38 44 44 46
<br /> Ca�dela 75 NA NA 158 153 Non-temporal High 57 56 69 75
<br /> Range g5 NA NA 181 176 Nan-temporal Medium 42 50 60 69
<br /> 110 NA NA 202 195 Non-temporal Low 41 44 50 50
<br /> 115 NA NA 210 205 Coded igh 57 55 69 75
<br /> 135 NA NA 228 207 Coded Medium 44 51 56 69
<br /> High 150 NA NA 246 220 Coded Low 40 46 52 50
<br /> Candela
<br /> Range »� NA NA 281 251
<br /> 185 NA NA 286 258
<br /> Page 2 0(4—DN-7067 C 1•11/9/11