D. All wiring conductors and conduits shall be installed in a neat and workmanlike manner at . <br /> right angles to the building walls, floors and ceilings, and supported from the building <br /> structure at intervals compliant with NEC requirements. <br /> E All power limited wiring conductors for the fire alarm system shall be installed in conduit in <br /> the following locations: <br /> 1 Seven (7)feet or less above the finished floor. <br /> 2. Electrical and mechanical rooms. <br /> 3. Concealed above ceilings or in partitions. <br /> 4. Areas subject to physical damage. <br /> 5. Where required by app►icable codes. <br /> 6 Wiring conductors in finished areas that cannot be concealed are allowed to be <br /> installed in surface-mounted metallic raceway only upon approval of the Owner's <br /> Representative. <br /> 7. Where indicated on the engineering drawings. <br /> F All non-power limited wiring conductors for the fire alarm system shall be installed in <br /> conduit. <br /> G. Power limited wiring conductors for the fire alarm system are not required to be installed <br /> in conduit in the following locations: <br /> 1 More than seven (7)feet above the finished floor. <br /> 2 Above lay-in ceilings. <br /> 3. Concealed in ceilings or partitions not subject to damage. <br /> 4 Where indicated on the engineering drawings. <br /> H Exposed wiring conductors and conduits shall be concealed from public view at all <br /> locations by routing on the inside of joists, above lay-in ceilings, over girders, within <br /> partitions or in any other manner acceptable to the Owner's Representative. <br /> I Wiring conductors and conduits installed above lay-in ceilings shall be supported from the <br /> building structure and shall not be permitted less than nine (9) inches above or behind <br /> removable panels or ceiling tiles <br /> J Exposed wiring conductors shall be supported from the building structure at intervals of <br /> no more than five (5)feet. <br /> K. All wiring conductors shall be tagged at all junction points and shall test free from grounds <br /> or crosses between conductors. <br /> L. Power-limited wiring conductors shall not be installed in conduits with electric light, power <br /> Class 1, non-power-limited fire alarm and medium power network-powered broadband <br /> communications circuits <br /> M Final connections between equipment and the wiring system shall be made under direct <br /> supervision of the qualified installation personnel. If other personnel are required by the <br /> AHJ to be present during final connections, this shall not relieve the Contractor of the <br /> responsibi►ity of providing qualified installation personnel. <br /> N Fire alarm cabling shall not be painted <br /> Hobby Lobby—Zephyrhills, FL FIRE ALARM SYSTEM <br /> Issued for Permit—October 23, 2013 16720 - 13 <br />