2 Activation of any supervisory device as indicated on the engineering drawings <br /> shall initiate a "supervisory"condition at the control panel and remote annunciator <br /> for that specific device. The"supervisory" indication shall describe the nature of <br /> the condition and specific address and alphanumeric description of the device <br /> affected. The DACT shall transmit point specific"supervisory"conditions to and <br /> approved UL central station as indicated on engineering drawings <br /> 3. Activation of any alarm device as indicated on the engineering drawings shall <br /> initiate an "alarm"condition at the control panel and remote annunciator for that <br /> specific device. The "alarm" indication shall describe the nature of the condition <br /> and specific address and alphanumeric description of the device affected The <br /> DACT shall transmit point specific"alarm" conditions to an approved UL central <br /> station as indicated on engineering drawings. <br /> 4. Initiation of an "alarm"condition shall result in the following functions to be <br /> performed by the system: <br /> a. Initiate an alarm indication on the control panel by tone and illuminate the <br /> corresponding device specific alphanumeric LCD description Manually <br /> activating the"Alarm Silence"shall silence the tone at the panel The <br /> alarm alphanumeric display shall remain "On"at the control panel until <br /> the condition causing the alarm has been cleared and reset. An <br /> additional alarm reported to the panel subsequent to activating the"Alarm <br /> Silence" shall reactivate the control panel tone. <br /> b Activate the audible and visual notification appliances throughout the <br /> Hobby Lobby. <br /> c Provide "Alarm Silence"feature at the contro� panel in accordance with all <br /> applicable codes and design standards as shown on the engineering <br /> drawings <br /> d. Transmit"alarm" conditions to an approved off-site monitoring station as <br /> indicated on engineering drawings. <br /> 5 Actuation of alarm notification appliances, fire safety functions, and annunciation <br /> at the protected premises shall occur within ten (10)seconds after the activation <br /> of an initiating device <br /> 6 Additional indications, notifications, enabling functions or control functions shall <br /> be as indicated on the engineering drawings <br /> 1.05 QUALITY ASSURANCE <br /> A. All work shall meet the requirements of the Owner, Engineer and Authority Having <br /> Jurisdiction (AHJ) <br /> B All equipment and components shall be UL listed for the actual intended use, unless <br /> hereinafter specifically excluded from such a listing. <br /> C. Installation and supervision of installation shall be in strict compliance with the <br /> requirements of the regulations, licenses, and permits for fire alarm system installers in <br /> this jurisdiction. <br /> Hobby Lobby—Zephyrhills, FL FIRE ALARM SYSTEM <br /> Issued for Permit—October 23, 2013 16720 - 3 <br />